MODBUS
FC013 Fancoil controller
Release 18.12.2014 ver. 01900
presence off
delay
38 MSB
R,W
EEPROM
delay to switch off the
Comfort/Day mode after DI
changes
(default = 0 min)
0...255 minutes
step temp
39 LSB
R,W
EEPROM
step for user temperature
setpoints setting
(default = 0.5 °C, 0x32)
step = read value / 100
10 … 0.1
50 … 0.5
100 … 1 etc.
step minutes
39 MSB
R,W
EEPROM
time step for time schedule setting
(default = 5 mins, 0x05)
in minutes
fan minimum
40 LSB
40 MSB
R,W
EEPROM
minimum fan level for Comfort/Day
mode (other modes have fixed
minimum of 0 %)
(default = 0 V)
in 0,01 V
range 0...1000 =
0 V .. 10,00 V
show mode
41 LSB
R,W
EEPROM
data that roll on the LCD display
(default = 1)
If only one of the bits is active
there is only one value displayed.
Otherwise they change
periodically after
show time
.
bit 0 … temperature
bit 1 … outside temp.
bit 2 … current time
bit 3 … temperature
correction
(default = temperature,
0x0001)
fan start delay
41 MSB
R,W
EEPROM
delay between heating valve
activation and fan start, for heating
only (prevents circulation of cold
air at startup)
in secs/10
2 ... 20 s
5 ... 50 s
show time
42 LSB
R,W
EEPROM
time (in 100 ms) to display each
value in show mode (default = 3 s,
0x1E)
see
show mode
edit return time
42 MSB
R,W
EEPROM
time (in secs) of user inactivity to
return from edit mode to show
mode (default = 30 s, 0x1E)
quick edit mode
number
43 LSB
R,W
EEPROM
number of mode which is editable
through quick edit menu (short
push of the knob)
(default = presence mode, 0x01)
0 ... push function inactive
1 ... presence mode
2 ... fan mode
change-over
period
43 MSB
R,W
EEPROM
time delay when switching
between heating and cooling
modes (default = 30 min, 0x1E)
in minutes, range 1...255
long push time
44 LSB
R,W
EEPROM
time (in 100 ms) evaluated as long
push (go to time schedule menu /
leave menu)
(default = 1.5 s, 0x0F)
for editing of the time
schedule and presence or
fan mode
[range
0.1…25.5 s]
super long push
time
44 MSB
R,W
EEPROM
time (in 100 ms) evaluated as
superlong push (go to settings
menu)
(default = 5 s, 0x32)
for actual time and
temperature settings
[range 0.1…25.5 s]