Dometic Radome ECU Installation, Operation & Maintenance Manual Download Page 8

THE DIGITAL CONTROL

 

Radome Environmental Control Unit

6

L-2283 ENGLISH

Important Programming Notes To Installer and End User

1.

When powering on the control, press and immediately release the Power button so you do not unintentionally enter 
Program Mode. You will enter Program Mode if the Power button is pressed and held for more than 5 seconds. If you 
enter Program Mode unintentionally, any subsequent presses of the Up or Down buttons will change the P-1 
parameter setting since it is the first parameter shown after entering this mode. This will change the operating mode to 
Cool Only, Heat Only, or Automatic, which could result in improper system operation. Always use care when in 
Program Mode. For further information, refer to “Using Program Mode” on page 6.

2.

The Radome ECU is a Cool Only system (it does not have a reversing valve), therefore you must make sure the Cool 
Only Mode value “1” is set for parameter P-1 (this is the factory default for Radome ECU systems). DO NOT program 
Automatic Mode for a Cool Only unit. If Automatic Mode is selected and the thermostat calls for heat, the compressor 
will run. Since there is no reversing valve, the air conditioning unit will supply cool air when heating is desired. Cool 
Only units do not heat. 

However, if you have the electric heat option installed you CAN program Automatic Mode, which will allow the unit to 
switch between cooling and heating as needed based on independent high and low set points. See “Automatic Mode” 
on page 5 for details.

See “P-1: Operating Mode” on page 7 for more information on how to set the proper operating mode.
See “P-15: Reverse-Cycle or Electric Heat” on page 8 for more information on how to set the electric heat option.

3.

You can restore the last memorized default settings by entering Program Mode and setting P-17 to “rSt”. 

Using Program Mode

Entering Program Mode

You can only enter Program Mode from the Off Mode. If necessary, press the Power button to enter Off Mode. Press and hold 
the Power button while in the Off Mode until the letter “P” appears in the display. The characters “P1” followed by the P-1 
parameter setting appear in the display. The control is now in the Program Mode. If no programming is attempted for one 
minute, the control exits Program Mode and returns to Off Mode.

Exiting Program Mode

Press the Power button once to exit Program Mode and return to Off Mode. Or, do not attempt any programming for 50 
seconds, then the control exits Program Mode and returns to Off Mode. Any programming changes made while in Program 
Mode will be saved and put into operation after exiting Program Mode and returning the control to the On Mode. (If you want the 
programming changes to become the new defaults, see “Memorizing New Program Parameters” on page 6.) When you exit 
Program Mode the software version number (such as “A24”) appears in the display.

Changing Parameters

While in Program Mode, press and release the Fan button to increment from one program parameter to the next until you reach 
the desired parameter number. The programmable parameters range from P-1 through P-22. 

When you reach the desired parameter number, use the Up and Down buttons to select the data or set the desired limits for the 
parameter being programmed. See Table 2 on page 9 for a list of the parameters, the possible settings for each, and their 
factory default settings for the Radome ECU.

Memorizing New Program Parameters

If you want new parameters to be the program defaults, adjust the parameters to the desired settings, then press the Up and 
Down buttons simultaneously while in Program Mode. This memorizes the new settings as program defaults and exits the 
Programming Mode.

To return to the factory default settings, refer to the factory defaults listed in Table 2 on page 9 and reset the parameters 
manually.

Restoring Memorized Default Settings

You can restore the last memorized default settings by entering Program Mode and setting P-17 to “rSt”. The memorized default 
settings are restored and the control returns to Off Mode. See “P-17: Reset Memorized Defaults” on page 8 for details. To return 
to the factory default settings, refer to the factory defaults listed in Table 2 on page 9 and reset the parameters manually.

Software Identification

The control’s software version (such as “A24”) appears in the display for one second prior to exit from Program Mode, then the 
control returns to Off Mode.

Summary of Contents for Radome ECU

Page 1: ...ic Corporation Every precaution has been taken in the preparation of this manual to insure its accuracy However Dometic Corporation assumes no responsibility for errors and omission Neither is any liability assumed for damages resulting from the use of this product and information contained herein Radome Environmental Control Unit With Passport I O Compact Digital Display INSTALLATION OPERATION MA...

Page 2: ... 4 Air Sensor 4 Fan Button 4 Power 4 MODES OF OPERATION 5 Off Mode 5 On Mode 5 Cool Mode 5 Heat Mode 5 Automatic Mode 5 Moisture Mode 5 Fan Modes 5 Automatic Fan Mode 5 Manual Fan Mode 5 Fan Only Mode 5 Cycled or Continuous Fan Operation 5 Program Mode 5 Important Programming Notes To Installer and End User 6 Using Program Mode 6 Programming 7 Programmable Parameters 7 OPERATION 10 TROUBLESHOOTING...

Page 3: ...e packing list to ensure all cartons were received Move units in the normal up orientation as indicated by the arrows on each carton Examine cartons for shipping damage removing the units from the cartons if necessary If the unit is damaged the carrier should make the proper notation on the delivery receipt acknowledging the damage HOW IT WORKS The Radome ECU consists of four main components and a...

Page 4: ...perates with compressed refrigerant at high pressures Proper care must be taken during installation operation and servicing to prevent injury or loss of life due to improper procedures DANGER This equipment is not ignition protected per CFR 183 410 and may not be installed in areas that may be exposed to flammable gases Do not install in spaces containing gasoline engines tanks LPG CPG cylinders r...

Page 5: ... ducting is taught secure and as straight as possible to minimize bends Use insulated ducting to reduce heat gain to dome 4 Make electrical connections as described in Electrical below 5 Position the Passport I O Compact digital display inside the dome in a location that will sense dome temperature To avoid short cycling do not place near the supply air stream into dome 6 Use a diverter to positio...

Page 6: ... Up or Down button The Radome ECU set point is 85 F AIR SENSOR Dome temperature is detected by the air sensor on the face plate FAN BUTTON Not used on Radome ECU POWER Press the Power button once to engage the system The display is blank when the system is off and indicates current room temperature when the system is on Figure 1 Passport I O Compact Display Panel and Indicators Table 1 Passport I ...

Page 7: ...ome temperature must exceed the set point by at least 4 F 2 2 C in order for the system to switch from heating to cooling This behavior prevents small temperature overshoots from causing the system to switch between heating and cooling when it is not necessary To make the temperature differential between cooling and heating larger see See P 23 Auto Mode Heat Differential on page 9 MOISTURE MODE No...

Page 8: ...P 1 parameter setting appear in the display The control is now in the Program Mode If no programming is attempted for one minute the control exits Program Mode and returns to Off Mode Exiting Program Mode Press the Power button once to exit Program Mode and return to Off Mode Or do not attempt any programming for 50 seconds then the control exits Program Mode and returns to Off Mode Any programmin...

Page 9: ...U P 5 Temperature Calibration This feature calibrates the ambient sensor within a range of 10 F Adjust this parameter to display the correct room temperature reading Note that setting increments are in F even when the control is set to display C P 6 Failsafe Level To protect the equipment certain fault conditions trigger a lockout The control shuts down and will not restart until the fault is repa...

Page 10: ...ut conditions If this low voltage condition occurs the fault code LAC appears in the LED display The fault will continue until the AC input voltage rises above the specified setting at which time the LAC fault code clears automatically and the cooling or heating cycle will commence After the compressor is started the low voltage monitor will not interfere with operation and the LAC fault will not ...

Page 11: ...ferential Available only in software revision A25 and newer This parameter creates a larger temperature differential between cooling and heating operation in Automatic Mode It is adjustable between 4 F and 40 F and is OFF by default Typically in Automatic Mode with P 23 OFF the unit will maintain a single set point only switching between cooling and heating when a 4 F 2 2 C change in temperature o...

Page 12: ...g or Electric Heat Only Option Installed nor nor Reverse Cycle Heating ELE Electric Heater Installed P 16 Fan Motor Type Split Capacitor or Shaded Pole SC SC Split Capacitor Fan Motor SP Shaded Pole Fan Motor P 17 Reset Memorized Programming Defaults nor rST Reset Defaults nor Normal P 18 Reserved for future use P 19 Reserved for future use P 20 Air Filter Cleaning Replacement Timer Setting x10 ho...

Page 13: ...ove reasons Compressor needs to cool down Turn system off for a while it may take up to three hours to reset thermal overload System runs continuously 1 Set point temperature is set too low for cooling Raise set point to 85 F 2 Porthole or hatches open Close all port holes and hatches Passport I O Compact display panel not lit 8 pin display cable plugs are not making contact unplugged dirty bent o...

Page 14: ...at set point is too low Raise to 85 F 2 Evaporator blower is not running Check to confirm Troubleshoot if necessary 3 Low pressure switch is open due to loss of refrigerant Check air conditioning unit for refrigerant oil leakage call service technician ASF is displayed Air Sensor Failure 1 Indicates failed face plate air sensor alternate air sensor or display cable Unplug alternate air sensor if i...

Page 15: ...Radome Environmental Control Unit DIAGRAMS L 2283 ENGLISH 13 Figure 2 HSA 16K C CZ CZ50 Self Contained Wiring Diagram for units shipped after August 1 2009 ...

Page 16: ...DIAGRAMS Radome Environmental Control Unit 14 L 2283 ENGLISH Figure 3 HSA 16K C CZ CZ50 Self Contained Wiring Diagram for units shipped prior to August 1 2009 ...

Page 17: ...E PROPERTY OF DOMETIC CORPORATION ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF DOMETIC CORPORATION IS PROHIBITED PROPRIETARY AND CONFIDENTIAL DIMENSIONS ARE IN INCHES TOLERANCES FRACTIONAL 1 32 ANGULAR BEND 1 TWO PLACE DECIMAL THREE PLACE DECIMAL N A DRAWN CHECKED DATE NAME DESCRIPTION SIZE B DWG NO RE WEIGHT SCALE 1 8 UNLESS OTHERWISE SPECIFIED 0 DRR RAP 6 19 09 6 19 0...

Page 18: ...DIAGRAMS Radome Environmental Control Unit 16 L 2283 ENGLISH TEMPLATE FOR INTERIOR UNIT Figure 5 Mounting Template For Interior Self Contained System ...

Page 19: ...Radome Environmental Control Unit DIAGRAMS L 2283 ENGLISH 17 MOUNTING DIAGRAMS Figure 6 Mounting Diagram For Self Contained System ...

Page 20: ...DIAGRAMS Radome Environmental Control Unit 18 L 2283 ENGLISH Figure 7 Mounting Diagram For System With Existing Hatchway Covers ...

Page 21: ...NOTES ...

Page 22: ...NOTES ...

Page 23: ...NOTES ...

Page 24: ...s dometic com 24 7 TECH SUPPORT FOR UNITED STATES AND CANADA 8 00 AM to 5 00 PM Eastern Time 1 800 542 2477 After hours and weekends 1 888 440 4494 INTERNATIONAL SALES AND SERVICE Europe and the Middle East 44 0 870 330 6101 For all other areas visit our website to find your nearest distributor dometic com L 2283 06 01 2017 ...

Reviews: