X1-8 ACCESS CONTROL
Quick Start Guide
LT-2268 21042 © 2021 Digital Monitoring Products, Inc.
MOUNT THE SYSTEM
The metal enclosure for the X1-8 system must be mounted to a wall, backboard,
or other flat surface. It is not necessary to remove the PCB when installing the
enclosure.
WIRE THE ELECTRONIC LOCK
This section only applies to the X1 Door Controller and the XD Door Controller
Modules.
Form C Relay
The X1 system provides a Form C (SPDT) relay that is rated for 1 Amp.
Diode
Connect the included diode as close to the magnetic lock or door strike as
possible to prevent inductive kickback to the Door Controller. Observe polarity
when connecting the diode.
Wet/Dry Jumper
Putting the jumper on the top two terminals will place it in the dry condition.
Putting the jumper on the bottom two terminals will place it in the wet condition.
Note:
The XD Door Controller only wires dry because it does not have a
wet/dry jumper.
Power Supply
Magnetic Lock positive
to Terminal NC
Power Supply positive
to Terminal C
Magnetic Lock negative to
Power Supply negative
NO
C
NC
Magnetic Lock - Normally Closed and Dry
D
RY
WET
Jumper set
to Dry
–
+
Magnetic Lock
Diode
Magnetic Lock - Normally Closed and Wet
Magnetic Lock positive
to Terminal NC
Magnetic Lock negative to
X1 terminal B2
NO
C
NC
D
RY
WET
Jumper set
to Wet
Reader 2
–
+
Magnetic Lock
B2
R2 W2 G2
LC BC
Diode
NO
C
NC
Door Strike - Normally Open and Dry
D
RY
WET
Jumper set
to Dry
Door Strike positive
to Terminal NO
Power Supply positive
to Terminal C
Door Strike negative to
Power Supply negative
–
+
DC Door Strike
Power Supply
Diode
Door Strike - Normally Open and Wet
Door Strike positive
to Terminal NO
Door Strike negative to
X1 terminal B2
D
RY
WET
Jumper set
to Wet
Reader 2
–
+
DC Door Strike
NO
C
NC
B2
R2 W2 G2
LC BC
Diode