Configurable Safety System SAFEMASTER PRO
62
0265525 / 16.05.19 en / 101A
UG 6911.10
CONTR
OL UNIT UG 6911.10
TR
OUBLESHOO
TING
MEANING
LED
REMED
Y
RU
N
IN
F
AIL
EXT
F
AIL
COM
ENA
IN1÷8
OSSD1÷2
CLEAR1÷2
ST
A
TUS1÷4
GREEN
RED
RED
ORANGE
BLUE
YELLO
W
RED / GREEN
YELLO
W
YELLO
W
Inter
nal f
ault
OFF
Flashing
2 or 3
times
OFF
OFF
OFF
OFF
RED
OFF
OFF
• Retur
n the unit to DOLD
to be repaired
OSSD output error
OFF
Flashing
4 times
OFF
OFF
OFF
OFF
Flashing
4 times
(only the
LED corre-
sponding to
the output
in F
AIL
mode)
OFF
OFF
• Chec
k the OSSD1/2 connections
• If the prob
lem persists retur
n the
UG 6911.10
to DOLD to be repaired
Error in comm
unication
with e
xpansion units
OFF
Flashing
5 times
OFF
OFF
OFF
OFF
OFF
OFF
OFF
• Restar
t the system
• If the prob
lem persists retur
n the
UG 6911.10
to DOLD to be repaired
Expansion unit
error
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
• Restar
t the system
• Chec
k which unit is in F
AIL mode
Memor
y chip O
A 6911
error
OFF
Flashing
6 times
OFF
Flashing
6 times
OFF
OFF
OFF
OFF
OFF
• Replace the O
A 6911
In-Rail-Bus error
Flashing
12
times
OFF
OFF
Flashing
12 times
OFF
OFF
RED
OFF
OFF
• Contact from Control unit or
e
xtension unit to IN-RAIL-B
US not
correct (ref
. System composition)
T
roub
leshooting