  BOOSTER PUMP SYSTEM

 

5          

 

 

BOOSTER PUMP SYSTEM N747D

 

 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

This advanced computer control device has been achieved its controlling of 
pump’s RPM by inverter through the newest electronic technology, and 
equipped with presumptive terminal pressure control technology and various 
intelligent functions which can determine and control the pressure of water 
supply according to the amount of supplied water and usage.     
 
  Up to 6 pumps can be controlled with functions generally such as; stopping 

low flow using pressure tank, control, scheduled operation, warning 
abnormal state, full automated sequential operation, interval shift operation, 
skipping failed pump automatically, displaying operation data and data 
storing 

 

Remote controlling and monitoring functions by remote modem 
communication, and easy operating for anyone by displaying of all screen 
view in Korean./ English / Chinese.   
 

 
 
 

2. 

Major functions of controller  

 

 

Summary of Contents for N747D

Page 1: ...BOOSTER PUMP SYSTEM 1 BOOSTER PUMP SYSTEM N747D User s Manual For Booster Pump N747D Controller DOOCH CO LTD...

Page 2: ...g 10 2 Display of user setting 10 3 Change of user setting 1 11 4 Change of user setting 2 15 5 Change of user setting 3 19 Chapter 3 Key operation of installer 1 Key operation of installer setting 26...

Page 3: ...1 Test operation key 46 Chapter 6 Other Keys 1 Inverter reset Key 49 2 Key of Initial display 49 3 Alarm display and Reaction 49 Chapter 7 Appendix 1 Control Board Arrangement and Description 52 2 Ch...

Page 4: ...BOOSTER PUMP SYSTEM BOOSTER PUMP SYSTEM N747D Chapter 1 The composition and features of controller 1 Features of controller 2 Functions of controller 3 Composition of controller 1 Features of controll...

Page 5: ...pply according to the amount of supplied water and usage Up to 6 pumps can be controlled with functions generally such as stopping low flow using pressure tank control scheduled operation warning abno...

Page 6: ...ment Alarming high pressure When specified pressure time is exceeded pump stops and alarm is given Alarming low pressure When every pumps are operated under specified pressure even during the continuo...

Page 7: ...y It displays system information Operation Key It is for data setting and checkup data It is for booster system user It is for booster system installer It is for checking operation data It is for chec...

Page 8: ...MP SYSTEM BOOSTER PUMP SYSTEM N747D Setting value It is for saving setting value and checking operation history alarm history It is for deleting operation history alarm history It is for moving cursor...

Page 9: ...UMP SYSTEM 9 BOOSTER PUMP SYSTEM N747D Chapter 2 Key operation of user 1 Key operation of user setting 2 Display of user setting 3 Change of user setting 1 4 Change of user setting 2 5 Change of user...

Page 10: ...MP SYSTEM BOOSTER PUMP SYSTEM N747D 1 Key operation of user setting 2 Display of user setting User setup display 1 User setup display 2 User setup display 3 The display of User setup 3 is related with...

Page 11: ...TER PUMP SYSTEM N747D Display of Monthly operation Display of weekly operation Display of timely operation 3 The change of user setup 1 1 Press installer setup on main display 2 Input password and sav...

Page 12: ...R PUMP SYSTEM BOOSTER PUMP SYSTEM N747D 3 In user setup 1 move to desire display with cursor 4 Move to desire display with cursor Cursor can be moved to left right 5 Setting value can be changed by fi...

Page 13: ...2 kgf cm 1 Using Key select 2 Initially the first 0 of the 00 20 blinks 3 Using Key select position to be changed in 00 20 kgf cm 4 After change using Key make sure to press Key Auxiliary stop pressur...

Page 14: ...pressure Change of stepl stop pressure Example In case current set value is 00 50 kgf cm 1 Using Key select 2 Initially the first 0 of the 00 50 blinks 3 Using Key select the position to be changed i...

Page 15: ...OSTER PUMP SYSTEM 15 BOOSTER PUMP SYSTEM N747D 4 The change of user setup 2 1 Press user setup on main display 2 Input password and save initial password is 0000 3 Press user setup key on user setting...

Page 16: ...16 BOOSTER PUMP SYSTEM BOOSTER PUMP SYSTEM N747D 4 In user setup 2 move to desire display with cursor 5 Setting value can be changed by figure Keys...

Page 17: ...to move to required position using Key The last number means day of the week as below 1 Mon 2 Tue 3 Wed 4 Thurs 5 Fri 6 Sat 7 Sun 4 After changing to required value make sure to press Key Set value i...

Page 18: ...time frame Initial setting is No use and operation method can be selected with 0 3 number keys Each number stands for 0 No use 1 Monthly operation 2 Weekly operation 3 operation by time frame Change s...

Page 19: ...OSTER PUMP SYSTEM 19 BOOSTER PUMP SYSTEM N747D 5 The change of user setup 3 1 Press user setup on main display 2 Input password and save initial password is 0000 3 Press user setup key on user setting...

