9. Putting into Service

Installation may only be carried out by an authorized technician. Observe the connection
diagram when installing. All leads to be connected must be dead.
The phase input serves to supply the unit as well as the actuating output.
In order to avoid malfunctions, the length of the line between push-button and the
DRO 1U should not exceed 3 m under normal environmental conditions and 1 m in in-
dustrial environments.

OBSERVE!

In order to make sure that the Dupline signal conductors have identical length,
please always lay both leads (D and -) towards the push buttons or
contacts!

The Dupline signal conductor (Dupline -) should be used as common potential, with the
connection being made directly at the terminal. The following table illustrates the connec-
tion configuration: 

Connections between the Dupline signal and earth potential will cause malfunctions and
are not permissible. Attention should be paid to the correct polarity of the Dupline signal.
Because of the integrated power pack, the DRO 1U will warm up slightly after a short run-
ning time. This is, however, no cause for concern.
In order to meet the requirements for protective low voltage, VDE0100, Part 410, should
be observed and put into practice during installation. For safety reasons mains cables
may not be routed through the same installation box.

10. Indicators

11. Technical Data

Terminal

Description

Terminal

Description

C5

Semiconductor input C5

Brown

Switching channel „UP“

C6

Motor 2 output (

DOWN

/UP)

Brown

Switching channel „DOWN“

C7

Motor 3 output (UP/

DOWN

)

D-

Dupline signal conductor -

Black

Phase input (L

IN

)

D+

Dupline signal con

Blue

Neutral (N)

Indicator

Description

Green “BUS OK”
LED

Dupline bus:
Off - bus fault / On - bus OK 

Min.

Typ.

Max.

Dupline

Current input

10 µA

Input channels 3 (semiconductor inputs C5/C6/C7)

Output channels 2 control channels (shutter „UP“ und „DOWN“)

Summary of Contents for DRO 1U

Page 1: ...eitung Operating Instructions Inhaltsverzeichnis 1 Allgemeines 2 2 Kodierung 2 3 Inbetriebnahme 3 4 Anzeigen 3 5 Technische Daten 3 6 Garantie 4 13 Anschlussschema Connection Diagram 8 Table of Conten...

Page 2: ...forderlichen Umschaltver z gerungen nicht eingehalten werden Dies kann zur Besch digung der Relaiskontakte und der daran angeschlossenen Motoren f hren Zudem ist die st ndige Versorgung des Ger tes mi...

Page 3: ...st die Verbindung direkt an der Klemme herzustellen Folgende Tabelle zeigt die An schlussbelegung Verbindungen zwischen dem Dupline Signal und dem Erdpotenzial f hren zu St rungen und sind nicht zul s...

Page 4: ...prellzeit 10 ms Kontaktinnenwiderstand 1 kOhm Erlaubte Leitungsl nge 3 m in industrieller Umgebung 1 m Ausg nge Art Schaltrelais Nennspannung 230 VAC Nennstrom 2 A Leistungsfaktor cos 0 6 1 Betriebssp...

Page 5: ...ince otherwise the required reverse delays cannot be kept This may lead to damages at the relay contacts and the motors connected to them In addition a permant supply of the device with voltage is nec...

Page 6: ...configuration Connections between the Dupline signal and earth potential will cause malfunctions and are not permissible Attention should be paid to the correct polarity of the Dupline signal Because...

Page 7: ...ms Permissible inh contact resistance 1 kOhm Permissible line length 3 m in industrial environment 1 m Outputs Type Switching relays Rated voltage 230 VAC Rated current 2 A Power factor cos 0 6 1 Oper...

Page 8: ...ra e 11 D 26506 Norden Germany Tel 49 0 4931 1806 0 Fax 49 0 4931 1806 101 E mail Internet info doepke de http www doepke de 3931195 03 10 F Dupline Doepke DRO 1U DRO 1U 230V 2A 230V 2A BUS OK BUS OK...

Reviews: