Test Plan Items
A-38
72A-1898 Rev. A 11/01
Monday
, November 26, 2001 1:09 pm
Test Initiation
Timing a Close test from test initiation is achieved using the Close Pulse
and Timing Event parameters (Figure A.37).
Figure A.37 Close Parameters
The default values for the Close Pulse are:
• 133.3 ms for 60 Hz
• 160 ms for 50 Hz
Figure A.38 shows how timing works for test initiation. The times, t
1
and
t
2
, indicate the following:
t
2
The time required to close the Main Contact.
The close time is measured from the test initiation.
t
1
The
time required to close the resistor switch.
The close time is measured from the test initiation
(if the T0 option is selected in Resistor Switch
Timing Specification, see ”Resistor Switch
Timing – Close” on page A-77).
Figure A.38 Close Time
Time (ms)
0
10
20
30
40
50
60
t
2
t
1
Summary of Contents for TDR9000
Page 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...