Installation & Operation Manual  

                                                                                  

Mini Merlin 

 

Rev: 11   09-20 

10  

   Auto Reset & Buzzer Switches 

 
There are two dip-switches on the circuit board. 
 

 

ON 

OFF 

Auto Reset 

In the event of a power loss – the mini merlin will 

restart automatically when power is restored.  

In the event of a power loss – the mini merlin will 

need to be reset manually when power is restored. 

This is the factory set condition. 

Buzzer 

The buzzer will sound every 15 seconds during 

pre-alarm and continuously at alarm level. 

This is the factory set condition. 

The buzzer will not sound at any gas level. 

 

   Building Management System Integration 

 
This device can be integrated with a Building Management System (BMS), a home alarm 

system, or be used as part of a boiler low voltage safety limit to make or break a circuit on both 

gases separately, (valve open or valve closed) depending on the system. 

 

These switches can be used for a variety of purposes including triggering alarm contacts, 

operating and external relay for multiple appliance shut-down and generating status signals for 

a BMS system. 

 

   Specification 

 

Product:

  Mini Merlin  

Version: 

CH4CO 

Display 

1.8” TFT – Thin Film Transistor 

Screen Brightness 

Non- adjustable  

Initial Stabilisation Time 

60 Seconds approx. 

Power Input Voltage  

100-240Vac /  50-60Hz 

Valve Output Voltage 

100-240Vac / 50-60Hz 

Fuse 

Anti-Surge 3.15A 250Vac 

Current Consumption 

3W Max  

Accuracy @ 25°C / 77°F 

± <10% 

Operating Temp 

32 – 122°F  30-85%RH Non-Condensing 

Audible Buzzer 

65dB (controlled conditions @ 1 ft) 

Volt Free BMS relay output 

0.5A switching current (resistive load) 

Gas Sensor Type 

Methane: Semi-conducting 
Carbon Monoxide: Electromechanical 

Gas Sensor Measuring Range 

Methane: 500-10,000ppm 
Carbon Monoxide: 0-1000ppm 

Gas Value Pre-Alarm  

Methane: >8% LEL 
Carbon Monoxide: 20ppm 

Gas Value Alarm 

Methane: >10% LEL 
Carbon Monoxide:  

20ppm after two (2) hours 
50ppm after one (1) hour 
100ppm after ten (10) minutes 

300ppm after one (1) minute 

Dimensions (mm) 

95(W) x 140(H) x 60(D) 

Weight  242g approx.

 

X-Cel House, Chrysalis Way, Langley Bridge, 
Eastwood, Nottinghamshire NG16 3RY

+44 (0) 1773 534555
[email protected]
dmsltd.com

Summary of Contents for MINI MERLIN

Page 1: ... levels of carbon monoxide at the sensor this device can shut off the gas supply via a gas safety valve and or a gas fired appliance This device has additional features for resetting systems as well as audible and visual alarms It can also be integrated with a Building Management System BMS The information contained within this manual should be referenced for typical installation and operation onl...

Page 2: ...oning 6 Mounting 7 Circuit Board Overview 8 Wiring 8 Auto Reset Buzzer Switches 10 Building Management System Integration 10 Specification 10 OPERATION 11 First Power Up 11 Touch Button 11 Device Overview 11 Gas Level Alarms 12 Remote Shut Off Screen 12 End of Life Screen 12 General Maintenance 13 Bump Testing 14 INSTALLATION DETAILS 16 X Cel House Chrysalis Way Langley Bridge Eastwood Nottinghams...

Page 3: ...n doubt consult a doctor physician Your product should reach you in perfect condition if you suspect it is damaged contact your supplier Manufacturer s Warranty Warranty Coverage The manufacturer warrants to the original consumer purchaser that this product will be free of defects in material and workmanship for a period of three 3 years from date of purchase The manufacturer s liability hereunder...

Page 4: ...t situation Medium levels Generally between 50ppm to 100ppm This should be cause for concern and should not be ignored or dismissed Low levels Maximum acceptable indoor level of CO is 9ppm Anything above this level may cause possible health effects with long term exposure See the specification table for how your device monitors Carbon Monoxide gas POSSIBLE SOURCES OF CARBON MONOXIDE GAS Inside you...

