Trip Free (C-O)
2-16
72A-1898 Rev. A 11/01
Monday
, November 26, 2001 1:09 pm
Trip Free (C-O)
Figure 2.11 is a simplified representation of the test waveform generated
for the Trip Free test.
Figure 2.11 Trip Free Command Pulse
Command
Parameters
Close Pulse
This time setting determines the duration of the
Close Pulse sent to operate the close circuit of the
circuit breaker.
Trip Free and Delay
These parameters determine when the Trip Pulse is
initiated:
Standing
Initiates .5 cycles (8.3 ms at 60 Hz) after the test
starts.
Delay
Initiates after the time entered in the
Delay Length
field.
Contact
1
Make
Initiates when the TDR9000 senses that a contact
make has occurred on the first of the Main
Contacts.
Recording Length
This setting determines the recording length and
implicitly sets the sampling rate at which the
recording is performed.
133 msecs
Trip Command
Close Command
Delay
On
Off
On
Off
Summary of Contents for TDR9000
Page 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...