Dorma RMZ Manual Download Page 2

DORMA

DORMA

RMZ

Implementing the Reset mode

Automatic reset – Jumper in position “A” (as-
delivered condition)

The RMZ smoke detector automatically resets

following an alarm trip and as soon as there is no

smoke or test gas in the smoke chamber. Status

display returns to green.

Manual reset – Jumper in position “B”

A manual reset is mandatory

- in hold-open systems with automatic swing door

operators, e.g. DORMA ED 200, CD 400 (in

accordance with DIN 18263: Part 4, item 2.5)

- in emergency exit control systems

(in accordance e.g. with IfBt Bulletin 5/983), item

3.1.4).

Status display flashes green as soon as there is no

longer any smoke or test gas in the smoke chamber.

Reset is performed by pressing the reset pushbutton.

If the manual reset mode has been implemented,

attach the enclosed RESET label to the RMZ casing.

Remove the red protective cap from the smoke

detector unit.

Switch on power supply – status display should show

green.

Clip on end cap trims and main cover.

Functional checks

Ensure compliance with instructions for use and also
the safety instructions provided on the test gas
container and safety datasheet.

Open door and engage hold-open device.

Spray test gas (Hekatron 918/5) from a distance of

approx. 10-15 cm towards the smoke chamber.

After approx. 4-6 short bursts, the status display

should switch to alarm (red).  If the RMZ is equipped

with the RS alarm module (option), an audible alarm

is also sounded.

The hold-open device is tripped and released, and the

door closes.

Fit dust protection cover supplied so that dust is

prevented from entering the smoke detector during

any subsequent building or finishing work.

If the dust protection cover is fitted, the unit must be
disconnected from the power supply as the
ventilation slots of the power pack are also covered.
Prior to final commissioning, remove the dust
protection cover and perform a further function
check procedure as described in item 8.

Function of the LEDs

LED on

LED off

Status display LED 1 (green/red)

Standby: green

Alarm: red

Manual reset necessary: green flashing

(see also item 5)

Service display LED 2 (yellow)

Servicing due: flashes

Contamination: flashes

Fault: continuous

FINAL INSPECTION AND MAINTENANCE

See instruction sheet relating to the use and

application of hold-open systems.

If the RMZ lintel-mounted smoke detector is used in
rooms with a high dust content, ensure compliance
with the specified maintenance intervals. These may
even have to be reduced in order to ensure that dust
deposits in the detector do not give rise to nuisance
tripping.

FURTHER INFORMATION/REGULATIONS

Approval certificate

Instruction sheets relating to the use and application

of hold-open systems.

3)

3)

3)

3)

3)

Guidelines for hold-open systems

3)

3)

3)

3)

3)

 published by the

Institute for Building Technology, Berlin, or equivalent

national guidelines.

3)

3)

3)

3)

3)

 Some documents are only printed in German as

they refer exclusively to the German market.

Subject to change without notice

5

6