DIP switches 
 

 

Back of the PCB 
 

BUS END:

 if ON, the bus is terminated (if last 

device on the line) 
 

USR:

 

   not  used,  reserved  for  future 

applications 
 

INIT:

 

sets  the  controller  into  default  state 

and sets bus address to 1, baud rate to 9600.  
 
To init, proceed as follows: 
- connect the device over RS485 to a PC with 
ModComTool config tool 
- set INIT to ON 
- apply power (use only the connector 
without bottom) 
- find the controller in the tool (Scan) 
 

Installation 
 

 

Units  are  intended  for  operating  in  a  normal  and  chemically  non-aggressive 
environment. They do not need any servicing or maintenance. Install them in a vertical 
position at places where they can be operated easily and measure correct values of 
temperature, i.e. in the height of about 150 cm, with no direct sunlight or other heat / 
cool source (AHU outlets, refridgerator, electrical appliances). The device consists of 
two parts: bottom with screw terminal block and cover containing PCB, display, and the 
knob. The bottom part is fixed by 2 or 4 screws to any flat surface or a flush-mounting 

box Ø 50 mm. At the back of the bottom there is an aperture for cabling. The bottom 

should be installed and cabling connected first, and the upper part inserted after the 
construction works have been finished to prevent damage to the unit.  
 
Seal the conduits to avoid influencing the sensor by draught. Use insulating pad when 
installing the sensor on cold walls. Avoid sensor exposition to sunlight or other heat 
sources. 
 

 

Opening the 
cover 
 
 

When removing the display part, proceed as follows: 
 

-

 

press gently the side parts of the unit and pull the right of the display part by 
several milimeters 

-

 

pull the left of the display part 

-

 

pull the display part and remove it from the bottom. 

 
Do not bend the display part too much, the connector pins could be damaged. The locks 
are only at the sides of the display part, not at the top nor bottom. 
 

Summary of Contents for UC120

Page 1: ...gorithm brought to one 0 10 V DC output All values are displayed on a large LCD display The functionality and control parameters i e P and I constants and hysteresis can be set with ModComTool the configuration software which is free to download at http domat int com en downloads software The controller contains real time clock with a weekly scheduler 6 events per day It changes between three oper...

Page 2: ...current Resolution 1x 0 10 V DC 10 mA corresponding to 1 kOhm load 50 mA tolerant to permanent short circuit 10 bit D A converter Setpoint correction according to configuration 10 to 1 K Communication RS485 separation Baud rate 2 wire RS485 Modbus RTU slave optically separated up to 1000 V selectable 1200 9600 115200 bps Display LCD 60 x 60 mm Terminals screw terminals for 0 14 1 5 mm2 wires Cover...

Page 3: ...erator electrical appliances The device consists of two parts bottom with screw terminal block and cover containing PCB display and the knob The bottom part is fixed by 2 or 4 screws to any flat surface or a flush mounting box Ø 50 mm At the back of the bottom there is an aperture for cabling The bottom should be installed and cabling connected first and the upper part inserted after the construct...

Page 4: ...m the event selection Turn the knob to select the operation mode Day Night Off Event inactive invoked by this event If the event is not active the operation mode is not changed at the set time Short push to confirm the operation mode setting The event time displays Turn the knob to set the time of the event and confirm by a short push Then turn the knob to select another event or long push and tur...

Page 5: ...sted value by a short push Turn knob to change value Confirm by a short push again If there is no user activity for 30 s the controller goes to the basic display mode Default values The default values as well as all other settings PI parameters address baudrate can be set by the configuration program ModComTool Dimensions All dimensions in mm ...

Page 6: ... Belden 8205 cable A terminal is designed for maximum 3 wires of 0 8 mm2 Temperature compensation After switching the unit on allow about 90 mins to dissipate the heat inside of the housing Then the sensor is measuring correctly Do not change the sensor correction variable immediately after powering the device on RoHS notice The device contains a non rechargeable battery which backups the real tim...

Page 7: ... versions 08 2016 Changed reference to the configuration software Added picture and description of the installation and link on the datasheet with other colours 03 2017 Added picture and description of the installation and link on the datasheet with other colours ...

Reviews: