FT7000, RACK MONITOR MANUAL 11033PA-ATEX
Maintenance
SERVICE SHOULD BE COMPLETED ONLY BY A QUALIFIED HAZARDOUS LOCATION TECHNICIAN.
LE SERVICE DOIT ÊTRE COMPLÉTÉ PAR UN TECHNICIEN QUALIFIÉ.
DO NOT OPEN ENCLOSURE WHILE UNIT IS ENERGIZED.
NE PAS OUVRIR LE BOÎTIER QUAND L’APPAREIL EST ALIMENTÉ.
DO NOT OPEN ENCLOSURE WHILE EXPLOSIVE ATMOSPHERE IS PRESENT.
NE PAS OUVRIR LE BOÎTIER DANS UN ENVIRONMENT EXPLOSIF.
DO NOT TOUCH OR CLEAN THE EQUIPMENT WHILE EXPLOSIVE ATMOSPHERE IS PRESENT.
NE TOUCHEZ PAS ET NETTOYEZ PAS L’ÉQUIPEMENT LORSQUE L’ÉQUIPEMENT EST DANS UN
ENVIRONNEMENT EXPLOSIF.
REPLACE PARTS WITH GENUINE DIXON OR APPROVED EQUIVALENT PARTS; SUBSTITUTION MAY
IMPAIR INTRINSIC SAFETY.
DIXON OU UN ÉQUIVALENT APPROUVÉ SONT LES SEULES RECOMMANDÉES POUR LE REMPLACEMENT
DES PIÈCES; LA SUBSTITUTION PEUT EMPÊCHER L’EFFICACITÉ ET LA SÉCURITÉ.
DO NOT REPAIR ANY FLAMEPROOF JOINTS; REPAIR MAY IMPAIR ENCLOSURE’S FLAMEPROOF
PROTECTION. CONTACT DIXON IF FLAMEPROOF JOINT IS DAMAGED.
NE RÉPAREZ PAS LES JOINTS À L’ÉPREUVE DES FLAMMES; CECI PEUT EMPÊCHER LA PROTECTION ANTI-
INFLAMMABLE DE LA PIÈCE. CONTACTEZ DIXON SI LE JOINT ANTI-INFLAMMABLE EST ENDOMMAGÉ.
The FT7000 has few parts that will require regular maintenance, however it is important to service
annually to extend the life of the monitor. Unsheltered units should be serviced in dry weather to
prevent rainwater from entering the enclosure and minimize moisture exposure.
1.
Once the unit has been powered down and hazardous gases have dissipated, remove the 12 lid
screws.
2.
Open the lid, then verify the O-ring gasket is in good condition and secured into the O-ring track.
If the O-ring is loose or damaged, replace and secure using ordinary superglue.
3.
Inspect the interior of the enclosure for condensation or pooled water. The presence of water
will cause corrosion and/or failure and should be fixed immediately.
If water or condensation is present, replace O-ring, inspect cable entry threads and reapply
corrosion inhibiting grease if needed. For conduit installations, verify the conduit-sealing fitting
is filled. For non-conduit installations, verify the cable gland is tightened properly to seal against
the cable jacket. If necessary, add sealing compound to fortify water tight seal. Re-inspect after
next rain to ensure water has not entered the enclosure. If water still enters enclosure, contact
Dixon support for further assistance.