Dometic 39626.501 Installation Instructions Manual Download Page 13

13

INSTALLATION INSTRUCTIONS

Where the return air must be provided through louvers
or mesh screen, the FREE AREA percentage of the
material used shall be taken into consideration when
making this determination. An example of how to
determine FREE AREA is included in "3.2.2. Outside
Coil".

B. Grills (See FIG. 3.4)

Note: The return air grill must have the same square
surface as the return air duct.
1. For each system, there must be a return grill to

bring vehicle air back into the unit. There must also
be at least four discharge grills per unit.

2. Return grills must be mounted in front of the inside

coil. If this is not possible, make sure there is
nothing blocking the air flow from the grill to the
inside coil.

3. The unit must have a return filter between the grill

and the unit. This filter must be accessible for
periodic cleaning.

C. Discharge Air (See FIG. 3.4)

The air diffusion system, supplied by the installer,
must be sized to maintain a static pressure at the
blower outlet between 0.40 (minimum) and 1.20 (maxi-
mum) inches water column.

The installer has the options of side discharge or top
discharge and side return. The unit can be ordered
originally with the inside blower mounted to discharge
the air as required. If the installer needs to change the
direction of the discharge it is necessary to rotate the
inside blower housing 90 degrees.

All air handling ducts must be properly insulated to
prevent condensation forming on their surface during
operation. A vapor barrier must also be supplied on the
outer surface of the insulation to prevent moisture from
traveling through the insulation and condensing on the
cold duct work.

D. Condensate Drain

A condensate drain tube is located on bottom of the
base pan, under the return air opening.
1. The installer needs to install the condensate drain

into the base pan and ensure a snug fit.

2. A 3" diameter hole must be provided for installation

of the tube and clearance. See Figure 2.11.
Note: Condensate will not drain properly if drain
tube is not installed or missing.

The outside coil is a "draw-through" type. When the
face of the coil is positioned behind a louvered or other
type of restrictive opening, the FREE AREA of the
opening must be at least 648 square inches.

FIG. 3.3

8

8

2

2

2

1/2

1/2

1/2

1/2

36
64

EXAMPLE OF HOW TO DETERMINE FREE
AREA OR % OPEN AREA:

TOTAL AREA =

8 X 8

=

64

FREE AREA

=

2 X 2 X 9 openings

=

36

% OPEN AREA

=

=

56%

B. Free Area

Free area is the opening that remains in a grill or
louvered panel after the restrictions are taken away.
For example, an opening of 10 x 20 inches has 200
square inches. When this opening is covered with a
grill that is 56 percent open the FREE AREA is (200
x .56), 112 square inches. See FIG. 3.3.
Expanded and perforated metal grills in general vary
from 30 percent to 60 percent open. Be certain that
648 square inches of FREE AREA is available to the
face of the outside coil.
Note: Service access must always be supplied either
as clearance or as a defined access panel.

Do not install the unit where the fan will draw
air from the exhaust of the vehicle, a motor
generator set, transmission, road heat or
any other heat producing source.

CAUTION

3.2.3 MOUNTING
The Model 39626 Air conditioner and 39726 Heat Pump units
design are for installation below the floor. This unit should be
mounted in an angle-iron frame, designed and built for the
Model 39626 and 39726. Frame rails should not restrict the
condenser air discharge opening.

Important:

 Do not mount the Units in a sealed com-

partment. Recirculation of hot condenser discharge air
will cause high system pressure and trip breakers.

3.2.4 CLEARANCES

A. The unit clearances depend on:

1. Inlet air access used;
2. Discharge air duct arrangement;
3. Return air duct;

Allow a minimum of eight (8) inches for the return air

duct. Access to the electrical connections must be
provided when making the installation.

3.2.5 INSIDE COIL SECTION

A. Return Air

The inside coil must have free access to room air. A
minimum of 135 square inches of FREE AREA
opening is required.

It is the responsibility of the installer to en-
sure that the drain tube is installed properly
and that it will not leak. Dometic Corporation
will not be liable for any structural damage
due to improperly installed, sealed or re-
stricted drain tube.

CAUTION

Summary of Contents for 39626.501

Page 1: ...of this product can be extremely hazardous and could result in personal injury or property damage 39626 501 39626 506 39726 501 39726 506 US Important Instructionsmuststaywithunit Owner read carefull...

Page 2: ...2 4 HIGH POT REQUIREMENTS PAGE 8 2 5 MOUNTING IN COACH PAGE 9 2 6 WIRING DIAGRAM 39726 501 39726 506 PAGE 10 2 7 SPECIFICATIONS HEAT PUMP PAGE 10 2 8 WIRING DIAGRAM 39626 501 39626 506 PAGE 11 2 9 SPE...

Page 3: ...ructions UNDERSTAND SIGNAL WORDS Asignal word WARNING OR CAUTION is used with the safety alert symbol They give the level of risk for potential injury indicates a potentially hazard ous situation whic...

Page 4: ...illdirecttheairtothesources of the greatest heat loss and or heat gain The effects of the gain or loss can then be offset by the supply air It is important that the selection of the diffusers and gril...

Page 5: ...the smallest size duct that will do the job of delivering required airflow rate with pressure available Nosinglesizeofductwillprovetobeidealfor all jobs B Length of Duct Pressure loss increases as du...

Page 6: ...es R W D R W RR Radius Ratio RR or RR 1 5 FIG 2 4 PREFERRED Standard FAIR POOR NOT ACCEPTABLE Various Elbows Showing Radius Ratios FIG 2 3 R b R a D W CR R a R b Curve Ration CR Optimum Reading CR 05...

Page 7: ...orizontally projected air streams The air stream from the outlet tends to hug the surface As a matter of fact this characteristic is almost essential for goodcomfortairconditioning Therefore rathertha...

Page 8: ...ct Area Requirement See Figure 2 10 3 Return air to the system must be filtered to prevent dirtaccumulationontheevaporatorcoolingsurface 4 Returnairopeningmustbewithinminimumsspeci fied in the system...

Page 9: ...nd reg ister location so that you receive maximum performance from the system These instructions DO NOT cover or warrant the final installation of the duct work that carries conditioned air within the...

Page 10: ...s When sizing the generator the total electrical power must be taken into consideration Keep in mind that generators lose power because of altitude increases above sea level high outdoor temperatures...

Page 11: ...acity 26 000 Volts Phase Hertz each circuit 115 AC 1 60 Run Amps Comp Circuit 1 10 1 Circuit 2 9 8 LRA Compressor Circuit 1 59 0 Circuit 2 59 0 Total Blwr Fan Motor Run Amps 8 5 Circuit 1 Total Blwr F...

Page 12: ...structions carefully before attempting to start your unit installation B Dometic Corporation will not be liable for any damages or injury incurred due to failure in the following of these instructions...

Page 13: ...aw through type When the faceofthecoilispositionedbehindalouveredorother type of restrictive opening the FREE AREA of the opening must be at least 648 square inches FIG 3 3 8 8 2 2 2 1 2 1 2 1 2 1 2 3...

Page 14: ...olators should be used at each mounting point 12 VDC required for thermostat operation INSULATED DUCT Minimum Maximum 45 IN 2 80 IN 2 3 depth Min FIG 3 4 Supply Duct must be insulated Supply Duct from...

Page 15: ...ng area is normally a good location Note If the system is to be used with a Remote Temperature Sensor the Comfort Control Center may be mounted anywhere that is convenient in the coach 8 Try to avoid...

Page 16: ...differential between the first and second stage is preset and cannot be changed E Turn ON the furnace dip switch when a furnace is connected to the blue wires off the control board F Differential dip...

Reviews: