DESCRIPTION
Figure 1: 263LTE-V
1
INSTALL THE 263LTE-V
Caution:
Touch grounded metal to discharge
static before handling the panel.
1. Open the panel enclosure and remove all
power from the panel. If needed, remove
the panel from the enclosure to allow easier
placement of the 263LTE-V.
2. Insert the included standoff into the
XT30/XT50 or XR150/XR550 Series panel
standoff hole.
3. For XT30/XT50 Series panels, align the
263LTE-V SMA antenna connector with
the antenna hole in the top of the panel
enclosure and secure it on the 12-pin cell
module connector. See Figure 2.
For XR150/XR550 Series panels, secure
the 263LTE-V on the 12-pin cell module
connector. See Figure 3.
4. Allign the 263LTE-V standoff hole with the
standoff already placed in the panel and
snap it into place.
The 263LTE-V Cellular
Communicator provides a fully-
supervised alarm communication
path over the Verizon LTE network.
The 263LTE-V installs on the panel
inside the enclosure and is powered
by the panel so no additional
enclosure, power supply, or battery
back-up is needed.
Compatibility
Control panel firmware should be
updated to the following versions
when installing a 263LTE-V:
• XT30/XT50 Series panels
with Version 172 or higher
• XR150/XR550 Series panels
with Version 172 or higher
What is Included
• 263LTE-V Cellular
Communicator
• 383LTE antenna
• PCB standoff
• 381-2 18” coax cable with
brass washers and nut
(Included only when ordering
the 263LTE-V/381-2)
1
2
3
4
Figure 2: 263LTE-V on an XT30/XT50 Panel
Back of the
263LTE-V
Standoff and
Standoff Hole
SMA Connector
Figure 3: 263LTE-V on an XR150/XR550 Panel
Standoff and
Standoff Hole
Back of the
263LTE-V
263LTE-V CELLULAR
COMMUNICATOR
Installation Guide