Maintenance-free duct sensor
AERASGARD
®
KLQ-SD
with active output, automatic calibration (fixed), in a compact plastic housing with snap-on lid,
for determining the air quality in three VOC sensitivity levels (low/medium/high). The measuring transducer converts the measured values into a
standard signal of 0 -10 V.
Maintenance-free duct sensor
AERASGARD
®
KLQ-W
with active/switching output, automatic calibration (can be deactivated), in a compact plastic
housing with quick-locking screws, for determining the air quality in three VOC sensitivity levels (low/medium/high). The measuring transducer
converts the measured values into a standard signal of 0 -10 V or 4...20 mA (switchable).
The sensor is used in offices, hotels, convention centres, apartments, shops, etc. for the purpose of evaluating the indoor climate. This enables
energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and improving well-being.
The air quality is detected by a
VOC sensor
(mixed gas sensor for volatile organic substances). This sensor determines the loading of the room air
due to contaminated gases such as cigarette smoke, body perspiration, exhaled breathing air, solvent vapours, emissions from building components,
etc. With regard to the expected air contamination, low, medium or high VOC sensitivity can be selected.
TECHNICAL DATA
Power supply:
24 V AC ⁄ DC (± 10 %)
Power consumption:
< 1.5 W ⁄ 24 V DC typical;
< 2.9 VA ⁄ 24 V AC typical; peak current 200 mA
Sensor:
VOC sensor (metal oxide) (VOC = volatile organic compounds), with manual calibration (via zero button),
KLQ - SD
with automatic calibration (fixed)
KLQ -W
with automatic calibration (can be deactivated via DIP switches)
Measuring range:
0...100 % air quality; referred to calibrating gas;
multi-range switching
(selectable via DIP switches)
VOC sensibility low, medium, high
Output:
(0 V = clean air, 10 V = polluted air)
KLQ - SD
0 -10 V (fixed)
KLQ - W
0 -10 V
or
4...20 mA, working resistance < 800 Ω
(selectable via DIP switches), with offset potentiometer (± 10 % of the measuring range)
Relay output:
KLQ - SD
without changeover contact
KLQ - W
with potential-free
changeover contact
(24 V / 1 A), switchpoint adjustable
Measuring accuracy:
typical ± 20 % of final value (referred to calibrating gas)
Service life:
> 60 months (under normal load conditions),
depending on the type of loading and gas concentration
Gas exchange:
by diffusion
Warm-up time:
approx. 1 hour
Response time:
approx. 1 minute, minimum flow rate 0.3 m / s (air)
Ambient temperature:
–10...+60 °C
Electrical connection:
0.14 - 1.5 mm
2
, via terminals
Housing:
plastic, UV-stabilised, material polyamide, 30 % glass-globe-reinforced,
colour traffic white (similar to RAL 9016),
KLQ - SD
with snap-on lid,
KLQ -W
with quick-locking screws
(slotted ⁄ Phillips head combination)
Housing dimensions:
72 x 64 x 37.8 mm (Tyr 1/Tyr 01 without display)
Cable connection:
cable gland
, plastic (M 16 x 1.5; with strain relief,
exchangeable, max. inner diameter 10.4 mm)
Protective tube:
PLEUROFORM
TM
, material polyamide (PA6), with torsion protection,
Ø 20 mm, NL = 202.5 mm, v
max
= 30 m/s (air)
Process connection:
by mounting flange, plastic (included in the scope of delivery)
Protection class:
III (according to EN 60 730)
Protection type:
KLQ - SD
IP 54
(according to EN 60 529)
*
Housing tested, TÜV SÜD, Report No. 713160960A (Tyr 01)
KLQ - W
IP 65
(according to EN 60 529)
*
Housing tested, TÜV SÜD, Report No. 713139052 (Tyr 1)
*
Housing in the built-in state (permeable PLEUROFORM: IP 30)
Standards:
CE conformity, electromagnetic compatibility according to EN 61 326, EMC Directive 2014 ⁄ 30 ⁄ EU
AERASGARD
®
KLQ - SD
Duct air quality sensor and measuring transducer, Standard
AERASGARD
®
KLQ - W
Duct air quality sensor and measuring transducer, Premium
Type ⁄ WG02
Measuring Range
VOC
Output
VOC
Equipment
Item No.
KLQ - SD
(fixed)
IP 54
K L Q - SD -U
0...100 %
0 -10 V
–
9501-3170-1001-200D1
KLQ - W
(switchable)
IP 65
K L Q -W
0...100 %
0 -10 V ⁄
4...20 mA
changeover contact
9501-3150-7301-200D1
Note:
This unit
must not
be used as safety-relevant device!