Page 20: ...setup 2 move to schedule setup with cursor 5 Choose desire figure from 0 to 3 0 Not used 1 Monthly operation 2 Weekly operation 3 Timely operation 6 After changing to operation setup make sure to pre...

Page 21: ...BOOSTER PUMP SYSTEM 21 BOOSTER PUMP SYSTEM N747D 7 After pressing Key press user setup to move user setup 3 8 In user setup 3 choose desire menu with cursor 9...

Page 22: ...BOOSTER PUMP SYSTEM BOOSTER PUMP SYSTEM N747D 10 Change the desire value with figure Keys 11 After changing to operation setup make sure to press Key Set value is not changed until input key is press...

Page 23: ...Key change to required value then make sure to press Key Set value is not changed until input key is pressed Screen configuration of monthly operation Weekly scheduled operation Any operation by weekl...

Page 24: ...scheduled operation in user setting 2 using Key then press user setting button to move to user setting 3 and change it Scheduled operation by time frame 1 Using Key select item to be set 2 Select req...

Page 25: ...BOOSTER PUMP SYSTEM N747D Chapter 3 Key operation of installer 1 Key operation of installer setting 2 Display of user setting 3 Change of installer setting 1 4 Change of installer setting 2 5 Change...

Page 26: ...26 BOOSTER PUMP SYSTEM BOOSTER PUMP SYSTEM N747D 1 Installer Setup Key 2 Display of Installer setup Display of installer setup 1 Display of installer setup 2 Display of installer setup 3...

Page 27: ...SYSTEM 27 BOOSTER PUMP SYSTEM N747D 3 The change of installer setup 1 1 Press ENG SET key on main display 2 Input password and save initial password is 0000 3 In installer setup 2 move to desire item...

Page 28: ...OOSTER PUMP SYSTEM BOOSTER PUMP SYSTEM N747D 4 5 Setting value can be changed by figure Keys 6 After changing to operation setup make sure to press Key Set value is not changed until input key is pres...

Page 29: ...ctor P It is a proportional factor in PID control variables Range 1 100 Change of proportional factor P settings Example In case of to change 80 to 90 1 Using Key select 2 Initially the first 0 of the...

Page 30: ...that current pressure setting pressure Dead zone is sustained for more than 20 seconds inverter decelerates in order to inspect the state of non flow Even if it decelerates when current pressure sett...

Page 31: ...s Key Set value is not changed until input key is pressed Operating method To set operation method of pump 1 Operating by fixed inverter Inverter is fixed for one pump operation and when all pumps sto...

Page 32: ...BOOSTER PUMP SYSTEM BOOSTER PUMP SYSTEM N747D 4 The change of installer setup 2 1 Press ENG SET key on main display 2 Input password and save initial password is 0000 3 Press ENG SET on installer setu...

Page 33: ...BOOSTER PUMP SYSTEM 33 BOOSTER PUMP SYSTEM N747D 4 In installer setup 2 move to desire item with 5 6 Setting value can be changed by figure Keys...

Page 34: ...0 using Key 4 After changing to required value make sure to press Key Set value is not changed until input key is pressed Preventing frozen rupture In order to prevent frozen rupture in cold season if...

Page 35: ...he first 0 of the 000 blinks 3 Enter by using Key 4 After changing to required value make sure to press Key Set value is not changed until input key is pressed System initializing Initialize setting v...

Page 36: ...BOOSTER PUMP SYSTEM BOOSTER PUMP SYSTEM N747D 5 The change of installer setup 3 1 Press ENG SET key on main display 2 Input password and save initial password is 0000 3 Press ENG SET on installer setu...

Page 37: ...BOOSTER PUMP SYSTEM 37 BOOSTER PUMP SYSTEM N747D 4 Press ENG SET on installer setup 2 5 In installer setup 3 move to desire item with cursor 6 Setting value can be changed by figure Keys...

Page 38: ...ct 2 Enter by using Key No use Use 4 After changing to required value make sure to press Key Set value is not changed until input key is pressed Slave ID Set Slave ID Range 1 255 Change setting of Sla...

Page 39: ...e first 0 of the 0000ms blinks 3 Using Key select the position to be changed in 0000 ms 4 Using Key enter by order of 0 0 and 2 5 After changing to required value make sure to press Key Set value is n...

Page 40: ...required value make sure to press Key Set value is not changed until input key is pressed BAUD RATE Select communication speed 0 40kbps 1 50kbps 2 100kbps 3 200kbps 4 250kbps Change setting of BAUD R...

Page 41: ...BOOSTER PUMP SYSTEM 41 BOOSTER PUMP SYSTEM N747D Chapter 4 Operation History Key 1 Confirmation of pump operation history 2 Confirmation of alarm history...

Page 42: ...42 BOOSTER PUMP SYSTEM BOOSTER PUMP SYSTEM N747D 1 Confirmation of pump operation history 1 Press operation Data key on main display 2 In operation data move to desire menu with cursor...

