START-UP
Having performed the installation, it is recommended to wait for at least 30 minutes before starting the
system up, in order to allow the lubricant oil collection in the compressor.
Normally upon the system start-up only the evaporator fan is activated, purposed for the air recycling
inside the enclosure. The compressor and the external air fan are not activated, if the internal enclosure
temperature is lower than the one set on the thermostat. In order to test the system, it is necessary to
increase the enclosure internal temperature or decrease the set temperature (35°C set as a default by the
manufacturer).
At these conditions the compressor and the condenser fan are activated. The internal circulation fan must
be always functioning, while the external fan is activated and deactivated simultaneously with the
compressor.
Having tested the correct functioning of the system, it is necessary to set the internal temperature
thermostat to the required value (recommended value 35°C)
INITIAL TESTS AFTER START-UP
Make sure that the air coming from the condenser fan is not drawn back into the enclosure. Observe the
minimum distances specified at the figure below.