G
KINASGARD
®
RBWF ⁄ LF
Rev. 2020 - V23
Schematic diagram
RBWF ⁄ LF
Connecting diagram
RBWF ⁄ LF
Measuring ranges
selectable
DIP
1
DIP
2
DIP
3
DIP
4
0…500 Lux
O N
OFF
OFF
OFF
0
…
1
kLux
(default)
OFF
O N
OFF
OFF
0… 5 kLux
OFF
OFF
O N
OFF
0… 20 kLux
OFF
OFF
OFF
O N
13 11 12
offset time
1 2 3 4
ON
1
2
3
0,5
kLux
1 kLux 5 kLux 20 kLux
4'' 16'
UB+ 24V AC/DC
Output Light
Intensity in lux
UB- GND
Normall
y
open c
ont
act
Br
eak
er
Pr
esenc
e
aft
er-running
Brightnes
s
corr
ection
Presence
detector
1
2
3
13
11
12
UB- GND
UB+ supply voltage 24V AC/DC
Output light intensity 0-10V (linearised)
Breaker
Normally
open contact
changeover
(24 V)
The room motion and light sensor and presence detector
KINASGARD
®
RBWF-LF
is a combined instrument that detects motion and light intensity using a diffuser as
well as the presence of persons and is used to recognize conditions. RBWF-LF
issues a standard signal of 0 - 10 V or 4...20 mA for light intensity and has a switching
(normally open contact) output for detecting motion.
This multi-sensor is used in building automation, in corridors, at workplaces, in
industrial halls, in offices and business facilities for the control of lighting as needed,
e.g. to control sunshade equipment, for daylight-dependant constant light control,
for activating Venetian blinds or luminaries, for automatic energy conservation, and
to avoid unnecessary heating-up or cooling of unoccupied rooms.
TECHNICAL DATA
Power supply:
24 V AC (± 20 %); 15...36 V DC for U variant
15...36 V DC for I variant, depending on working
resistance, residual ripple stabilised ± 0.3 V
Working resistance:
R
a
(ohm) = (U
b
-14 V) ⁄ 0.02 A for I variant
Load resistance:
R
L
> 5 kOhm for U variant
Power consumption:
< 1 W at 24 V DC; < 2 VA at 24 V AC
Sensor:
infra-red motion sensor and light sensor with diffuser
Output, motion sensor: without ⁄ with presence, potential-free
normally open contact (24 V), 1 A ohmic load
After-running time:
adjustable from 4 s to 16 min
Measuring ranges:
multi-range switching
(via DIP switches)
with 4 switchable measuring ranges
0...500 Lux ⁄ 1 kLux ⁄ 5 kLux ⁄ 20 kLux
(other individual ranges optional, e. g. 100 kLux)
Output, light sensor:
0 -10 V (linearised, active, 3-wire connection) or 4...20 mA
Deviation, light sensor:
typically < 5 % of final value
Ambient temperature:
0...+50 °C
Electrical connection:
0.14 - 1.5 mm², via terminal screws
Housing:
plastic, material ABS,
colour pure white (similar to RAL 9010)
Dimensions:
85 x 85 x 27 mm (Baldur 1)
Installation:
wall mounting or on in-wall flush box, Ø 55 mm, base
with 4-hole for mounting on vertically or horizontally
installed in-wall flush boxes for cable entry from the
back, with predetermined breaking point for on-wall
cable entry from top ⁄ bottom in case of plain on-wall
installation
Protection class:
III (according to EN 60 730)
Protection type:
IP 20 (according to EN 60 529)
Standards:
CE conformity, electromagnetic compatibility according to
EN 61 326, EMC directive 2014 ⁄ 30 ⁄ EU
Type ⁄ WG01
Detection, Measuring Range
Output
Item No.
RBWF ⁄ LF
Room motion sensor and light sensor
RBWF-LF-U
Pr Motion: Yes ⁄ No (relay on ⁄ off)
Changeover contact
9401-41A1-1100-000D1
Light Intensity: 0...500 Lux ⁄ 1 kLux ⁄ 5 kLux ⁄ 20 kLux
0 - 10 V
(linearised)
RBWF-LF-I
Pr Motion: Yes ⁄ No (relay on ⁄ off)
Changeover contact
9401-41A1-3200-000D1
Light Intensity: 0...500 Lux ⁄ 1 kLux ⁄ 5 kLux ⁄ 20 kLux
4 … 20 mA
RBWF
Room motion sensor
RBW F -W
Pr Motion: Yes ⁄ No (relay on ⁄ off)
Changeover contact
9401-41A0-4000-000D1
RHKF
Room light intensity sensors
RHK F -I
Light Intensity: 0...500 Lux ⁄ 1 kLux ⁄ 5 kLux ⁄ 20 kLux
4 … 20 mA
9601-41A2-2000-000D1
RHK F -U
Light Intensity: 0...500 Lux ⁄ 1 kLux ⁄ 5 kLux ⁄ 20 kLux
0 - 10 V
9601-41A1-2000-000D1
Extra charge:
Other individual measuring ranges optional, e. g. 100 kLux
on request