DOTECH FX3DH Series Manual Download Page 2

ALA

ALB

ALC

ALD

2

A L 1

AL2

AL3

AL4
AL5
AL6
SBA

IN

H
T

HT

HTD

HOP
HST

TOP
TST

HLL

TLL

HHH
SYS

THH

PRG

SEL

23.4

H

C

E

T

O

D

PRG

SEL

23.4

H

C

E

T

O

D

HTX20-FTS-502

dotech,inc

RH : 10~95%RH, 1.2~3.5V
T    :  NTC5K

RH & Temp Sensor

+5V
RH
GND
TH
TH

PRG

SEL

23.4

H

C

E

T

O

D

OUT1
OUT2

HTX20-FTS-502

dotech,inc

RH : 10~95%RH, 1.2~3.5V
T    :  NTC5K

RH & Temp Sensor

+5V
RH
GND
TH
TH

PRG

SEL

23.4

H

C

E

T

O

D

UH2

UL2

St

dF

dF

PV

St

dF/2

dF/2

PV

OUT1
OUT2

FX3DH

FX3DH

FX3DH

FX3DH

OUT1
OUT2

OUT1
OUT2

OUT1
OUT2

Set control sensibility of alarm output. 

Temperature Setting Group

 

The set point is indicated by flickering at every 

    0.5 seconds intervals and this set point can be 

    established by using th

e ▲

 key or

 ▼

 key.

    After changing set point, it displays the current temp.

 

If there’s no input made for a period of 60 seconds during the setting,  

     then it returns back to the run mode automatically.

Run Mode

Set output #1 setup value.

Set output #2 setup value.

Display Current Temp.

Push for 
3 sec.

Output #1 setup value

Output #2 setup value

Setting 1 Group

Run Mode

Set control sensitivity of control output #1.

Setting Range 0 ~ 19.9

Display

Current Temp.

Set control function of 

control output #1.

Select Control Type #1

Select Control 

Type #2

Control Deviation Value #1

ON Delay Time #1

Minimum OFF Time #1

Minimum ON Time #1

Output #1 at Sensor Error

Alarm Deviation Value

Alarm Option

Manual Output Mode Output #1

Push for 3 sec.

No use output function

(Use display mode only.)

Use cooling control only

(Use OVER temperature sensing only.)

Use heating control only

(Use UNDER temperature sensing only.)

Deviation High Limit Alarm

Output is ON when the deviation between 

PV value and SV value is higher than setup 

value of deviation temperature.

Deviation Low Limit Alarm

Output is ON when the deviation between 

PV value and SV value is lower than setup 

value of deviation temperature.

Deviation High & Low Limit Alarm

Output is ON when the deviation between 

PV value and SV value is higher or lower 

than setup value of deviation temperature.

Deviation High & Low Limit Reverse Alarm

Output is OFF when the deviation between 

PV value and SV value is higher or lower 

than setup value of deviation temperature.

Absolute Value High Limit Alarm

Output is ON when PV value is higher than or 
equal as alarm temperature setup value.

Absolute Value Low Limit Alarm

Output is ON when PV value is lower than or 
equal as alarm temperature setup value.

Sensor Open Wire Alarm

Output is ON when sensor wire is opened.

No output within Min. OFF time
after control output #1 OFF.

Output after delaying during setting
delay time in case of control 
output #1 ON.

Set output #1 when sensor is

disconnected or shorted.

e.g) In case of setting as ON, 
output #1 is ON when error occurs.

Maintain ON in spite of OFF 
condition during Min. ON time 
after ON.

Setup range is 0~99.9

General alarm

Standard alarm operation 

without option

Maintain alarm

Maintain output ON after 

alarm occurs

Standby alarm

No output at initial operation 

(until achieve the 1st setup value)

Execute both 

ALD 

ALC

at the same time

(-R4 Model)

OFF : Output by temp.

ON : Output by 

MV1

Output continuously regardless setup 

temp. if manual output value is ON 

when manual output mode is ON.

Manual Output Value Output #1 

(-R4 Model)

Select deviation type  #1

e.g)Condition : Cooling mode, 
       setting temp.10.0

, deviation 1.0

+Deviation control : ON at 11.0

 , OFF at 10.0

℃.

±Deviation control : ON at 10.5

 , OFF at 9.5

℃.

