DLG E-BOX-48100R LFP Battery User Manual
12
installation in a 19-inch cabinet. Vertical installation is similar. All
equipment must be steady during installation.
6.4.2 Connect Ground cable
Unscrew the screw at the grounding hole on the front panel of the
battery, wrap the ground cable around the screw, and tighten with a
screwdriver. Connect the other end of the ground cable to a reliable
ground point.
Note: The grounding resistance should be less than 1Ω.
6.4.3 Connecting the power cable
Before connecting the power cable, connect and disconnect the
cable to identify the positive and negative terminal, then make a mark
respectively. After the cable is connected, measure whether there is a
short line or reverse connection.
Connecting the power cables:
(1)
Power cable connection instructions of Single-Rack:
●
Single battery: Connect the positive pole of the battery to the positive
terminal of the DC port of the energy storage inverter (or the junction
box) with a red cable, and connect the negative pole of the battery to
the negative terminal of the DC port of the energy storage inverter (or