  Remove the red protective cap from the smoke detector 

unit. Switch the main switch on the swing door 

operator to “ON”.

      ED 100, ED 250:  

Status display should show green. 

Reset of the hold-open system is performed by the 

swing door operator (see instruction ED 100, ED 250).

   ED 200:  

Status display flashes green. 

Press the RESET pushbutton – status display should 

show green.

 5 

  Clip on end cap trims and main cover.

 6 

 

Functional checks

  Ensure compliance with instructions for use and 

also the safety instructions provided on the test gas 

container and safety datasheet.

      Select “Permanent Open” at the program switch 

of the door swing operator – the door opens. 

Spray test gas (Hekatron 918/5) from a distance of 

approx. 10 – 15 cm towards the smoke chamber. 

After approx. 4 – 6 short bursts, the status display 

should switch to alarm (red). 

The hold-open device is tripped and released, and the 

door closes.

      ED 100, ED 250:  

Status display should show green as soon as there is  

no longer any smoke or test gas in the smoke chamber. 

Reset of the hold-open system is performed by the 

swing door operator (see instruction ED 100, ED 250).

   ED 200:  

Status display flashes green as soon as there is  

no longer any smoke or test gas in the smoke chamber. 

Press the RESET pushbutton – status display should 

show green and the door opens.

 7 

  Fit dust protection cover supplied so that dust is 

prevented from entering the smoke detector during any 

subsequent building or finishing work.

 

Prior to final commissioning, remove the dust 

protection cover and perform a further function check 

procedure as described in item 6.

 8 

 

Function of the LEDs

 

LED on 

    LED off 

 

Status display LED 1 (green/red) 

Standby: green 

 

Alarm smoke detector: red 

 

Alarm manual push-button: red 

 

 

 

 

Service display LED 2 (yellow) 

Servicing due: flashes 

 

   

Contamination: flashes 

 

 

 

 

Fault: continuous 

 

Error: flashes 

 

 

incorrect wiring to the smoke detector /manual push-

button

 

DIP switch change after commissioning: 

LED 1: flashes 

 

 

 

 

 

 

LED 2: flashes 

 

 

 

 

 

 

Changes will be applied only after the reset button has 

been pressed.

FINAL INSPECTION AND MAINTENANCE

 

+

See instruction sheet relating to the use and 

application of hold-open systems.

 

If the RM-ED lintel-mounted smoke detector is used 

in rooms with a high dust content, ensure compliance 

with the specified maintenance intervals. These may 

even have to be reduced in order to ensure that dust 

deposits in the detector do not give rise to nuisance 

tripping. 

 

The smoke detector unit must be replaced after 

8 years according to DIN 14677. The LED 2 will 

permanently indicate when the time for replacement 

has come.

FURTHER INFORMATION / REGULATIONS

 

+

Approval certificate 

Instruction sheets relating to the use and application 

of hold-open systems.

3)

 

Guidelines for hold-open systems

3)

 published by the 

Institute for Building Technology, Berlin, or equivalent 

national guidelines.