PDD-FT-1.5

Fire Panel Interface 

With EOL Trigger

Installation and Specifications Manual

PDD-FT-1.5

I n s t a l l a t I o n

ISPSFPD-1.5

PCN18003

R04-18GR-1

       © 2018 dormakaba Canada Inc.

www.rutherfordcontrols.com • Phone: 1.800.265.6630 • Fax: 1.800.482.9795 • E-mail: [email protected]

Summary of Contents for RCI PDD-FT-1.5

Page 1: ...OL Trigger Installation and Specifications Manual PDD FT 1 5 I n s t a l l a t i o n ISPSFPD 1 5 PCN18003 R04 18GR 1 2018 dormakaba Canada Inc www rutherfordcontrols com Phone 1 800 265 6630 Fax 1 800 482 9795 E mail sales_RCI dormakaba com ...

Page 2: ...re used and power supply enclosure is properly grounded b As this device can be used to power multiple devices ensure that all wiring is of an appropriate gauge for the devices being installed c This RCI board is for use in a controlled environment The PDD FT 1 5 and all devices connected to or powered through the PDD FT 1 5 shall be installed within the same continuous building structure Installa...

Page 3: ... supply to activate control board and test all connected devices Specifications For UL listed power supply UL 294 6e and ULC S319 Class I Access Control System Unit Access control Levels Endurance Level 4 Line Security Level 1 Power Standby Level 1 Destructive Attack Level 1 Input Input Voltage 12 or 24VDC 10 Typical Current Draw with no Output Load 38mA 12VDC 70mA 24VDC Output Output Relay Rating...

Page 4: ...o an override switch When OVR is open unit will trigger Input Trigger AUX IN 2 Pos Terminal block Will accept 12AWG wire This pair is normally closed and can be connected to an auxiliary device When AUX IN is open unit will trigger Reset 2 Pos Terminal Block 2 Pos Terminal block Will accept 12AWG wire When this pair is shorted input triggers do not latch If pair is open the input triggers will lat...

Page 5: ...e PDD FT outputs will also reset N OFF N ON INPUT GRN EOL RESET AUX OVR RST AUX IN OVR C NO NC TRIGGERED 2 2 K PDD FT C NO NC TRIGGERED DC Input Trigger Output Ground Fault Jumper Reset Input End Of Line Override Input Auxilary Input Normally On Output Normally Off Output Output Led s BAT Output 24V 12V DC N OFF N ON INPUT GRN EOL RESET AUX OVR RST AUX IN OVR C NO NC TRIGGERED PDD FT C NO NC TRIGG...

Page 6: ...nly as long as the fire alarm relay is active When the fire alarm resets the PDD FT outputs will also reset Connecting the EOL input of one board to the trigger relay of the next board as shown will allow for override and reset of multiple boards Note The RST jumper must be left in place on all boards for automatic reset operation Remarque La bretelle RST doit être laissée en place sur tous les pa...

Page 7: ...until both relays have been reset and the N O manual reset is triggered Note Ensure jumpers for RST OVR and AUX IN are removed to allow terminals to operate correctly Remarque Assurez vous que les bretelles RST OVR et AUX IN sont retirées afin de permettre aux terminaux de fonctionner correctement BAT Output 24V 12V DC N OFF N ON INPUT GRN EOL RESET AUX OVR RST AUX IN OVR C NO NC TRIGGERED PDD FT ...

Page 8: ...puts for a short circuit PTC s may require short to be removed for several minutes before automatically resetting Check trigger jumpers Output LED should be lit if output is active Check for proper wiring connections on trigger connections Ensure that 2 2K resistor is installed at End of Line position in the wiring Check devices connected to outputs for a short circuit PTC s may require short to b...