Wall Hang Bo lers User’s Installat on Manual
A suitable electrical connection is needed for the device to be able to operate correctly.
It must be grounded and gas installation and measurements need to be done.
The producer shall not be responsible for any damage caused by a fault grounding
system.It is suggested that the device is connected with a Y type connection and
1x2A B type key automatic circuit breaker. Be careful about the polarity in the connection.
It is recommended that if there is no residual current relay in the home installation,
1 phase 30mA leakage relay can be installed.
PHASE: Brown cable, NEUTRAL: Blue cable and GROUND: Yellow-Green cable.
Electric Connection
Room Thermostat
Your device is designed to be connected to a low voltage room thermostat. Connecting
230V voltage to the terminals of the room thermostat can cause repairable damages in the
electronic card. Both the room thermostat and the outdoor air sensor should be
connected to the terminals inside the device
Flue Connection
Your device is a C type device. For your connections and accessories, use the items of
authorized companies.Chimney segments are available in the end of the guidance. Keep
conditions mentioned in the guidance and ventilation processes in mind for different
chimney connections.
Condensing Discharge Connection
Make sure to connect the waste water connection of your device to a closed drain.
Any kind of open connections to the rooms strictly forbidden.You may use chemicals that
will neutralize waste water(to balance asdc level of the water) in accordance with the
regulations when necessary.
The appliance creates 25I/h app. PH:4,5 asdc condensing water as maximum level.It is
suggested to make ventilation against overows in the condensation drain.