background image

DFS 4 A

Rated current

16 A

25 A

40 A

63 A

80 A

100 A

125 A

Thermal back-up 
fuse OCPD gG

1)

16 A

25 A

40 A

63 A

80 A

Short-circuit back-
up fuse SCPD gG

1)

100 A

125 A

Inc

 / I�c

2)

  

10 kA

1)

 DIN VDE 0636, IEC 60269 

|

 

2)

 DIN EN 61008-1

Application instructions and warnings

The following notes and warnings must be observed in order to ensure safe opera

-

tion:

1.  Without  any  additional  protective  housing,  the  residual  current  circuit-breaker 

should only be stored and operated in a dry, low-dust environment. Aggressive 
atmospheres must also be avoided.

2.  The user must be made aware of repeat testing using the test button T.
3.  Using surge current strength residual current circuit-breakers cannot absolutely 

guarantee to rule out trips due to leakage currents caused by surge voltage. In 
cases where an interruption of the power supply may lead to potential dangers for 
humans and animals or serious damage to property, residual current protection 
should be implemented by means of increased surge current strength, selective 
residual current circuit-breakers and upstream surge arresters. In specific cases, 
the switching status should be monitored by means of an auxiliary contactor at 
the residual current circuit-breaker and an appropriate signalling device.

4.  Please be aware that the short-circuit back-up fuse (SCPD) does not ensure any 

thermal overload protection. Thermal overloading must be ruled out as a matter 
of priority by means of thorough project planning or using the specified thermal 
back-up fuse (OCPD).

5.  When working on electrical systems, this fuse must always be activated and the 

safety rules must be observed. Should there unexpectedly be any contact with 
active parts, a doctor must be called immediately.

6.  Disposal  is  subject  to  the  statutory  regulations  of  the  European  Union  

(WEEE/German Electrical and Electronic Equipment Act).

7.  Opening the device or removing the safety seal will invalidate the warranty.

Notes for users

1.  The test button 'T' must be used regularly to check the function of the residual 

current circuit-breaker. This should be carried out at least every six months in the 
case of stationary systems and should be repeated every working day in the case 
of non-stationary systems (BGV A3). 

2.  Recurrent testing of the protective measures must be carried out at regular inter

-

vals by an authorised specialist (BGV A3).

3.  After tripping by pressing the test button or a system-specific residual current, 

the toggle of the residual current circuit-breaker is located in the middle position 
'+'. Resetting to position 'I' is only possible if the toggle has firstly been moved 
to position '0'.

4.  If the residual current circuit-breaker can no longer be switched on in accordance 

with the procedure indicated under point 3, an authorised specialist must be con

-

tacted.

5.  If any damage to the housing is identified, an authorised specialist must be con

-

tacted.

6.  Disposal  must  be  performed  by  an  authorised  specialist  and  is  subject  to  the 

statutory regulations of the European Union (WEEE / German Electrical and Elec

-

tronic Equipment Act).

Guarantee

All  professionally  installed,  unaltered  devices  are  covered  by  warranty  during  the 
statutory guarantee period from the day of purchase by the end user. The guaran

-

tee is not applicable to damage incurred during transport or caused by short-circuit, 
overloading  or  improper  use.  In  the  event  of  defects  in  workmanship  or  material, 
which are discovered within the guarantee period, the company will provide a repair 
or replacement free of charge. The guarantee will be rendered null and void if the 
device is opened without authorisation.

Installation and Operating Manual

for two-/four-pole residual current circuit-breakers

General

In order to avoid personal injury and damage to property, the operating manual must 
be read carefully before using the residual current circuit-breaker. The manual must 
also be retained for future reference. Installation may only be carried out by an au

-

thorised specialist, who is familiar with the relevant national installation regulations.

Intended use and mounting

For snapping onto mounting rail and for installation in distributions board with cor

-

responding device covers, to prevent contact with dangerous active parts.

Electrical connection

Guide phase and outer cables (L1, L2 and L3) as well as the neutral conductor (MP/N) 
through the switch. Energy may flow in either direction, i. e. the mains or consumer 
unit may be connected to the upper or lower terminal block. To ensure that the in

-

stalled testing facility functions correctly, for two-pole connection four-pole devices, 
the terminals must be used in accordance with the wiring diagram. Scrape and grease 
aluminium conductors immediately before connection.

Residual current circuit-breakers

two-pole / four-pole

Terminal cross-

section

single / stranded

1.5 mm² – 50 mm²

flexible

1.5 mm² – 35 mm²

Tightening torque

2.5... 3 Nm

Screwdriver

Slotted/cross recess Pozidriv (Z) size 2

Testing and functional check

The testing of all safety measures on commissioning must be carried out according to 
the information in the valid national installation regulations. A functional inspection 
of the residual current circuit-breaker itself is possible with connected mains voltage 
by pressing the test button T and, as in commercial use (BGV A3), should be carried 
out at least every six months in the case of stationary systems and should be repeated 
every working day in the case of non-stationary systems. After tripping by pressing 
the test button or a system-specific residual current, the toggle of the residual current 
circuit-breaker is located in the middle position '+'. Resetting to position 'I' is only pos

-

sible if the toggle has firstly been moved to position '0'. The operating display beneath 
the toggle indicates the status of the switching contacts. If the switching contacts are 
closed, the display is red and it is green if the switching mechanism is open.

Short-circuit and thermal protection

DFS 2 AC

Rated current

16 A

25 A

40 A

63 A

80 A

100 A

125 A

Thermal back-up 
fuse OCPD gG

1)

16 A

25 A

63 A

80 A

Short-circuit back-
up fuse SCPD gG

1)

63 A

100 A

125 A

Inc

 / I�c

2)

  

10 kA

1)

 DIN VDE 0636, IEC 60269 

|

 

2)

 DIN EN 61008-1

DFS 2 A

Rated current

16 A

25 A

40 A

63 A

80 A

100 A

125 A

Thermal back-up 
fuse OCPD gG

1)

16 A

25 A

40 A

63 A

80 A

Short-circuit back-
up fuse SCPD gG

1)

 

100 A

125 A

Inc

 / I�c

2)

 

10 kA

1)

 DIN VDE 0636, IEC 60269 

|

 

2)

 DIN EN 61008-1

DFS 4 AC

Rated current

16 A

25 A

40 A

63 A

80 A

100 A

125 A

Thermal back-up 
fuse OCPD gG

1)

16 A

25 A

40 A

63 A

80 A

Short-circuit back-
up fuse SCPD gG

1)

63 A

100 A

125 A

Inc

 / I�c

2)

  

10 kA

1)

 DIN VDE 0636, IEC 60269 

|

 

2)

 DIN EN 61008-1

Wiring diagrams

1 3

2 4

 

V

two-pole, neutral on left or right

(N)1 3 5 7(N)

(N)2 4 6 8(N)

 

V

four-pole, neutral on left or right, depending on device version

Doepke

3930132 

|

 11/2013 | Doepke Schaltgeräte GmbH, Stellmacherstraße 11, D-26506 Norden

DE EN

Reviews: