2
736V INSTALLATION GUIDE | DIGITAL MONITORING PRODUCTS
3
The 736V requires wiring connections from the LX header and polling loop terminals. Refer to Figure 4 when
wiring the module.
Warning:
Cycling power to the panel or rebooting the 736V with the jumper on both Write Ena/Clear pins
will delete any data saved in the 736V. Leaving V‑Plex devices disconnected from power for long periods of
time may also result in data loss. When the system is powered on, do not to touch the polling loop wires
together.
1. Use the Model 330 4‑wire harness to connect the module LX header directly to a panel LX‑Bus header.
This connection allows the module to communicate with the panel and receive 12 VDC power.
2. Short the two V‑Plex polling loop wires by touching them together for approximately 30 seconds.
3. Connect the red wire from the polling loop to the positive module terminal. Connect the black wire from
the polling loop to the negative module terminal.
4. Remove both jumpers from Keypad Ena and Write Ena/Clear, then power up the panel.
Note:
DMP XR150/XR550 Series panels provide up to 1.5 Amps of auxiliary power. The total current of all
keypads, modules, and devices that are connected to modules cannot exceed 1.5 Amps. When performing
standby battery calculations, include the total current draw of all connected V‑Plex devices.
WIRE THE 736V
Keypad Ena.
Write Ena./
Clear
RED
BLACK
To Polling Loop
To LX-Bus
LX
Figure 4: 736V Wiring Diagram