dormakaba 8900 EMF Installation Instructions

08281000

03-2020

8900 EMF

9

Final steps

Operation

5.1  Determine power supply

Fig.12 

5.1.1  Determine power supply and unit voltage type: 

24VAC/24VDC.

CAUTION! DO NOT CONNECT 120VAC TO A 24 VOLT 
UNIT TYPE!!!

5.1.2  Connect power supply wires, one (1) to terminal 

block one (1) to bypass switch.

5.1.3  Connect other bypass switch wire to terminal 

block. (Terminal block can be removed for easier 
wiring).

5.1.4  Slide wiring connection cover over wire 

connections.

Wire 

connection 

cover

Bypass 

switch

Terminal 

block

Incoming 

power 

connection

UL listed alarm 

control unit or 

smoke detector

Final steps

CAUTION! IMPROPER 

VOLTAGE TO UNIT, WILL 

RESULT IN DAMAGE TO UNIT 

AND VOID WARRANTY.

NOTE: All wiring must comply with 

national, state and local electrical 

codes.

NOTE: This 

connection is not 

polarity dependent. 

Terminal block 18 

AWG max.

1.  After installation is completed, recheck all connections. Apply power to units.
2.  Open door so slide block engages with hold open assembly.
3.  Advise fire officials prior to testing.
4.  Activate system into alarm so the electromagnet releases and the doors close.
5.  If the closer is used in conjunction with a detectored unit, trip the test switch of the main closer detector as explained in the test 

procedure for that unit. After a short time delay, the hold open electromagnet of both units will release and the doors will close. 
Resetting the test switch will allow the units to return to standby.

5.2  Final steps

IMPORTANT: THE UNIT MUST BE TESTED AFTER THE INSTALLATION, BY THE END USER, TO ASSURE THAT THE DOOR 
CLOSER UNITS FUNCTION PROPERLY WHEN THE ALARM SYSTEM IS ACTIVATED. THE ENTIRE SYSTEM MUST ALSO BE 
TESTED PERIODICALLY AFTER THE INITIAL INSTALLATION TEST, IN CONJUNCTION WITH THE TESTING OF THE FIRE 
ALARM SYSTEM. THE END USER IS ALSO RESPONSIBLE FOR THE ADJUSTMENTS AND MAINTENANCE TO RETAIN THE 
SYSTEM IN WORKING ORDER.

5.3  Unit testing

NORMAL: 

The closer unit’s solenoid will be 
energized across a normally closed 
alarm contact from 24VDC, 24VAC 
or 120VAC power supply based on 
unit voltage.

FIRE ALARM: When the alarm sounds, the alarm 

contact will open and interrupt 
current to the solenoid which 
releases the hold open allowing the 
door to close and latch.

ELECTRICAL SPECIFICATION:
Voltage input -  24VDC + 10% - 15%
 

   

24VAC + 10% - 15%

Maximum input current -     24VDC 166mA
 

   

 

     24VAC 166mA

5.4  Operation

Summary of Contents for 8900 PT

Page 1: ...8900 EMF Surface Applied Closer no Detector Installation instructions 08281000 03 2020 EN ...

Page 2: ...wire access plug 4 2 3 Secure track to frame 5 2 4 Set up wire connections 5 2 5 Secure main arm 6 2 6 Secure arm to slide shoe 6 3 Adjustments 7 3 1 Adjust closing speeds sweep latch backcheck delayed action 7 3 2 Adjust spring force 7 3 3 Adjust hold open 8 3 4 Auxiliary stops 8 4 Bypass switch optional 8 4 1 Secure bypass switch 8 5 Final steps 9 5 1 Determine power supply 9 5 2 Final steps 9 5...

Page 3: ...t can be connected directly to a fire control panel 2 Read entire instruction sheet prior to installation and refer to NFPA 72E Standards may be obtained from THE NATIONAL PROTECTION ASSOCIATION Batterymarch Park Quincy MA 02269 3 Reference unit carton for unit mounting style and voltage 4 Prepare door and frame for fasteners using the appropriate template Mark drill and tap holes as indicated If ...

Page 4: ...ug according to the installation type NOTE Three access wire holes on optional surface wired units only T DE RH T DE LH Surface wiring NOTE No top plug on PT mounts 2 1 Install closer to door Fig 1 8900T and 8900DE Right hand door 8900PT Right hand door Left hand door Left hand door C L C L Hinge Hinge C L C L Hinge Hinge 2 2 Remove wire access plug Fig 2 ...

Page 5: ...ood screws Route wires from frame through appropriate wire access hole in track being careful not to pinch wires during installation 8900T and 8900DE Wire connection cover 8900PT Hinge C L 2 3 2 8900PT Install PT track to soffit with wire access plugs toward hinge Install with 1 1 4 20x1 1 4 combo screw and 1 1 4 20x2 metal or 1 No 14 x 2 3 4 wood screw as shown Route wires from frame through appr...

Page 6: ...n screw and washer 6mm hex key Left hand door Right hand door 8900T 8900DE 8900PT Hinge C L Hinge C L 2 5 1 With door in closed position rotate spindle 45 with wrench 2 5 2 Place arm on spindle parallel to door 2 5 3 Secure arm with pinion screw and washer 2 5 1 With door in closed position rotate spindle 45 with wrench 2 5 2 Place arm on spindle parallel to door 2 5 3 Secure arm with pinion screw...

Page 7: ... Sweep Latch Speed Latch Backcheck intensity Sweep Latch Backcheck Delayed action Sweep Delayed action 3 2 Adjust spring force Fig 8 Increase Decrease 8916 Supplied with a size 3 spring setting 8956 Supplied with a size 6 spring setting NOTE DO NOT ADJUST SPRING LOWER THAN SIZE 3 Closer size Max door weight lbs Door width Full turns Interior 8916 4 125 2 6 0 5 150 3 8 6 200 3 6 16 8956 6 200 3 6 0...

Page 8: ...ews 3 32 hex Hold open force adjustment 5 32 hex Clockwise stronger Less Hold Open Angle Greater Hold Open Angle NOTE Power must be supplied to reset position An auxiliary door stop by others must be installed to limit the maximum degree of door swing Failure to do so may result in damage to the unit 4 Bypass switch optional Fig 11 4 1 1 Slide wiring connection cover to allow access 4 1 2 Attach b...

Page 9: ...the electromagnet releases and the doors close 5 If the closer is used in conjunction with a detectored unit trip the test switch of the main closer detector as explained in the test procedure for that unit After a short time delay the hold open electromagnet of both units will release and the doors will close Resetting the test switch will allow the units to return to standby 5 2 Final steps IMPO...

Page 10: ...www dormakaba com dormakaba DORMA USA Inc 1 Dorma Drive Drawer AC Reamstown PA 17567 USA T 717 336 3881 F 717 336 2106 ...

Reviews: