F.  Thermostat, Optional Indoor 

Temperature Sensor & Thermostat 

Communication Cable Installation 

1.  CCC 2 System

a.  The previously run communication cable (4 

conductor telephone cable) must be termi-

nated with two (2) RJ-11-6C4P telephone 

connectors. Refer to the crimp tool manufac-

turer for crimping instructions. See (FIG. 8) 

& (FIG. 9).

RJ-11-6C4P connectors

 MUST 

be in-

stalled as shown in (FIG. 8) & (FIG. 9).

FIG. 8

FIG. 9

Flat 4-Conductor 

Communication Cable

RJ-11-6C4P 

Connector

Pin 1

Black

Red

Green

Yellow

b.  Route the communication cable through the 

2" diameter hole in the wall required for the 

thermostat. See (FIG. 10).

c.  Optional Indoor Temperature Sensor

I.  Refer to the instructions provided with the 

indoor temperature sensor for details of 

installation.

a.  Route an indoor temperature sensor (option-

al) from the roof opening to the indoor tem-

perature sensor location. The 2 pin connec-

tor end goes to the roof opening. See indoor 

temperature sensor installation instructions 

for proper sensor location.

5.  If system includes a gas furnace, route two 18 

gauge thermostat wires from the furnace to the 

roof opening of the unit that will control it. If more 

than one furnace is to be used, route the second 

set of thermostat wires to the second unit. Make 

sure  that  at  least  15″  of  wire  extends  into  the 

opening.

6.  (CCC 2 system only) If an Energy Management 

System (load shed feature) is to be used with 

the control, two wires must be routed to the 

roof opening of the zone to be managed. The 

signal required for this function is normally an 

open relay contact. When the EMS calls for the 

compressor to shut off, the relay contacts should 

close. Make sure that at least 15″ of the EMS 

wire extends into the roof opening.

7.  (CCC 2 system only) If an Automatic Generator 

Start (AGS) kit will be installed, an additional 4 

conductor communication cable must be routed 

from the last unit to the location of the AGS kit. 

Follow AGS kit instructions for installation.

E.  Choosing Thermostat Location

1.  CCC 2 system without an optional indoor tem-

perature sensor and LCD SZ system

a.  The proper location of the thermostat is very 

important to ensure that it will provide a com-

fortable RV temperature. Observe the follow-

ing rules when selecting a location.

 

● Locate the thermostat 54″ above the floor.

 

Install the thermostat on a partition, not 

on an outside wall.

 

NEVER

 expose the thermostat to direct 

heat from lamps, sun, or other heat pro-

ducing items.

 

Avoid locations close to doors that lead 

outside, windows, or adjoining outside 

walls.

 

Avoid locations close to supply registers 

and the air from them.

2.  CCC 2 system with an optional indoor tempera-

ture sensor in ALL zones

a.  The thermostat may be mounted anywhere 

in the RV that is convenient. Try to avoid 

hard to reach and hard to see areas.

I.  Refer to the instructions provided with the 

indoor temperature sensor for details of  

installation.

INSTALLATION INSTRUCTIONS

Summary of Contents for Blizzard NXT H541815A

Page 1: ...h 3316202 000_B 2017 Dometic Corporation LaGrange IN 46761 Roof Top Unit Quiet Zone Ducted Application Description Blizzard NXTTM Model Board Built In Thermostat Optional Indoor Temperature Sensor Air Conditioner CCC 2 Controls H541815A H541816A Board Built In 3314082 000 CCC 2 Blk 3314082 011 CCC 2 Wht 3311931 000 20 3311931 012 40 3311931 020 60 LCD SZ Controls H541915A H541916A Board Built In 3...

Page 2: ...SZ System Only System Checkout 16 N CCC 2 System Only Reset Checkout 16 O CCC 2 System Only Furnace Aqua Temperature Differential Setting 16 GENERAL INFORMATION 17 A Heat Gain 17 B Condensation 17 WIRING DIAGRAMS 18 A Simple RV Wiring Diagram 18 B Unit Wiring Diagrams 19 DOCUMENT SYMBOLS Indicates additional information that is NOT related to physical injury Indicates step by step instructions INT...

Page 3: ... all safety information and instructions to avoid possible injury or death Read and understand these instructions be fore installing using servicing performing maintenance on this product Incorrect installation operation servicing maintaining of this product can lead to seri ous injury Follow all instructions The installation MUST comply with all ap plicable local or national codes including the l...

Page 4: ...n actual applications When sizing the generator the total power usage of your RV must be considered Keep in mind generators lose power at high altitudes and from lack of maintenance CIRCUIT PROTECTION Time Delay Fuse or Circuit Breaker Required B Roof Requirements A 14 1 4 x 14 1 4 1 8 square opening hereinafter referred to as roof opening is required for installing this unit This opening is part ...

Page 5: ...to product and or RV could occur The roof must be designed to support 130 pounds when RV is in motion Normally a 200 lb static load design will meet this requirement B Roof Preparation 1 FIRE OR ELECTRICAL SHOCK HAZARD Make sure there are no obstacles wires pipes etc inside RV s roof floor walls Shut OFF gas supply disconnect 120 Vac power from RV and disconnect positive 12 Vdc terminal from suppl...

