Configurable Safety System SAFEMASTER PRO
70
0265525 / 16.05.19 en / 101A
OUTPUT MODULE SIGNAL UG 6915/008
UG 6915/008
MEANING
LED
REMED
Y
RU
N
IN
F
AIL
EXT
F
AIL
SEL0÷1
ST
A
TUS1÷8
GREEN
RED
RED
ORANGE
YELLO
W
Inter
nal f
ault
OFF
Flashing
2 or
3 times
OFF
Sho
ws the
ph
ysical address
of the unit
OFF
• Retur
n the unit to DOLD
to be repaired
Compatibility error
OFF
Flashing
5 times
OFF
Flashing
5 times
• Fir
mw
are v
ersion not compatib
le
with control unit, retur
n to DOLD
f
or FW upg
rade
Error in comm
unication
with control unit
OFF
Flashing
5 times
OFF
OFF
• Restar
t the system
• If the prob
lem persists retur
n the
UG 6915
to DOLD to be repaired
Error on other unit
OFF
ON
OFF
OFF
• Restar
t the system
• Chec
k which unit is in F
AIL mode
Same type of e
xpansion
unit with same address
detected
OFF
Flashing
5 times
Flashing
5 times
OFF
• Change the unit's address
(see NODE SEL)
Shor
t circuit or o
ver
load
detected on status 1
÷
8
OFF
OFF
ON
OFF
Flashing
• Chec
k connections at ter
mimals 1
÷
8
P
ow
er supply missing on
status 1
÷
8
OFF
OFF
ON
OFF
Flashing
alter
nativ
ely
• Connect ter
minal 5 to
po
w
er 24
V DC
Error on
node detection circuit
OFF
Flashing
3 times
OFF
Flashing
3 times
OFF
• Inter
nal f
ault
Retur
n the unit to DOLD
to be repaired
T
roub
leshooting