User manual for meter with U/I input PD72S
11.2. TRANSMISSION ERRORS DESCRIPTION
If an error occurs while write or read of single register, then the device sends an error code
according to Modbus RTU specifications (example message no 1).
Error codes:
01h
- illegal function (only functions 03h, 06h and 10h are available),
02h
- illegal register address
03h
- illegal data value
08h
- no write permission (see:
“
mbAc
” parameter)
A0h
- exceed of upper border of input range
60h
- exceed of lower border of input range
A0h and 60h codes can appear only during reg. 01h is reading by 03h function (read of a single
register).
11.3. EXAMPLES OF QUERY/ANSWER FRAMES
Examples apply for device with address 1. All values are represent hexadecimal.
Field description:
ADDR
Device address on modbus network
FUNC
Function code
REG H,L
Starting address (address of first register to read/write, Hi and Lo byte)
COUNT H,L
No. of registers to read/write (Hi and Lo byte)
BYTE C
Data byte count in answer frame
DATA H,L
Data byte (Hi and Lo byte)
CRC L,H
CRC error check (Hi and Lo byte)
1. Read of the displayed value (measurement), PD72S device address = 01h:
ADDR FUNC
REG H,L
COUNT H,L
CRC L,H
01
03
00
01
00
01
D5
CA
a) The answer (we assume that the measure result is not out of range):
ADDR FUNC
BYTE C
DATA H,L
CRC L,H
01
03
02
00
FF
F8
04
DATA H, L - displayed value = 255, no decimal point. Decimal point position can be
read from reg. 03h.
43