CX9230
Recipro/Scroll(Chiller) Controller
REV DATE
R20180403
USERS MANUAL
- 14 -
4 0122
LO-TEMP AL.TEMP
4.0℃
-50.0 150.0 FREE
SERVICE Temperature is less than
low temperature
alarm, low temperature alarm will occur. (Comp.
stops immediately). Deviation of low temperature
alarm release is
+2.0K
4 0123
LO-TEMP AL.DELAY
60 Sec
0
9999 FREE
SERVICE Working condition for temperature sensor
4 0124
HI-TEMP ALARM
1
0
3
FREE
SERVICE 0=Unuse
1=Auto-Reset
2=Checkd-Reset
3=Forced-Reset
4 0125
HI-TEMP AL.TEMP
20.0℃
-50.0 150.0 FREE
SERVICE Temperature is less than high temperature
alarm, outlet high temperature alarm will
occur. Deviation of high temp. alarm release
is -2.0K
If high temp. alarm mode is auto-reset,
comp. will not stop.
In case of checkd reset or forced reset,
comp. will stop immediately.
4 0126
HI-TEMP AL.DELAY
60 Sec
0
9999 FREE
SERVICE Working condition for temperature sensor
4 0127
LP-HI ALARM
MODE
1
0
3
FREE
SERVICE 0=Unuse
1=Auto-Reset
2=Checkd-Reset
3=Forced-Reset
4 0128
LP-HI AL.PRESS
12.0 Bar
-1.0
99.9
FREE
SERVICE If low pressure is higher than the upper limit
of alarm pressure and maintain it during
LP-
HI AL.DELAY,
LP-HI ALARM
will occur.
Deviation
of LP-HI ALARM release is
-2.0K
4 0129
LP-HI AL.DELAY
60 Sec
0
999
FREE
SERVICE
4 0130
HP-LO ALARM
MODE
1
0
3
FREE
SERVICE 0=Unuse
1=Auto-Reset
2=Checkd-Reset
3=Forced-Reset
4 0131
HP-LO AL.PRESS
10.0 bar
-1.0
99.9
FREE
SERVICE If high pressure is less than the lower limit
of alarm pressure and maintain it during
[611
HP-LO AL.DELAY
],
HP-LO ALARM will occur.
(Comp. stops immediately) Deviation of
HP-
LO ALARM release is
+5.0K
4 0132
HP-LO AL.DELAY
60 Sec
0
9999 FREE
SERVICE