troubleshooting
Problem
Cause
Solution
1. No discharge
a. No water
a. Open water supply
b. Excessive water pressure
b. Install regulator if water pressure (with
water running) exceeds 80 PSI
c. Clogged water inlet strainer
c. Disconnect inlet water line and clean
strainer
d. Magnetic valve not functioning
d. Install valve parts kit
e. Eductor clogged
e. Clean* or replace
2. No concentrate draw
a. Metering tip or eductor has scale
build-up
a. Clean (descale)* or replace
b. Low water pressure
b. Minimum 20 PSI (with water running)
required to operate unit properly
c. Discharge tube not in place
c. Push tube firmly onto eductor discharge
hose barb, or replace tube
d. Concentrate container empty
d. Replace with full container
e. Clogged water inlet strainer
e. Disconnect inlet water line and clean
strainer
f.
Incorrect check valve installation
f. See diagram page 3
g. Air leak in pick-up tube
g. Put clamp on tube or replace tube if brittle
h. Selector out of position
h. Assure selector is in position desired
3. Excess concentrate draw
a. Metering tip not in place
a. Press correct tip firmly into barb on
eductor
4. Failure of unit to turn off
a. Push button stuck
a. Remove button and clean cabinet/button
to remove excess dirt lodged in slide
recess
b. Magnet doesn‘t fully return
b. Make sure magnet moves freely
Replace spring if short of weak
c. Water valve parts dirty or defective
c. Clean or replace with valve parts kit
5. Excess foaming in discharge a. Air leak in pick-up tube
a. Put clamp on tube or replace tube if brittle
Hydro Systems Company
3798 Round Bottom Road
Cincinnati, OH 45244 U.S.A.
Phone
513-271-8800
Fax
513-271-0160
Web
hydrosystemsco.com
Page 6
HYD10099864 Rev A 5/21
* In hard water areas, scale may form inside the discharge end of the eductor, as well as in other areas of the unit that are exposed to water.
This scale may be removed by soaking the eductor in a descaling solution (deliming solution). To remove an eductor located in the cabinet,
firmly grasp water valve and unthread eductor. Replace in same manner. Alternatively, a scaled eductor can be cleaned (or kept from scaling)
by drawing the descaling solution through the unit. Operate the unit with the suction tube in the descaling solution. Operate the unit until
solution is drawn consistently, then flush the unit by drawing clear water through it for a minute. Replace concentrate container and put suction
tube into concentrate.