92
continually, the fault
code is 45-49
sure there is no any fault or
internal short circuit of the
loads.
And then restart the UPS. If
the problem persists, contact
the supplier.
Fault icon display,
audible buzzer alarm
continually, the fault
code is 50-54
Overload
Check the load level and
disconnect the non-critical
equipments, recount the
total capacity of your load
and reduce the load to the
UPS.
Check whether the load
equipments has fault or not.
Fault icon display,
audible buzzer alarm
continually, the fault
code is 55-59
Input NTC fault Contact the supplier.
Fault icon display,
audible buzzer alarm
continually, the fault
code is 60-64
Power fault
Check whether the input &
output power are normal or
not, contact the supplier if it
is abnormal.
Fault icon display,
audible buzzer alarm
continually, the fault
code is 65-69
Input fuse fault
Check if the input fuse is
burnt. Replace the old fuse
and restart the UPS. If the
problem persists, contact the
supplier.
Fault icon display,
audible buzzer alarm
continually, fan icon in
the LCD flickers
Fan fault
Check whether the fans are
connected and fixed well or
not, and if fans are not
broken. If all seems fine,
contact the supplier.
UPS fail to start when
operate ‘On’ key
Pressing time
too short
Press the power key more
than 2 seconds to start the
UPS.
The input
connection is
not ready or
Connect the input well, if the
battery voltage is too low,
disconnect the input and
Summary of Contents for SMALLT1
Page 1: ...User s Manual Small Tower 1000 3000 Uninterruptible Power Supply Small Tower 1000 3000 VA...
Page 2: ......
Page 7: ...5...
Page 8: ...6...
Page 9: ...7 1 SMALLT1 SMALLT2 SMALLT3 2 125167 4 8 6 9 7 800 250 52 63 service dkc ru...
Page 10: ...8 3 3 1 Small Tower 3 2 1...
Page 11: ...9 3 3 1 2 3 1 3 4 3 4 1 2 15 3 4 3 5...
Page 12: ...10...
Page 15: ...13 4 3 Small Tower IGBT VFI IEC EN62040 1 2...
Page 16: ...14 2 4 4 4 4 1 4 4 2...
Page 17: ...15 4 4 3 4 4 4 4 5 3 4 5 1...
Page 18: ...16 4 5 2 4 5 3 4 6 4 6 1...
Page 20: ...18 1 4 1 2 3 4 4 7 4 7 1 RS232 USB RS232 port 1 2 3 4 5 6 7 8 9...
Page 24: ...22 AS400 7 DB 9 5 24 DB9 AS400 11 D8 D6 D2 D8 D9 D2 D7 D8 D9 D1 D2 D8 K1 K1 7 DB 9...
Page 25: ...23 5 5 1 8 0 5 0 5 1 1 15 2 2...
Page 26: ...24 0 5 2 0 5 2 2 2 0 5 2 0 5 2 2 0 5 2 8...
Page 27: ...25 5 2 9 0 25 26 50 51 75 76 100 0 25 26 50 51 75 and 76 100...
Page 28: ...26 ECO CUCF 20 20 STDBY BYPASS LINE BAT BATT ECO SHUTDN CUCF 9 5 3 5 3 1 OFF ON...
Page 29: ...27 ON 0 5 ON 0 5 5 3 2 OFF 0 5 BPS ON OFF 7 5 4 2...
Page 30: ...28 3 8 5 4 ON ON Line...
Page 31: ...29 bat 4 ECO ECO ECO ECO ECO...
Page 32: ...30 CUCF CUCF CUCF 50 CUCF 80 60 CUCF 70 OFF 10 5 5 0 5 2...
Page 33: ...31 220 50 800 1 0 v1 7 40 220 50 24 100 11...
Page 34: ...32 5 6 2 0 5 2 0 5 2 0 5 2 1 2 0 5 2 208 220 230 240...
Page 35: ...33 9 8 9 9 10 10 2 10 5 dEF dEF 21 5 CF ON OFF 50 60 ON OFF...
Page 37: ...35 EPO EP EPO ON EPO OFF EPO 6 6 1 1 2 3...
Page 38: ...36 6 2 6 3 1 15 25 C 2 6 3...
Page 39: ...37 4 2 5 6 8 8 2 30 1 2 3 4 5...
Page 43: ...41 10 0 1 2 3 4 5 6 7 8 9 A B...
Page 44: ...42 C D E F 0 1 2 3 4 5 6 7 8 9 A B C D E F EEPROM Median 0 1 2 3 4 5 6 7 8 9 A B...
Page 45: ...43 C D E F 4 0 1 2 3 4 5 6 7 14 2000 7 2 11 00 14...
Page 46: ...44 15 24 25 39 40 44 10 45 49 50 54 55 59 NTC 60 64...
Page 47: ...45 65 69 On 2 3 15...
Page 50: ...48 13 SMALLT1A10 14 SMALLT2A5...
Page 51: ...49 15 SMALLT2A10 16 SMALLT3A5...
Page 52: ...50 17 SMALLT3A10...
Page 54: ...52 8 5 004 2011 020 2011 9 2 batt dkc ru service_center...
Page 55: ...53 8 800 250 52 63 service dkc ru www dkc ru...
Page 56: ...54...
Page 57: ...55 English language...
Page 58: ...56...
Page 99: ...97 Figure 15 Runtime graph of SMALLT2A5 Figure 16 Runtime graph of SMALLT2A10...
Page 100: ...98 Figure 17 Runtime graph of SMALLT3A5 Figure 18 Runtime graph of SMALLT3A10...
Page 103: ......
Page 104: ......