Page 43: ...SYSTEM N747D 3 It shows pump operation history If you want to delete all pump operation history press Del key 2 Confirmaton of alarm history 1 Press operation Data key on main display 2 Press operatio...

Page 44: ...UMP SYSTEM BOOSTER PUMP SYSTEM N747D 3 In alarm history display move to desire menu with cursor 4 5 It display alarm history It shows latest 10 alarm history If you want to delete all alarm history pr...

Page 45: ...BOOSTER PUMP SYSTEM 45 BOOSTER PUMP SYSTEM N747D Chapter 5 Test Operation Keys of test operation...

Page 46: ...7D Test Operation Key It is used for checking direction of motor rotation After turning off the STOP START switch on panel please operate this function 1 Press Test Run key on main display 2 In the te...

Page 47: ...BOOSTER PUMP SYSTEM 47 BOOSTER PUMP SYSTEM N747D 3 Use left right cursor to select pump operation method 4 Using Key change the sensor correction value and Min operation ratio...

Page 48: ...48 BOOSTER PUMP SYSTEM BOOSTER PUMP SYSTEM N747D Chapter 6 Other Keys...

Page 49: ...larm is given buzzer sounds and lamp blinks At the same time the alarm notes are displayed on LCD screen To stop the buzzer just press any key of the controller keys Lamp keeps blinking until the root...

Page 50: ...mp 2 pump 3 pump 4 pump 5 and pump 6 if there are 6 pumps as MANU so that one pump can be started and increases the pressure up to the low alarm setting pressure 2 Press In Test Operating key among th...

Page 51: ...PUMP SYSTEM 51 BOOSTER PUMP SYSTEM N747D Chapter 7 Appendix 1 Control board arrangement and description 2 Check items 3 Procedure and manual for pump test operation 4 Emergent operation 5 RS 485 commu...

Page 52: ...52 BOOSTER PUMP SYSTEM BOOSTER PUMP SYSTEM N747D 1 Control board arrangement and description...

Page 53: ...0 frequeancy setup voltage 0 10V 12 CG RS485 signal earthing common terminal 35 iO0 inverter 0 frequeancy setup current 0 11V 13 485 RS485 signal High terminal 36 CG Earthing common terminal 14 RI0C I...

Page 54: ...zing relay A contact 6 PTHT Pump overload terminal 18 rI2C Inverter 3 initializing relay C contact 7 PRA Pump operation relay A contact 19 CG Earthing common terminal 8 PRC Pump operation relay C cont...

Page 55: ...CG wire of Pump OPT board Verify LED ON state of Pump OPT board 5 Start Stop switch of the front panel does not work Check switch contact points Verify the shortages of 20 CG and 25 Run wire of main...

Page 56: ...mp it s possible in test operating Re set the operating pressure and time of the auxiliary pump 12 Auxiliary pump operates frequently In the user setting screen re set the operating pressure and time...

Page 57: ...Ex factory default setting is voltage control method 3 Pump test operation Thank you for your selection of our boost pump system In this section check items procedures and manuals for test operation a...

Page 58: ...ontroller LCD screen is the desired input value in case of change set pressure correct the date set pressure according to this manual printed inside of the panel 11 When all steps are completed set ST...

Page 59: ...operates under emergent automatic operation mode Indications In case of inverter failure auto emergent operation is carried out automatically and the failure notice is indicated in main screen In the...

Page 60: ...operation method to be carried when normal operation is unavailable due to the failure of most of core components such as inverter pressure transmitter pressure switch controller and etc Starting meth...

Page 61: ...tocol ModBus RTU Protocol Function code Code Name 0x03 Read Hold Register 0x06 Preset Single Register READ Query example response Single Write Query example Pressure 5 5bar response Setting for commun...

Page 62: ...485 485 signal high Check whether RS485 is use or not Refer Page 38 Check communication Refer Page 38 Check N747D Slave ID Protocol Slave ID should be Same with N747D Slave Refer Page 38 Check the st...

Page 63: ...0 100 0x400A Pump 6 output 1 R 0 100 0x400B Option inverter output 1 R 0 100 0x400C Setting Pressure 0 1 bar R W 0 250 0x400D Current Pressure 0 1 bar R 0 250 0x400E Pump1 operation number 1 Num ber R...

Page 64: ...peration time 1 hour R 0 65535 0x401C Pump3 operation time 1 hour R 0 65535 0x401D Pump4 operation time 1 hour R 0 65535 0x401E Pump5 operation time 1 hour R 0 65535 0x401F Pump6 operation time 1 hour...

Page 65: ...or each pump Low Byte Trip content Bit 0 High pressure Bit 1 Low pressure Bit 2 Pump over current Bit 3 Inverter1 Bit 4 Low level Bit 5 Sensor Bit 6 Inverter2 option Bit 7 Emergent operation High Byte...