![Dometic 620515.321 Installation Instructions Manual Download Page 7](http://html1.mh-extra.com/html/dometic/620515-321/620515-321_installation-instructions-manual_2518161007.webp)
7
620515, 620525, 620526, 630515 & 630516 Installation Instructions
3.
If a Remote Temperature Sensor is used, the con-
nector end must be routed to the roof opening of the
system which it will control. Make sure that at least
15" of the sensor cable extends into the roof open-
ing. Refer to the Remote Sensor Instructions for
details of the installation. See Section E-1.
4.
If a furnace is to be controlled by the system, the two
furnace thermostat leads must be routed to the roof
opening of the air conditioner that will control it.
Make sure that at least 15" of the furnace thermostat
wires extend into the roof opening.
5.
If an Energy Management System (load shed fea-
ture) is to be used with the control, two wires must
be routed to the roof opening of the zone to be
managed. The signal required for this function is
normally open relay contact. When the EMS calls
for the compressor to shut off, the relay contacts
should close. Make sure at least 15" of the EMS
wires extend into the roof opening.
6.
Route a 4-conductor control cable from the Comfort
Control Center™ mounting position into the
14-1/4" x 14-1/4" (±1/8") roof opening. Make sure
that at least 15" of the wire extends into the roof
opening and 6" extend from the wall at the mounting
position of the Comfort Control Center™. See
Section E-2.
Air Distribution Duct Sizing & Design Chart For Ducted Applications
Return Air Cover Model
3105007.XXX
3308120.XXX
3105935.XXX
Genesis Air Filtration System
Roof Cavity Depth
2.0 In. Min. - 5-1/2 In. Max.
2.0 In. Min. - 5-1/2 In. Max.
Duct Cross Sectional Area
21.0 Sq. In. Min.
32.0 Sq. In. Min.
Duct Size
Depth
1-1/2 In. Min. - 2-1/2 In. Max.
2.0 In. Min. - 2-1/2 In. Max.
Width
7.0 In. Min. - 10.0 In. Max.
8.0 In. Min. - 10.0 In. Max.
Total Duct Length
15.0 Ft. Min. - 40.0 Ft. Max.
15.0 Ft. Min. - 40.0 Ft. Max.
Duct Length (short run)
1/3 Total Duct Length
1/3 Total Duct Length
Center Duct System (Only)
Depth
2.0" In. Min. - 2.0" Max.
Width
8.0 In. Min. - 8.0 In. Max.
Total Duct Length
15.0 Ft. Min. - 40 Ft. Max.
Duct Length (Short Run)
1/3 Total Length
Register Requirements
Number Required Per Run
4 Min.
4 Min.
Register Free Air Area
14.0 Sq. In.
14.0 Sq. In.
Distance From Duct End
5.0 In. Min. - 8.0 In. Max.
5.0 In. Min. - 8.0 In. Max.
Distance From Elbow
15.0 In.
15.0 In.
Total System Static Air Pressure
Blower at High Speed,
Filter & Grill In Place
0.12 - 0.65 In. W.C.
0.12 - 0.65 In. W.C.
Note: Duct sizes listed are inside dimensions.
7.
In the event that other Air Conditioners are installed
(additional zones) an additional 4-conductor control
cable must be routed to the other Air Conditioners.
Make sure that at least 15" of the wire extends into
the roof opening. See FIG. 31.
8.
If an automatic generator start kit (AGS) will be
installed, a 4-conducter control cable must be
routed from the last air conditioner to location of
AGS kit. Follow AGS kit instructions for installation.
E. Dometic Comfort Control Center™ & Cable
Installation
1.
Location
a.
If the system is to be used WITHOUT a Re-
mote Temperature Sensor, the proper loca-
tion of the Comfort Control Center™ is very
important to ensure that it will provide a comfort-
able RV temperature. Observe the following
rules when selecting a location:
•
Locate the Comfort Control Center™ 54"
above the floor.
•
Install the Comfort Control Center™ on a
partition, not on an outside wall.
•
NEVER expose it to direct heat from lamps,
sun or other heat producing items.