Page 6: ...cts and their joints must be sealed to prevent condensation from forming on adjacent surfaces during operation of the unit 4 Return air openings must have 40 square inches minimum free area including the filter 5 Return air to the unit must be filtered to prevent dirt accumulation on unit cooling surface Frame Duct Duct Frame Frame Roof Opening Roof Opening Roof SIDE VIEW TOWARD BACK OF RV Duct Ce...

Page 7: ...7 INSTALLATION INSTRUCTIONS Return Supply Supply Return FIG 4 Return Supply Return Supply FIG 5 Return Return Supply Supply Supply Supply FIG 6 ...

Page 8: ...ning b Make sure that at least 15 of supply wire extends into the roof opening 3 Thermostat Communication Cable a CCC 2 Thermostat I Route a 4 conductor communication ca ble from the roof opening to the thermo stat mounting location using the shortest most direct route Make sure that at least 15 of the wire extends into the roof open ing and 6 extends from the wall at the thermostat mounting locat...

Page 9: ...stem load shed feature is to be used with the control two wires must be routed to the roof opening of the zone to be managed The signal required for this function is normally an open relay contact When the EMS calls for the compressor to shut off the relay contacts should close Make sure that at least 15 of the EMS wire extends into the roof opening 7 CCC 2 system only If an Automatic Generator St...

Page 10: ... Align the thermostat with the back plate and snap into position FIG 12 4 Conductor Communication Cable 2 LCD SZ System Wire colors listed for the communication cable 3 conductor cable match the wire colors in the unit wire harness and the wire harness at the LCD SZ electronic control box Available wire colors may vary a Remove the cover from the LCD SZ thermo stat Depress tab on bottom of thermos...

Page 11: ...to the side of the roof opening to access wiring H CCC 2 System Only Configuration 1 Electronic Control Configuration Depending on the equipment options installed by the RV manufacturer the appropriate dip switches will need to be switched to the ON position Placing the switch in the ON position selects that option See FIG 16 FIG 17 FIG 18 FIG 16 Dip Switches Dip switches are in the OFF position w...

Page 12: ...position h Gen Start selection Leave in the OFF position i Install unit electrical box cover and out side plastic shroud j Repeat this procedure for each additional zone FIG 18 On Position Off Position I 120 Vac Power Supply Connection 1 ELECTRICAL SHOCK HAZARD Make sure 120 Vac power is disconnected from RV Failure to obey this warning could result in death or serious injury 2 ELECTRICAL SHOCK HA...

Page 13: ...ill be necessary Wires must not extend beyond the locators See FIG 26 FIG 26 Housing Assembly Hinge Slots Strain Relief Cover Wires Trimmed And Correctly Located In Locator Stops Hinge Posts 9 While holding the strain relief cover position the housing s hinge posts into the hinge slots and press down until both lock into place See FIG 26 10 Close the strain relief cover and housing by hand Squeeze...

Page 14: ...nal 5 Connect the orange wire protruding from the roof opening to the wire of the three wire cable that goes to the thermostat COMMS terminal K CCC 2 System Low Voltage Wire Connections Make sure the positive 12 Vdc terminal is disconnected from supply battery Oth erwise damage to unit could occur 1 Connect the previously run 12 Vdc supply wires to the red and black wires protruding from the roof ...

Page 15: ...pth gauge Do NOT drill without depth gauge to en sure bit does NOT penetrate cold air duct 7 Match 3 lag with bonded sealing washer 8 Drive screw using 9 16 socket Finish installa tion with socket until base pan is lightly seated on Dometic cubes See FIG 30 Tighten mounting bolts to achieve proper foam block compression Overtightening could damage unit s base pan Under tighten ing will allow an in...

Page 16: ...s do not work disconnect the 120 Vac and 12 Vdc power supplies and verify that all wiring is correct N CCC 2 System Only Reset Checkout 1 System Reset After setting the dip switches in the electronic control do a system reset a Re connect the 12 Vdc and 120 Vac power supplies b Make sure the CCC 2 thermostat is in the OFF mode c Simultaneously press the MODE and ZONE buttons The LCD will display I...

Page 17: ...rning and giving it a head start on the expected high outdoor ambient will greatly improve its ability to maintain the desired indoor temperature For a more permanent solution to high heat gain acces sories like Dometic outdoor patio and window awnings will reduce heat gain by removing the direct sun They also add a nice area to enjoy company during the cool of the evening B Condensation The manuf...

Page 18: ...18 A Simple RV Wiring Diagram OPTIONAL 12 VDC INPUT 2 WIRES 12 VDC INPUT 2 WIRES FIG 35 WIRING DIAGRAMS ...

Page 19: ...ASSED DIELECTRIC REVERSING VALVE BR WHT WHT BR START CAP RED WHT BLK BLU FIG 39 B Unit Wiring Diagrams 1 H541815A H541816A Wiring Diagram P2 1 3 2 4 5 6 P1 RELAY T1 NO YEL P3 P4 P5 T6 T7 BLU P6 YEL BLU RED BLK T4 RELAY NO K2 COM BLK K1 T5 T3 RED WHT COMPRESSOR DIELECTRIC USE COPPER 60 Hz 1ɸ 115 VAC CONDUCTORS ONLY 3312441 045 TO T STAT RJ 11 CABLE SENSOR FREEZE YEL BLK FACTORY WIRING FIELD WIRING ...

Reviews: