background image

8 0 0 - 6 4 1 - 4 2 8 2

I N T R U S I O N   •   F I R E   •   A C C E S S   •   N E T W O R K S

w w w . d m p . c o m

2 5 0 0   N o r t h   P a r t n e r s h i p   B o u l e v a r d

Designed, Engineered and

 

Assembled in U.S.A.

S p r i n g fi e l d ,   M i s s o u r i   6 5 8 0 3 - 8 8 7 7

LT

-1260  1.01 © 2013 Digital Monitoring P

roducts, Inc.

13455

Diagnostics

The XR100/XR500 Series panels provide a Diagnostics function to test the Communication integrity and Cellular Signal 
strength of the 463C. To use Diagnostics, reset the panel, enter the Diagnostics code 2313 (DIAG), and press COMMAND.

Communication Status

Select COMM STATUS from the Diagnostics menu. The XR100/XR500 Series panels test the 463C for the following items:

• 463C Installed

• Cellular Tower Detected

• 463C Registered

• Communication Path Integrity

• 463C Operating

• NOC Success

• 463C Identified

Cellular Signal

Select CELL SIGNAL from the Diagnostics menu. The XR100/XR500 Series panels test and indicates the 

strength of the signal using a bar display. One bar indicating a weak signal. Seven bars indicating a 

strong signal. The X's represent the numerical value of the cell signal strength in -dBm.

Wiring Specifications for LX-Bus

When planning an LX-Bus installation, keep in mind the following specifications:
1.  DMP recommends using 18 or 22-gauge 

unshielded 

wire for all keypad and LX-Bus circuits. 

Do Not use twisted pair or 

shielded wire for LX-Bus and keypad bus data circuits. To maintain auxiliary power integrity when using 22-gauge wire 

do not exceed 500 feet. When using 18-gauge wire do not exceed 1,000 feet. Install an additional power supply to 

increase the wire length or add devices.

2.  Maximum distance for any one circuit (length of wire) is 2,500 feet regardless of the wire gauge. This distance can be 

in the form of one long wire run or multiple branches with all wiring totaling no more than 2,500 feet. As wire distance 

from the panel increases, DC voltage on the wire decreases.

3.  Maximum number of devices per 2,500 feet circuit is 40.

Note:

 Each panel allows a specific number of supervised keypads. Add additional keypads in the unsupervised mode.

 

Refer to the panel installation guide for specific number of supervised keypads allowed.

4.

  Maximum voltage drop between the panel (or auxiliary power supply) and any device is 2.0 VDC. If the voltage at any device 

is less than the required level, add an auxiliary power supply at the end of the circuit. When voltage is too low, the devices 

cannot operate properly. For additional information refer to the LX-Bus/Keypad Bus Wiring Application Note (LT-2031).

FCC Information

This device complies with Part 15 of the FCC Rules. Affix the included FCC label to the exterior of the panel enclosure in plain sight. 

Operation is subject to the following two conditions:

 

(1) This device may not cause harmful interference, and

 

(2) this device must accept any interference received, including interference that may cause undesired operation.
Changes or modifications made by the user and not expressly approved by the party responsible for compliance could void the user’s 

authority to operate the equipment.

NOTE

: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the 

FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This 

equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, 

may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular 

installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the 

equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
 

- Reorient or relocate the receiving antenna.

 

- Increase the separation between the equipment and receiver.

 

- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

Consult the dealer or an experienced radio/TV technician for help.

                 -XX dBm

SIGNAL: 

▐▐▐▐▐▐▐

Listings and Approvals

California State Fire Marshall (CSFM)

Cellular FCC ID: MIVCNN0301

New York City (FDNY COA #6055)

New York City (FDNY COA #6145)

Underwriters Laboratories (UL) Listed

 

ANSI/UL 365 Police Station Connect Burglar Alarm Systems

 

ANSI/UL 1023 Household Burglar Alarm System Units

 

ANSI/UL 1076 Proprietary Burglar Alarm Units & Systems

 

ANSI/UL 1610 Central Station Burglar Alarm Units

 

ANSI/UL 864 Fire Protective Signaling, 9th Edition

 

ANSI/UL 985 Household Fire Warning System Units

Specifications

Primary Power 12 VDC from panel

Current Draw 

  Standby 

 

22mA

 

Alarm 

 

22mA

Accessories

381-2  18-inch Coax cable with SMA connector
381-12  12' Coax Extension
381-25  25' Coax Extension
383 

Rubber Duck Antenna

386 

Wall Mount Antenna Bracket