Instructions for
Model
SS-2100
Water
Alert
®
PRINCIPLE OF OPERATION
Refer to Figure 1. The SS-2100 is activated by liquid bridging the adjustable sensors (A & A). The unit can
detect water film from zero height, (sensors turned out to make contact with the floor), to 1/8" height, (sensors
turned all the way in). The units are factory adjusted to activate with 1/32" water film height which is satisfactory
for most applications. The pads B1, B2, B3 provide a gap between the case and the surface to admit water
under the unit for detection. CAUTION: If the pads are removed, the unit may form a seal with the surface and
prohibit the sensors from detecting water. If desired, the self-adhesive pad feature may be used by peeling off
the thin protective layer from each pad. The unit will remain in place when located on the mounting surface.
Replacement pads are available from Dorlen at no charge.
NOTE
Although the two sensors (A & A) may be adjusted to make contact with the surface, it is recommended
that a small gap be set between the sensors and the surface so undesired activation, caused by damp
-
ness or dirt film, does not occur.
If you have installation questions,
call
toll free
1-800-533-6392
Figure 1
WHEN WATER FILM FORMS
A BRIDGE BETWEEN SEN
-
SORS (A&A), WATER ALERT
IS ACTIVATED.
A
A
A
A
FLOOR
B2
B1
FLOOR
To 110 VAC
SS-2100
Monitor
3
-CONDUCTOR
CABLE
2500'
Max.
SERIES 2100
1 2 3 4 5 6
Alert Actvated
System Powered
1-19 M-9860
CAUTION
Not For Explosive Environments!
5 YEAR
LIMITED
WARRANTY
See catalog or pr
ice
list for details
6615 W. Layton Ave. Milwaukee, WI 53220
Phone: (414) 282-4840 FAX: (414) 282-5670
E-Mail: [email protected]
Products Inc.
DORLEN
DORLEN
SYSTEMS INSTALLIED IN OVER 25,000 SITES!
Mfgr. of:
R
Oil Alert
Oil Alert
R
CEILING
GUARD
R
www.wateralert.com
www.oil-alert.com
LIQUID LEAK DETECTION SYSTEMS SINCE 1975
Page 1 of 2
Model SS-2100 Bottom View