Technical Data

B-7.1,2,3,4  -Auto, LitePak Panels

www.DouglasLightingControls.com

Components   7.4 

Programmable LitePak Panels 

L i t e P a k

Timed Schedules

n

  Use timed schedules to automatically 

switch lights. 

n

  Remote switches permit occupant 

ON/OFF switching. 

*  If switches are installed, ON schedules 

should not be used, because the switches 
permit the lights to be turned ON only 
when needed. The OFF schedules ensure 
lights are eventually switched OFF. 

Astronomical Control

n

  With longitude, latitude, time zone 

and date, the controller calculates 
the sunset and sunrise times. An 
output can be programmed to 
switch at these calculated times. 

n

  An offset time (± 180 min) can be 

entered to cause the switching to 
occur sooner or later than actual 
sunset and sunrise.

Time-Out Mode

n

  The time-out mode causes a 

controller output to start an internal 
timer when the relay is switched 
ON. Upon time expiry, the output 
switches the relay OFF. 

n

  The time-out mode can be enabled 

and disabled with a time schedule. 
Thus, switches work normally during 
business hours and function with 
time-out mode during closed hours.

Flick Warn

n

  Flick warn feature is used to war n  

occupants that lights will be 
switched OFF in 5 minutes. 
Occupants can cancel the OFF by 
switching the relay again (with 
remote switch or override in panel).

Photometric Control

n

  Connecting WPS-5527K Photo 

Sensor to the LitePak controller 
permits digital entry of light levels. 
Range of sensor: 0-6,500 fcandles

n

  Each output of the controller can 

have unique ON and OFF set points 
for different requirements of a 
lighting group.

Override Switching

n

  To override circuits at the panel, use 

manual on/off levers built into relays. 

n

  Install switch stations at locations 

convenient to occupants. 

n

  To control individual circuits, connect 

switch direct to relay. To control all 
circuits, use group input on controller.

1

2

3

4

5

6

7

8

Schedule enables

time-out mode

during closed hours.

Sw

12

3

6

9

12

3

6

9

After close

Scheduled OFF

AM

PM

12

3

6

9

Late Night

Repeat OFF

PM

OFF signal

12

3

6

9

PM

Flash lights to

warn of OFF

Occupant

has 5 minutes
to cancel OFF

If cancelled,

 lights stay ON

12

3

6

9

PM

Lights ON with
wall switch -
timer starts.

Exit without

switching OFF.

Timer expires,
lights go OFF.

Schedule disables

timed-ON mode for

occupied hours.

Sw

Sw

Sw

Sw

Sw

Sw

Flick Warn Sequence

1

2

3

Sw

4

If no cancel,

 lights turn OFF

12

3

6

9

AM

Sw

At opening,

lights ON*

Time-Out Mode when building is unoccupied

Sensor

Skylight/
Windows

Sunny

Cloudy

Night

Night

Timed OFF

12

3

6

9

FEATURES & APPLICATIONS

When sunny, interior

lights near window or
skylights can be OFF.

When overcast, interior

lights near window or

skylights are turned ON.

When dark, interior

lights near window or

skylights are turned ON.

Time control can be used

to switch lights OFF and

to disable sensor effect.

1

2

3

4

5

1

2

3

Dusk

Dawn

Late

Night

Day

Parking lot and Building
security lights ALL OFF.

Switch exterior

lights ALL ON.

Switch parking lot OFF,

leave wall packs ON.

Before dawn, parking can

go back ON (not shown).

At dawn, ALL OFF.

Wall
Packs

Parking
Lights

Remote Switch Station

8 individuals & 1 Group Sw.

Switches at different locations

10

2

2

2

4

At the panel, use

built-in ON/OFF levers 

Gr

LitePak

LitePak

LitePak

Mode
Change