Page 5: ...xic and associated with being a simple asphyxiator displacing oxygen in the lungs However Methane is extremely combustible Exposure to high levels of Methane can cause Suffocation Loss of consciousness Headache and dizziness Nausea and vomiting Weakness Loss of co ordination Increased breathing rate METHANE GAS LEVELS The LEL Lower Explosive Limit of methane is considered to be 5 BV by volume of a...

Page 6: ...cation they should be located near identified sources of a potential gas leaks pockets where hazardous gas could quickly accumulate and areas of identified consequential risk A 6ft from sources of combustion e g boiler s heaters gas fired appliances etc B 4ft from draft zones and ventilation areas e g windows doorways and A C units etc C 5ft from ground level Recommended heights may vary based on ...

Page 7: ...are pre fractured areas for cable entry and barrier to separate low and high volt connections 4 Mount at 5 feet from ground level and in accordance with any applicable regulations 5 After executing the mounting and connections secure the rear cover Take care when making connections to high voltage connectors Any damage attempting to remove the circuit board may void any warranty Wiring of differen...

Page 8: ...iple appliances Use an external transformer not supplied to close a 24VAC gas solenoid valve that could supply gas to one or more appliances Gas Supply Controlled by 100 240VAC Solenoid Valve Gas Supply Controlled by 24VAC Solenoid Valve We do not recommend installing a gas solenoid valve with standing pilots If you use a gas solenoid valve please note that standing pilots will need to be re lit X...

Page 9: ...ance Multiple appliance limit switches can be wired in series Remote Shut Off Connections Your mini merlin can be integrated with remote devices with an open close circuit via the Remote Shut Off volt free switch terminal This terminal has a factory fitted link installed This terminal is normally closed and will alarm when energised open isolating the gas supply When using this input only the main...

Page 10: ...ntacts operating and external relay for multiple appliance shut down and generating status signals for a BMS system Specification Product Mini Merlin Version CH4CO Display 1 8 TFT Thin Film Transistor Screen Brightness Non adjustable Initial Stabilisation Time 60 Seconds approx Power Input Voltage 100 240Vac 50 60Hz Valve Output Voltage 100 240Vac 50 60Hz Fuse Anti Surge 3 15A 250Vac Current Consu...

Page 11: ...p automatically when electrical power is supplied Reset the device To reset after an alarm press the touch button once Test device outputs Press and hold for 3 seconds during normal operation to test screen colouration audible buzzer alarm and gas BMS relay This test only proves that the device will operate and activate connections as intended in the event of dangerous levels of gas being detected...

Page 12: ...mote shut off devices such as smoke fire alarms When activated the device will isolate the gas supply if configured to do so End of Life Screen This message indicates that the devices gas sensing elements have reached their expected operational lifecycle No gas levels will be displayed Contact your supplier and replace the unit immediately The expected lifecycle may vary depending on the environme...

Page 13: ...resheners hair spray paint or other aerosols near the device NEVER paint the device Paint will seal vents and interfere with the device High concentrations of alcohol found in many products may damage deteriorate or affect the gas sensing elements such as wine deodorants stain removers thinners etc Other gases and substances to avoid Corrosives i e chlorine hydrogen chloride Alkali metals Basic or...

Page 14: ...table range the gas detector must not be used until a full calibration has been conducted Bump testing has a number of benefits for the end user Peace of mind that the system does actually detect the gas in question Allows the site to practice safe operations in a similar manner to the fire system Early indication of any issues How Often Regular bump tests are important to make sure the detector i...

Page 15: ...Installation Operation Manual Mini Merlin Rev 11 09 20 15 Notes X Cel House Chrysalis Way Langley Bridge Eastwood Nottinghamshire NG16 3RY 44 0 1773 534555 sales dmsltd com dmsltd com ...

Page 16: ...ION DETAILS Please pass this manual to the system owner user Date of Installation Installation Location Organisation Stamp Signature of the installer X Cel House Chrysalis Way Langley Bridge Eastwood Nottinghamshire NG16 3RY 44 0 1773 534555 sales dmsltd com dmsltd com ...

Reviews: