dormakaba 1856 HT SD, 1856 SFT SD Installation Instructions
08220880
03-2020
1800 Closer
3
Technical specifications
1 Technical specifications
1.1 Overview
Each 1856 HT SD & 1856 SFT SD unit contains a
door closer, hold open solenoid and a smoke
detector .
The unit can be used as a single installation or as
a series of devices. When the units are wired
together in a run, up to 5 may be interconnected.
Interconnections are accomplished through
terminals #4 and #15 resulting in all alarming
when any one unit senses smoke. In turn, all
associated hold open solenoids are de-energized.
Within any run smoke detecting units it is
permissible to form as many interconnected
series as the total power supply amperage will
allow; but again no more than 5 can be
interconnected.
Any unit with a smoke detector can be connected
to a non-smoke detector unit, or a remote
detector, or both. It can be a single installation
or part of any of the multiple arrangements
described above. A non-smoke detector solenoid
is a slave to the main unit de-energizing when the
main does. Single or group installations can be
connected to the alarm initiation circuit of a
compatible UL/ULC listed fire alarm control 4 or
6 wire configuration panel.
Additional functions are provided to separately
power the hold open solenoids directly from the
alarm control panel or remotely from an alarm
indicator lamp.
ATTENTION!!! Read the entire instruction sheet
prior to installing and refer to NFPA 72E.
Standards may be obtained from THE NATIONAL
FIRE PROTECTION ASSOCIATION in
Batterymarch Park, Quincy, Massachusetts,
02169.
Please make sure you have the tools listed plus
make sure you have the correct model unit and
hand designation per your application.
CAUTION: Sex nuts are required for attachment
of components to unreinforced, wood or plastic
faced composite type fire doors, unless an
alternative method is identified in the individual
door manufacture’s listings. Make sure door
efficiently operates prior to installing the closer.
When Installing main arm attachment observe
directions closely. Confirm dead stop degree prior
to door and frame preparations.
1.2 Tools recommended
Drill bits:
#2 Phillips screwdriver
No. 7 drill bit & drill or 13/64”
drill bit
3/16” slotted head screwdriver
1/4-20 tap & holder
M5 hex key
1/2” box wrench
#3 cross point screwdriver
10” adjustable wrench
Table 1