Digital Monitoring Products, Inc. | 1100T Wireless Translator Installation and Programming Guide
9
Walk Test
To test the system, perform a standard walk test. Non-DMP wireless devices are not
compatible with the DMP Wireless Walk Test. See the panel programming guides for
more information.
XR Series Panels
1.
Reset the control panel by placing and removing a jumper on
RESET
.
2. At the keypad, enter
8144
(WALK).
3. Select the zone type you want to test. An asterisk indicates the chosen zone
type. Press the select key or area again to deselect the zone type. When you
have selected all the zone types you want for testing, press
CMD
.
Note:
For the purpose of the Walk Test, do not select
WLS
or
PIR
. These
options are not compatible.
4. Select
BELL
. This option is for when a zone under test faults. This option
allows the panel bell, and/or burglary bell, and/or fire bell to turn on and then
off each time a zone is tripped.
•
NO
- Select for no bell output action during Walk Test.
•
YES
- Select to turn on any bell output for 2 seconds during Walk Test.
•
PULS
- Select to turn on any bell output for 1/4 second during Walk Test.
5. Once in the Walk Test, walk around and trip each protective device. Continue
tripping devices until the entire system is tested.
6. Press the select key or area directly below
END
to stop the Walk Test.
6