P/N DKML-065 REV C 5/02 

IMPORTANT! – Magnetic locks must be supplied with DC power for proper operation.  Use 
only a UL listed (or equivalent) DC power transformer that supplies the proper voltage and 
amperage. 

• 

P/N 1812-035 – 24-Volt DC power transformer.  .5 amp maximum power output. 

• 

P/N 1812-037 – 12-Volt DC power transformer.  1 amp maximum power output.

 

 

12 VDC POWER 

• 

Requires .5-amp power. 

• 

Connect 12 Volt DC POSITIVE to terminal 1. 

• 

Connect 12 Volt DC NEGATIVE to terminal 2. 

• 

Be sure power select jumpers are set for 12 VDC operation.

 

 

24 VDC POWER 

• 

Requires .25-amp power. 

• 

Connect 24 Volt DC POSITIVE to terminal 1. 

• 

Connect 24 Volt DC NEGATIVE to terminal 2. 

• 

Be sure power select jumpers are set for 24 VDC operation.

 

 

Lock Status LED and Relay (DKML-S12-1L and DKML-S12-1LT only) 

• 

LOCKED CONDITION - LED glows green and relay activates. 

• 

UNSECURE CONDITION – LED glows red and relay is deactivated. 

• 

Relay contacts are rated for 1 amp at 24 VDC maximum.  Do not exceed this rating.

 

 