463C CDMA Cellular Communicator
Description
The 463C CDMA Cellular Communicator provides a fully supervised alarm communication path over the CDMA network. The
463C is installed in the panel J6 Interface Card connection or a 461 Interface Adaptor card and powered by the panel so no
additional enclosure, power supply or battery back-up is needed.
What is Included
The 463C includes the following:
• One Model 463C
• One Model 381-2 18-inch Coax cable with SMA connector
• One Model 300 4-Wire LX-Bus harness
• One Model 383 Rubber Duck Antenna
Compatibility
The 463C is compatible with the XR100/XR500 Series panels using software Version 211 or higher.
Installation Safety
Ground Yourself Before Handling the Panel! To discharge static, touch any grounded metal, such as the enclosure, before
touching the panel.
Remove All Power From the Panel!
Remove all AC and
Battery power from the panel before installing or
connecting any modules, cards, or wires to the panel.
Installing the 463C
Align the 463C card 50 pin connector with the J6 connector and
press the card onto the connector while applying even pressure to
both sides of the board. See Figure 1.
Connecting the Antenna
1. Position one of the supplied washers onto the SMA connector
and push the threaded end through an enclosure knockout.
2. Position the second washer onto the threaded end extending
through the knockout and secure the nut.
3. Attach the included 383C Antenna to the SMA connector.
See Figure 1.
As an alternative, the antenna coax can be connected directly
to the 463C SMA connector when the coax enters the enclosure
via conduit.
LX-Bus™ Expansion Capability
The 463C card also provides a 4-wire LX-Bus™ for the addition of
any combination of 100 protection zones and 100 relay outputs. Insert the harness
connector into the 4-pin LX-Bus header on the bottom of the 463C Interface Card.
Note:
Do not use shielded wire when using the LX-Bus. Do not connect the wires
from the 463C to panel terminals or the panel J22 header.
Programming/Activation
Cellular Service is required before using the 463C for signal
transmission. The 463C comes ready for activation with SecureCom
Wireless, LLC.
1. In Remote Link panel communication programming, select
Cellular Network as the Communication Type and select the
Activate button. See Figure 2.
A. In the Activate SIM/MEID window, enter the MEID number,
found on the 463C label.
B. Select the rate plan for the 463C. See Figure 3.
C. Select the Activate button at the bottom of the window.
2. After the 463C is installed at the site, use a keypad and enter
the XR100/XR500 panel's Diagnostics menu (2313).
A. Select ACTIVATE CELL by pressing a top row Select Key.
B. Press the button beneath YES on the next screen to activate
the device.
Note:
The ACTIVATE CELL prompt will only display if a CDMA modem is installed.
Coax Cable
from 463C
SIM
Card
Nut
Washers
SMA
Connector
SMA
Connector
Antenna
Connector
B
J6 Interface Card
Connector
18
19
20
21
22
23
24
25
26
27
28
Z5
Z6
Z7
Z8 Z9+ Z9- Z10+ Z10-
GND
GND
Red—Auxiliary Power
Yellow—Data In
Green—Data Out
Zone Expansion
Harness Connector
To LX-Bus
Modules
XR100/XR500
Panel
463C
Interface
Card
Black—Ground
Figure 1: Install and connect the 463C and Antenna
Figure 2: Remote Link Activation
Figure 3: Remote Link Activation