Dorma TS 99 FL Fixing Instructions Download Page 2

DORMA

DORMA

TS 99 FL EN 2-5

Functional test

Interrupt power supply using manual pushbutton

(e.g. DORMA HT)  .  The hold-open device is

de-energised and the door is closed  .

Clip on end caps  .

Break out the tab as marked for the spindle recess in

the cover 

Clip on cover  .

Ensure that the cables are not damaged in this
process.

Clip on DORMA logo badge  .

Clip on slide channel cover  .

FINAL INSPECTION AND MAINTENANCE

Instruction sheet relating to the use and application

of hold-open systems.

1)

EN 14600 Appendix C

FURTHER INFORMATION / REGULATIONS

Instruction sheet relating to the use and application

of hold-open systems.

1)

Guidelines for hold-open systems published by the

Institute for Building Technology, Berlin 

1)

, or

equivalent national guidelines

FIXING INSTRUCTIONS (Transom mounting)

Technical Data

Operating voltage:

24 V DC ±15%

Power  consumption:

approx. 2 W

Duty factor:

100% continuous duty

Activation is effected via an external central smoke

detector with integral power pack (e.g. DORMA RMZ).

Note:

 According to the guidelines for hold-open systems

issued by the Institute for Building Technology, Berlin, it

must be possible to release every hold-open device by

manual means.

If free-swing door closers are used, release must be
initiated by a pushbutton.

The manual release pushbutton used for this must be red

and carry the inscription “Close Door”. The pushbutton

must be in the immediate vicinity of the door (barrier) and

must not be concealed when the door (barrier) is open.

The DORMA TS 99 FL is non-handed.
The following relates to installation for an LH (ISO 6) door.
In the case of RH (ISO 5) doors, apply mirrored
arrangements as applicable.

Drill fixing points for closer and slide channel as per

template.

Lay 24V DC power supply cable from the central

smoke detector.

Fix mounting backplate.

Fix closer to the mounting backplate.

When using the TS99 FL as a replacement unit,

please ensure that the 24V power supply cable is not

damaged.

Connect power supply cable (24V DC from the central

smoke detector) to terminals.

Attach, align and firmly fix slide channel.

Open door  .

Position arm at an angle of approx. 80° to the

doorframe 

 

 and secure with screw  .

Close valve for adjusting closing speed  .

Preload arm approx. 45°  .

Undo screw again  , remove arm   and, turning 90°,

re-fit   and tighten  .

Connect arm to slide block.

Adjust spring strength (closing force).

Adjust closing speed 180° - 0°  .

Adjust latching action 7° - 0°  .

Setting the free-swing function

Setting the free-swing function

Switch on power (24V DC from central smoke

detector). Open the door leaf to the required

hold-open position. The closer spindle is held in

this position by the electro-hydraulic hold-open

device, but the door can be freely moved thanks to

the free-swing arm assembly.

Leave the door open.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

DORMA GmbH + Co.KG

DORMA Platz 1 D-58256 Ennepetal • Tel. +49 (0) 23 33 / 793-0 • www.dorma.com

Door Control Division

Postfach 40 09 D-58247 Ennepetal • Fax +49 (0) 23 33 / 79 34 95

1)

These documents are only printed in German as they refer

     exclusively to the German market.

Subject to change without notice