background image

Instructions

1. Mark horizontal center line (CL) of existing device latch from active door to inactive door.

2. Mark the mounting holes for the Door Pair Housing (DPH) on the inactive door.

3. Drill two 13/32” (10.5mm) holes through inactive door.

4. Mount DPH to inactive door using hardware as shown below. 

Note: Wire access hole is not provided, drill DPH as required.

5. Make wire connections from the power source to the appropriate wire harness supplied. Use the 12V

harness for 12VDC, 12-24VAC or 11-16VAC. Use the 24V harness only for 24VDC.

6. Mount the electric strike with 1/4-20 UNC (Hole C) screws provided in the horizontal mounting holes (the

outer slots). Adjust electric strike horizontally until exit device latch fully engages with the door closed.
Note: Ensure a 1/16” [1.5mm] clearance between exit device latch and the electric strike is maintained.

7. Tighten the two mounting screws and check operation. Adjust the horizontal position of electric strike as

required.

8. Using the electric strike as a template, drill & tap for 1/4-20 UNC (Hole D) screws the two locking holes.

Using the 1/4-20 UNC screws provided secure the electric strike through the locking holes. 
Note: ES  62 strike is not adjustable after installing these screws.

ISES62DPH
08281190

PCN110055

R11/11SH

Typical Door Pair 
Housing Assembly

INACTIVE 
DOOR
 

SEX NUT 1/4-20

WITH 13/32" HOLE

THROUGH (DOOR)

(2 PLACES)

1/4-20 X 2.5"
(2 PLACES)

ES62 DPH

HOLE C

1/4-20 X 1"

SCREW

 

HOLE C

1/4-20 X 1"

SCREW

 

HOLE D

1/4-20 X 1"

SCREW

(2 PLACES)

Electric Strikes

I N S T A L L A T I O N

E S 6 2   -   D O O R   P A I R   H O U S I N G

© 2011 DORMA 

USA: DORMA DRIVE, DRAWER AC, REAMSTOWN, PA 17567  PHONE: (800) 523-8483 (717) 336-3881  FAX: (717) 336-2106 

EMAIL: [email protected] WEBSITE: dorma-usa.com