background image

Digital Monitoring Products 

1119 Installation Guide

2

Programming the 1119 in the Panel

To allow the 1119 sounder to be turned on or silenced by the panel, the OUTPUT serial number must be programmed 

as an output in Output Information, and assigned to the 1119 zone ALARM ACTION output section in panel Zone 

Information programming.
If the 1119 is programmed as a zone, but the output is not programmed into the panel at Output Information, the 

1119 annunciates up to five minutes dependant on the sounder cutoff jumper setting and cannot be silenced from 

the panel.

If the 1119 is programmed into Output Information, but not assigned to the 1119 zone ALARM ACTION output section, 

the sounder only operates for a few seconds when the 1119 zone is tripped even if the sounder cut off jumper is set 

to five.

Output Programming

Enter the output number, output name, and eight digit OUTPUT serial number. For extended battery life, a 15 

second slow response output is recommended. This gives the 1119 an estimated battery life of 2 1/2 years, 

depending on usage. A list of the slow response outputs for each panel is listed below.
 

 

 

XR100/XR500:  450-474  

XTL/XT30/XT50: 31-34

Use the following output numbers for fast response outputs that respond within 1 second. The typical battery life is 

3 months. Fast response outputs are listed below.
 

 

 

XR100/XR500:  480-499  

XTL/XT30/XT50:  41-44

Zone Programming

Program the 1119 in Zone Information as a Day type zone (DY) when local annunciation at the keypad is required in 

addition to the sounder when the panel is disarmed. If the 1119 sounder is to be the only annunciation during the 

disarmed state, program as a Night type zone (NT). At the Serial Number: prompt enter the eight-digit ZONE serial 

number. To allow the panel to control the output, program the output number in the zone ALARM ACTION.

Supervision Time

When programming the 1119 in both Zone Information and Output Information, the supervision time should be the 

same, typically 240 minutes for burglary applications.
Note: When a receiver is installed, powered down and powered up, the panel is reset, or programming is complete, 

the supervision time is reset. If the receiver has been powered down for more than one hour, the 1119 may take 

up to an additional hour to send a supervision message unless tripped, tampered, or powered up. This operation 

extends battery life. A missing message may display on the keypad until the supervision message is sent. Refer to the 

panel programming guide as needed.

Selecting the Proper Location (LED Survey Operation)

The 1119 provides a survey capability to allow one 

person to confirm communication with the receiver 

while the cover is removed. The 1119 PCB Red Survey 

LED (See Figure 2) turns on whenever data is sent to 

the receiver then immediately turns off when the 

receiver acknowledgement is received. Pressing the 

tamper switch is a convenient way to send data to the 

receiver to confirm operation. When the 1119 does 

not receive an acknowledgement from the receiver 

the survey LED remains on for about 8 seconds to 

let you know communication is not established. 

Communication is also faulty when the LED flashes 

multiple times in quick succession. Relocate the 

1119 or receiver until the LED immediately turns off 

indicating the 1119 and receiver are communicating 

properly. Proper communication between the 1119 and 

receiver is verified when for each press or release of 

the tamper switch, the LED blinks immediately on and 

immediately off.

Figure 2: 1119 Wireless Sounder PCB

Mounting Holes

Model

1119

RED LED

(SURVEY)

TAMPER

SWITCH

SOUNDER

Mounting Holes

Zone

terminals

Red 

Survey

LED

Locking Screw

Locking Screw

1

SEC

5

MIN

SOUNDER 

CUTOFF

ZONE

OUT

Summary of Contents for 1119

Page 1: ... left pins or for five minutes if the jumper is placed on the two right pins When the sounder output is programmed in Output Information and is turned on by an output command from the panel such as a different zone trip group output or manually from a keypad the 1119 always turns the sounder output off automatically after five minutes regardless of the position of the jumper J5 In addition when th...

Page 2: ...w the panel to control the output program the output number in the zone ALARM ACTION Supervision Time When programming the 1119 in both Zone Information and Output Information the supervision time should be the same typically 240 minutes for burglary applications Note When a receiver is installed powered down and powered up the panel is reset or programming is complete the supervision time is rese...

Page 3: ... 2 Lift the cover from the bottom to remove 3 If replacing the batteries remove the used batteries and dispose of properly Always replace both batteries at the same time Caution Properly dispose of used batteries Do not recharge disassemble heat above 212 F 100 C or incinerate There is a risk of fire explosion and burns with improper disposal 4 Place the two 3 0V Lithium batteries in the holders a...

Page 4: ...t expressly approved by the party responsible for compliance could void the user s authority to operate the equipment NOTE This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates u...

Reviews: