D.  Wiring Requirements

1.  

Route a copper, with ground, 120 Vac supply 

wire from the time delay fuse or circuit breaker 

box  to  the  roof  opening.  Use  a  listed/certified 

non metallic - sheathed single strand cable. See 

"A. Table - Unit Data" on page (4).

a.  This supply wire must be located in the front 

portion of the roof opening.

b.  The power 

MUST

 be on an appropriately 

sized separate time delay fuse or circuit 

breaker. See "A. Table - Unit Data" on page 

(4).

c.  Make sure that at least 15" of supply wire 

extends into the roof opening. This ensures 

an easy connection at the junction box.

d.  Protect the wire where it passes into the 

opening with approved method.

2.  12 volt DC supply comes from control box.
3.  Thermostat Communication Cable

a.  LCD SZ Thermostat

I.  Route a 3 conductor communication ca-

ble, 18-22 AWG, from the roof opening 

to the Liquid Crystal Display Single Zone 

(hereinafter referred to a LCD SZ) ther-

mostat mounting location. Make sure that 

at least 15" of the wire extends into the 

roof opening and 15" extends from the 

wall at the thermostat mounting location. 

See "E. Choosing Thermostat Location" 

on page (8).

4.  If system includes a gas furnace, route two 18-

22 AWG thermostat wires from the furnace to 

the roof opening of the unit that will control it. 

If more than one furnace is to be used, route 

the second set of thermostat wires to the second 

unit. Make sure that at least 15" of wire extends 

into the opening.

If converting from Bi-Metal Thermostat to 

Single Zone Thermostat, see "I. LCD SZ 

System Low Voltage Wire Connections" 

on page (12) for wiring details.

E.  Choosing Thermostat Location

1.  LCD SZ system

a.  The proper location of the thermostat is very 

important to ensure that it will provide a com-

fortable RV temperature. Observe the follow-

ing rules when selecting a location.

 

● Locate the thermostat 54" above the floor.

 

Install the thermostat on a partition, not 

on an outside wall.

 

NEVER

 expose the thermostat to direct 

heat from lamps, sun, or other heat pro-

ducing items.

 

Avoid locations close to doors that lead 

outside, windows, or adjoining outside 

walls.

 

Avoid locations close to supply registers 

and the air from them.

INSTALLATION INSTRUCTIONS

FIG. 7

Duct Size And Requirements For 3105007.XXX And 3105935.XXX RAG

Register Required

Registers

4 Min - 8 Max.

(Per Unit)

14 Sq. In. Free

Area Per Register

Summary of Contents for 520300.501

Page 1: ...ic Control Kit Thermostat Optional Indoor Temperature Sensor Air Conditioner LCD SZ Controls 57908 59712 57915 59516 59530 520300 520310 520315 520316 600312 600315 3316155 000 Thermostat Included Wit...

Page 2: ...NFORMATION 14 A Frost Formation On Cooling Coil 14 B Heat Gain 14 C Condensation 14 D Air Distribution 14 WIRING DIAGRAMS 15 A Simple RV Wiring Diagram 15 B Unit Wiring Diagrams 16 DOCUMENT SYMBOLS In...

Page 3: ...all safety information and instructions to avoid possible injury or death Read and understand these instructions be fore installing using servicing performing maintenance on this product Incorrect ins...

Page 4: ...kW 59530 532 N A 8 0 53 0 2 5 5 8 18 5 15 Amp 3 5 kW 5 0 kW 59530 536 N A 7 8 53 0 2 0 5 6 19 0 15 Amp 3 5 kW 5 0 kW 520310 501 9 000 7 8 49 0 3 0 8 5 20 0 20 Amp 2 5 kW 4 0 kW 520315 501 13 500 10 3...

Page 5: ...n Amount of insulation in walls and roof Geographical location where the RV will be used Personal comfort level required 1 For one unit installation The unit should be mounted slightly forward of cent...

Page 6: ...e are no obstacles wires pipes etc inside RV s roof floor walls Shut OFF gas supply disconnect 120 Vac power from RV and disconnect positive 12 Vdc terminal from supply battery BEFORE drilling or cutt...

Page 7: ...ame Duct Duct Frame Frame Roof Opening Roof Opening AC Power Supply Wire Low Voltage Wires 12 Vdc Furnace Indoor Temperature Sensor Cable Control Wires Roof SIDE VIEW TOWARD BACK OF RV Duct Ceiling Du...

Page 8: ...location See E Choosing Thermostat Location on page 8 4 If system includes a gas furnace route two 18 22 AWG thermostat wires from the furnace to the roof opening of the unit that will control it If...

Page 9: ...lors listed for the communication cable 3 conductor cable match the wire colors in the unit wire harness and the wire harness at the LCD SZ electronic control box Available wire colors may vary a Remo...

Page 10: ...et Electrical Cord 120 Vac Power Supply Control Wires 5 Hold the ceiling template up to the roof opening Make sure the large plate faces the rear of the RV See FIG 13 a Start each mounting bolt throug...

Page 11: ...supplied with the RAG kit Remove the backing paper from the insulation and care fully stick onto the ceiling template divider plate See FIG 16 FIG 16 Foam Tape Place Insulation In Position Do Not Cov...

Page 12: ...hermo stat wires if applicable to the blue wires protruding from the roof opening or to the 1 4 connectors at the electronic control box using the supplied 1 4 insulated connectors The polarity of thi...

Page 13: ...eiling tem plate 3 Install cover to template using six 6 supplied 8 x 10 mm blunt point Phillips head screws 4 Re install filter return air grille into return air cov er Align tabs with mating notches...

Page 14: ...hades blinds and or curtains 3 Keeping windows and doors shut or minimizing usage 4 Avoid the use of heat producing appliances Operation on High Fan Cooling mode will give optimum or maximum efficienc...

Page 15: ...15 A Simple RV Wiring Diagram OPTIONAL FIG 21 WIRING DIAGRAMS...

Page 16: ...540 J4 J3 4 3 2 1 J5 FURNACE FURNACE 2 1 12V TSTAT 12V TSTAT PART No 3316300 000 FOR USE WITH AIR CONDITIONER PASSED DIELECTRIC FACTORY WIRING FIELD WIRING FAN LO J2 BLK 2 1 BLU 3 4 N C RED 3 1 4 2 P...

Reviews: