Cable glands and attachments

30

48

8

PE

8

 

V

Stripping lengths

Commissioning
The appropriate voltage must be supplied to the Dasy for commissioning. Therefore, 
make sure that the housing is properly closed and screwed together.

Switch-on threshold
After connecting the operating voltage, move the potentiometer to the left stop   
to set the switch-on threshold EON. If the outdoor brightness is at the desired level, 

the potentiometer should be slowly turned to the right 

 until the control diode  

illuminates. This process sets the switch-on threshold to the desired illuminance. The 
load relay switches on after the switch-on delay has expired.

Switch-off threshold
The switch­off threshold E

OFF

 is fixed at 1.5 times the value of the switch on threshold 

E

ON

. If the switch­off threshold is exceeded due to increasing brightness, the control 

diode and the load relay switch off once the switch­off delay time has expired.

switch-off threshold

switch-on threshold

hysteresis

10 s

40 s

time

U

L

turn on delay

turn off delay

load voltage

luminosity

E

on

E

Off

(adjustable)

fixed, 1.5 x E

Eon

 

time

Lux

Switch-on/switch-off delay time
As soon as the switch-on threshold is altered due to the potentiometer being oper-
ated, the switching delays are reduced to 1 second for 5 minutes. This causes the load 
relay to switch almost synchronously with the control diode, to be able to check im-
mediately that the device and load are functioning correctly. Should the delay times 
be activated prematurely, the power supply to the device should be momentarily 
interrupted.

Instructions for function test
When the weather is sunny or if the device is installed at an unfavourable location 
with a lot of natural light, covering the lens with your hand may not suffice for test 
purposes. The switch-on point cannot be reached because too much light is able to 
enter the housing. In these cases, use the packaging to cover the housing or another 
opaque aid to create conditions which are sufficiently dark for testing. 

Warranty
All professionally installed, unaltered devices are covered by warranty for the dura-
tion of the statutory warranty period from the day of purchase by the end user. The 
warranty is not applicable to damage incurred during transport or caused by short-
circuit, overloading or improper use. In the event of defects in workmanship or mate-
rial being discovered within the warranty period, the company will provide repair or 
replacement free of charge.

Installation and operating instructions

for twilight switches DASY 10-2/230V,  
DASY 10-2/24V, DASY 10-2/12V, DASY 16-2/230V

These instructions describe the installation and commissioning of the 
Dasy twilight switch. They are intended for use by electrically skilled 
persons. Electrical laypersons must not install and connect devices of 
this type due to the considerable potential dangers. The instructions 
must be kept so that they can be referred to at a later stage.

Safety instructions
Working with and on high voltages can be potentially fatal; the extent of injury can-
not be predicted. The basic requirement for safe work and the avoidance of accidents 
due to electric current (electric shock, electric arcs, secondary effects, e.g. accidents 
caused by tripping) is to comply with all safety and operating requirements stated 
in these instructions. The local accident prevention regulations are also applicable.

1.  Installation and connection must only be carried out by an electrician.
2.  When the device is opened, voltage-carrying parts (terminals) become exposed. 

Touching these can cause life-threatening injury. Therefore, only open the Dasy 
when the supply voltage is disconnected.

3.  Ensure there are no people or animals in the danger area when manually switching 

(putting the Dasy in dark conditions).

4.  Avoid quick switching sequences if sensitive luminaires (e.g. HQL) are connected.

Intended use 
The Dasy is intended for brightness-linked control of electrical consumers. Accord-
ing to its protection class, it is also suitable for outdoor use, in which case it must be 
installed on the wall or on a mast.

Functional description
The twilight switch compares the current illuminance with the set switch-on thresh-
old. If the illuminance drops below the desired switch-on threshold, the internal relay 
switch (normally opened contact) is switched on once the switch-on delay has ex-
pired. If the switch­off threshold is reached due to increasing illuminance (1.5 times 
the switch­on threshold), the load relay switches off again after the switch­off delay 
has expired. The delay ensures that the load relay of the twilight switch does not re-
spond to brief lighting fluctuations (e.g. lightning, car headlights).

