EN
CRX
Troubleshooting
37
Compressor does not run (battery connection)
5
Overheating of the elec-
tronics unit
If the cooling system is loaded too heavily or
the temperature is set too high, the electron-
ics can overheat.
Constantly
Temperature sensor
errors
Temperature sensor is defective.
Problem
Possible cause
Remedy
U
Term
= 0 V
There is an interruption in the
battery – electronics connection
Establish a connection
Main switch faulty (if installed)
Replace the main switch
Additional supply line fuse has blown
(if installed)
Replace the supply line
fuse
U
Term
≤
U
ON
Battery voltage is too low
Charge the battery
Start attempt with
U
Term
≤
U
OFF
Loose cables
Poor contact (corrosion)
Establish a connection
Battery capacity too low
Replacing the battery
Cable cross section too small
Replace the cable
(fig.
Start attempt with
U
Term
≥
U
ON
Ambient temperature too high
–
Insufficient ventilation
Move the refrigerator to
another location
Condenser is dirty
Clean the condenser
Electric circuit between
the pins in the compres-
sor interrupted
Defective compressor
Contact customer service
U
Term
Voltage between the positive and negative terminals of the electronics
U
ON
Cut-in voltage of the electronics
U
OFF
Cut-off voltage of the electronics
Number of
flashes
Fault
Possible cause
DometicCRX50-65-80-110-140_IOM_4445103148_APAC(en)_20xx-xx-xx.book Seite 37 Dienstag, 1. Juni 2021 5:24 17