DLS PD408-AN10-277 User Manual Download Page 4

Wiring Notes

0

DO NOT EXCEED

 2216 W (8 Amps.) per dimmer output @ 277 VAC.

0

All wiring between the  control stations, dimmers, and other system 
controllers (network bus) is low voltage (NEMA Class 2) 

0

PD408-AN10-277

 dimmer packs may be fed by one or two 20 A 

(maximum) branch circuits and may have up to four separately dimmed 
loads.

0

Both breakers must be on the same power phase. 

0

CAUTION: DO NOT

 attempt to parallel outputs to increase capacity.

0

Installations must conform to local and/or NEC code requirements.

0

Each load must have its own Neutral wire for full load operation.

0

All line voltage wires must have copper conductors of adequate Gauge 
with 90

°

 C wire insulation.

0

POWER EACH LOAD DIRECTLY BEFORE CONNECTING IT TO THE 

PD408-AN10-277

 TO ENSURE PROPER WIRING.

PD408-AN10-277 General Wiring Instructions

Figure 7 -  PD408-AN10-277 Typical 277 VAC  Wiring.

User's Manual - Page 3

+

-

+

-

#

1

#

4

+

-

Control 

+

-

Analog 0-10V Control inputs

Figure 4 - PD408-AN10-277 Typical Control Wiring.

Control 

Optional: 
Could be also controlled  with 4x 100 KOHM potentiometers . 

+

-

+

-

#

2

#

3

+

-

Control 

+

-

Control 

PD408-AN10-277-UM

   - 10/12  

Copyright   2012 Digital Lighting Systems, All rights Reserved   Specifications are subject to change without notice.   

Printed

 in U.S.A.

12302 SW 128 Ct. ; Miami, FL 33186

Tel: 305-969-8442  

[email protected]

4x 2250 W.@ 277 V  Dimmer Pack

PD40

8

-AN10-277

Digital Lighting Systems, Inc.

Analog 0-10V control

DigitalLighting.com

2x20 A - 

220/240/277 VAC

Breakers

On Same Phase

Electrical

Distribution Panel

To Distribution Panel

Neutral Bus

LOAD #4

LOAD #3

LOAD #2

LOAD #1

ON

INT04

Control

Board

Load Driver Module

LDM

NEUTRAL

 BUS

1

2

N1

N2

N3

N4

N5

N6

3

4

SSR1

SSR2

SSR3

SSR4

H1

H2

SSR's OPTICAL

 ISOLA

T

ORS

9 V

AC

T

ransformer

J3

ON

For Full Load Operation Use:
#12 AWG copper conductor wire for Line & Neutral Feeds.
#14 AWG copper conductors in/out to each load.
Max. Load: 8 Amperes per output.

Earth Ground

20 Amps Max.

20 Amps Max.