Assembly
Observe the following points when selecting the place of installation and during 
mounting itself:

 

»

Avoid locations in direct sunlight. North and east-facing walls are ideal.

 

»

The light reaching the sensor must not be interrupted by overhanging roofs etc.

 

»

The switched light source must not directly affect the sensor.

 

»

Mount the device so that the warning light and potentiometer are facing  
downwards.

 

»

Use the optional mounting kit (must be ordered separately) to mount the device 
on masts or pipes.

Installation

 

»

In order to prevent death or injury due to electric shock, the power supply must be 
cut off before installation.

 

»

The  device’s  supply  line  must  be  protected  using  the  specified  miniature  
circuit breaker.

 

»

The cable gland on the underside or back of the device should be used for the  
supply line.

 

»

The specified stripping lengths for the lines are given in the following diagram.

 

»

The silicon tubes enclosed are to be fitted to the cores of the connection lines.

 

»

The terminal assignment is shown in the following figure.

 

»

The maximum torque when tightening screw-type terminals must not be  
exceeded.

Wiring

N N L L

L1

PE

N

DASY 10-2 / 230 

V

DASY 16-2 / 230 

V

DASY 10-2 / 24 

V

DASY 10-2 / 12 

V

N N

L

L

12 V AC / DC

24 V AC / DC

230 V AC

0 V

0 V

N

 condensate water opening

Derating based on the cable cross-section

5 A

10 A

16 A

20°C

30°C

40°C

50°C

1,5 mm²

5 A

10 A

16 A

20°C

30°C

40°C

50°C

2,5 mm²

10°C

10°C

Dimensions

90

70

53

Technical Data

DASY

Device design

DASY

10­2/12 V

Dasy 10­

2/24V

Dasy 10­

2/230V

Dasy 16­

2/230V

Operating voltage

12 V AC/DC 

± 10%

24 V AC/DC 

± 10%

230 V AC 

± 10%, 50 Hz

230 V AC 

± 10%, 50 Hz

Item no white

09 500 040

09 500 041

09 500 043

09 500 042

Item no anthracite

09 5000 47

09 500 046

Integrated overvoltage 
protection

No

Miniature circuit-
breaker

max. 10 A

max. 16 A

Output

Type

All-or-nothing relay

Contact

1 NO contact 

Micro switch­off

Switching power

2500 VA

4000 VA

Max. capacitor for shunt 
compensation

70 µF

140 µF

el. switching cycles

> 100,000

Internal consumption  
at rated load

0.9 W

Switch-on delay

10 s (1 s)

a)

Switch­off delay

40 s (1 s)

a)

Switching thresholds

Switch-on value,  
adjustable

1­200 lux

Switch­off value

1.5 × switch­on value

Control display

Red  
LED: on

Switch-on threshold exceeded 

(immediate LED display)

Red  
LED: off

Switch­off threshold exceeded 

(immediate LED display)

Terminals

Type

Screw terminals with strain-relief clamp

Clamping area

0.4 mm Ø to 4 mm

2

 (rigid)

Tightening torque

0.5 Nm

Housing

Dimensions  
(H x W x D in mm)

90 x 70 x 53

Type

On-wall case for wall or mast mounting

b)

Protection class

IP54

Material

Polycarbonate (PC)

Ambient temperature

­25 °C to +50 °C

Weight

0.140 kg

0.136 kg

0.139 kg

0.144 kg

Design regulations/
standards

DIN EN 60669

Accessories  
mast bracket 

b)

09 500 049

a) 

These values apply for five minutes after the last switch­on threshold change.

b)

 Optional mounting kit to be ordered separately

Doepke

3932141 | 08/2017 | Doepke Schaltgeräte GmbH, Stellmacherstraße 11, D­26506 Norden