+ Deviation control

± Deviation control

Max. Setup Value by User

Min. Setup Value by User

Input max. value settable by user

Possible to set until 100.

Input min. value settable by user

Possible to set until 0.

Simple Trouble Check Point 

Setting Method of control mode 

Use for humidity only

Use for temperature only
Use for humidity and temperature control 

(Output1: humidity control, output2: temperature control)

Humidity and temperature are displayed by every 

2.5 sec. interval in shifts.

Use for humidity control and temperature display.

Humidity Sensor 

Open Wire
Humidity Sensor 

Short Circuit

Temperature Sensor 

Open Wire
Temperature Sensor 

Short Circuit

Minimum range 

for Humidity use

Minimum range 

for Temperature use

Maximum range 

for Humidity use
If the stored value is changed randomly, please re-setup after 

parameter initialization.

maximum range 

for Temperature use

Humidity and temperature are displayed by every

2.5 sec. interval in shifts.

Setup sensor input of setting 2 group.

※ According to user’s setup, FX3DH is able to use humidity only or temperature

   only or for both temperature and humidity. Please use after you setup the 

   parameter of sensor input of setting 2 group.

※ FX3DH controls by measured value which is detected by sensor.   

   If sensor fault alarm occurred as following, please check wiring with sensor

※ In case of the above-mentioned error, it will be normally operated with cancelling error 

   status if the reason of error is solved.

In the case of Humidity display, 
unit will not be displayed.

Distinguishment between Temperature and Humidity.

In the case of temperature display, 

℃ unit is displayed.

Deviation Control(TP mode)

Dehumidification 

(Cooling)Control

OUTPUT ON

when 

TP 

 mode is 

when 

TP 

 mode is 

PN

OUTPUT ON

Humidification

(Heating)Control

Dehumidification 

(Cooling)Control

Humidification

(Heating)Control

OUTPUT ON

OUTPUT ON

When it use for Humidity & Temp. control

(Apply HTX20-FTS-502 Temp. & Humidity sensor) 

YELLOW

BLUE

WHITE

BLACK

RED

YELLOW

BLACK

RED

WHITE

BLACK

RED

When it use for Humidity control

(Apply HTX20-FTS-502 Humidity sensor)

When it use for temperature control

(Apply DPR-TH1-ET Temp. sensor) 

※ Set sensor input setting(

IN

) of setting 2 group to 

T

.

※ Set sensor input setting(

IN

) of setting 2 group to 

H

.

※ Set sensor input setting(

IN

) of setting 2 group to 

H

.

※ Set sensor input setting(

IN

) of setting 2 group to 

HT

.

When it use for Humidity control 

(Apply HTX3515 Humidity sensor)

Maintain & standby alarm

Push for

3 sec.

Summary of Contents for FX3DH Series

Page 1: ...ase use with being attached to a dual safety device in case of using for controlling instruments which could be effective to human life or property eg controlling atomic energy medical instruments cars trains flights burners amusement instruments or safety machinery Power AC100 240V 50 60Hz Current MAX 4VA Model Input Output Relay output 2p OUT1 2 250Vac 8 2 A Humidity 1 4V Voltage input 1p Temp N...

Page 2: ... alarm Standard alarm operation without option Maintain alarm Maintain output ON after alarm occurs Standby alarm No output at initial operation until achieve the 1st setup value Execute both ALD ALC at the same time R4 Model OFF Output by temp ON Output by MV1 Output continuously regardless setup temp if manual output value is ON when manual output mode is ON Manual Output Value Output 1 R4 Model...

Page 3: ...It outputs after setting delay time in spite of output condition During ON delay time output lamp is turned on with output after flickering in fast cycle 2 Min OFF Time It lets output not occur within min OFF time after it is turned off During min OFF time output lamp is turned on with output after it flickers every 1 second intervals 3 Min ON Time It is for avoiding frequent ON OFF of control out...

Page 4: ...iation Control deviation is set up at DF in setting 1 group If DF value 0 it is always OFF Deviation High Low Limit Reverse Alarm Output is OFF when the deviation between PV value and SV value is higher or lower than setup value of control deviation Control deviation is set up at DF in setting 1 group If DF value 0 it is always OFF Absolute Value High Limit Alarm Output is ON when PV value is high...