2-4 Changing the Alarm Settings 

 

The values of alarm settings on this unit can be changed. The method for changing them is explained 

here. 

 

(1) Release the password lock. (Refer to 

1-2 Releasing the Password Lock

.) 

 

(2)  Press the AL switch until the alarm setting   

to be changed is displayed on the LCD display.   

(The bottom right of the screen, as in the table below.) 

The alarm setting for the actual gas concentration is 

displayed in the middle of the screen, and the 

percentage of the full scale value is displayed in the 

bottom right corner 

LCD Display 

Indication 

(Lower right) 

Default value 

Explanation of 

the default value 

Adjustable 

Range 

Toxic  : CDS-7 
Comb. : CHS-7 

A1  10 

10% F.S. 

A1  ** 

Oxygen: COS-7 

A2    72 

72% F.S. 

0 to 100% F.S. 

Toxic  : CDS-7 
Comb. : CHS-7 

A2  20 

20% F.S. 

A2  ** 

Oxygen: COS-7 

A2  76 

76% F.S.

 

0 to 100% F.S. 

* Pressing the AL switch changes to 1st level 

Æ

 2nd level

Æ

 Normal display. 

* The A2 value should be greater than the A1 value in any case. 

 

(3) Press the special command switch. 

The setting to be changed and the    “—“ 

indication will then flash alternately. 

 

 

 

 

(4) Change the value by using the UP/DOWN key “

U

” and”

V

”. 

When you are done, press the special command switch again, and the alternating display in the lower 

right corner of the LCD display will become constant. The process is now finished. 

 

(5) When this is finished, press the UP/DOWN switches (“

U

” or”

V

”) again to return to the normal display. 

 

Note 

The relationship between 1

st

 level and 2

nd

 level alarm values of each alarm mode is as follows: 

AL switch 

The percentage of the full scale value

Gas concentration

- - - - - 

A1 10

Special 
command 
switch 

UP/DOWN switches 

Summary of Contents for PS-7

Page 1: ... 5300 Fax www dodtec com Operate this unit only after reading and fully understanding the content of this manual This Operation Manual was written for administrator use Instructions for the basic operations of this unit are provided separately in the standard Operation Manual Refer to the Operation Manual when necessary For Administrators ...

Page 2: ...ettings Refer to 2 4 Changing the Alarm Settings 1 2 Releasing the Password Lock 1 Press these key switches in the following order 1 ZERO switch 2 UP switch 3 Special command switch 4 DOWN switch 2 The password lock is released when the POWER lamp green blinks once 3 The password lock is automatically reactivated 10 minutes after it has been released 1 2 3 4 POWER lamp green Blinks once Warning Im...

Page 3: ...creen will go off and the span adjustment will be completed 7 Remove the calibration gas check that the detected gas concentration is under that of the alarm value and restore to the normal mode by switching the maintenance switch to the center Toxic gas sensor unit CDS 7 Combustible gas sensor unit CHS 7 Pull back to open Left Maintenance 1 MNT1 Center Normal mode Right Maintenance 2 MNT2 TROUBLE...

Page 4: ...ttom right corner of the LCD screen will then disappear and the 21vol adjustment is complete 7 Remove the calibration gas and confirm that no alarm is displayed ALARM 1 ALARM 2 is not shown Then restore to the normal mode by switching the maintenance switch to the center Pull back to open Left Maintenance 1 MNT1 Center Normal mode Right Maintenance 2 MNT2 TROUBLE lamp yellow blinks MNT1 or MNT2 is...

Page 5: ...ock Refer to 1 2 Releasing the Password Lock 2 Press the UP DOWN switch U or V until the setting you wish to change LCD Screen Indication in the table below is displayed at the bottom right of the LCD display 3 Then press the special command switch and the setting to be changed LCD Screen Indication in the table below and will flash alternately Special command switch Setting to be changed UP DOWN ...

Page 6: ...ue rounded to the percent zs 5 zs 2 0 to 30 H H L L H L Alarm mode 1st upper limit 2nd upper limit warning 1st lower limit 2nd lower limit warning 1st upper limit 2nd lower limit warning H H L L H H L L H L Con Pyroletic converter failure alarm 0 Off 1 On Con 0 Con 0 0 or 1 CG Calibration gas concentration For our maintenance purposes only CG 40 CG 84 nEt The existence of a DeviceNet unit 0 Non ex...

Page 7: ...72 72 F S 0 to 100 F S Toxic CDS 7 Comb CHS 7 A2 20 20 F S A2 Oxygen COS 7 A2 76 76 F S 0 to 100 F S Pressing the AL switch changes to 1st level Æ 2nd levelÆ Normal display The A2 value should be greater than the A1 value in any case 3 Press the special command switch The setting to be changed and the indication will then flash alternately 4 Change the value by using the UP DOWN key U and V When y...

Page 8: ...vel alarm ALARM 1 ALARM 2 is displayed Alarm contact ZA1 and ZA2 are activated Alarm value is set by entering A1 0ppm Full Scale 2 nd level gas alarm ALARM 1 ALARM 2 is displayed Alarm contacts ZA1 and ZA2 are activated Alarm value is set by entering A2 1 st level gas alarm ALARM 1 is displayed Alarm contact ZA1 is activated Alarm value is set by entering A1 Upper alarm ALARM 2 is displayed Alarm ...

Page 9: ...able Contact the following address for ordering information Manufacturer New Cosmos Electric Co Ltd 2 5 4 Mitsuya naka Yodogawa ku Osaka 532 0036 Japan Phone 81 6 6309 1505 Fax 81 6 6309 1514 Distributor DOD Technologies Inc 740 McArdle Drive Unit C Crystal Lake IL 60014 Phone 815 788 5200 Fax 815 788 5200 www dodtec com ...

Reviews: