P/N DKML-065 REV C 5/02
IMPORTANT! – Magnetic locks must be supplied with DC power for proper operation. Use
only a UL listed (or equivalent) DC power transformer that supplies the proper voltage and
amperage.
•
P/N 1812-035 – 24-Volt DC power transformer. .5 amp maximum power output.
•
P/N 1812-037 – 12-Volt DC power transformer. 1 amp maximum power output.
12 VDC POWER
•
Requires .5-amp power.
•
Connect 12 Volt DC POSITIVE to terminal 1.
•
Connect 12 Volt DC NEGATIVE to terminal 2.
•
Be sure power select jumpers are set for 12 VDC operation.
24 VDC POWER
•
Requires .25-amp power.
•
Connect 24 Volt DC POSITIVE to terminal 1.
•
Connect 24 Volt DC NEGATIVE to terminal 2.
•
Be sure power select jumpers are set for 24 VDC operation.
Lock Status LED and Relay (DKML-S12-1L and DKML-S12-1LT only)
•
LOCKED CONDITION - LED glows green and relay activates.
•
UNSECURE CONDITION – LED glows red and relay is deactivated.
•
Relay contacts are rated for 1 amp at 24 VDC maximum. Do not exceed this rating.
Timer (DKML-S12-1LT only)
•
Adjustable from 0-90 seconds.
1
+
3
NO
5
NC
4
C
2
-
LED1
J1
J2
L1
L2
12 or 24 VDC POSITIVE
12 or 24 VDC NEGATIVE
RELAY NORMALLY OPEN
RELAY COMMON
RELAY NORMALLY CLOSED
GRN
BLK
RED
FROM MAGNET
TIMER
INCREASE
IMPORTANT!
12 VDC
24 VDC
J1
J2
TO
MA
G
N
E
T
TO LED
WH
T
BLK
GR
N
RED