Operating Instructions XWA11V
dIXEL
V8.8-KIT
9
Weiss Instruments,
LLC
. 905 Waverly Ave. Holtsville
, NY 11742 631-207-1200 www.weissinstruments.com
LHt Light
timer
: (0-255 min)
Amount of time the light will stay on after pressing the light switch on the
keyboard or after the door is closed.
FLH Light Flashing
: (0-5 min)
The light will “double flash” every 20 seconds during the FLH time period before
turning off after the LHt time.
This should only be enabled for use with incandesant or LED lighting!
doA Open door alarm delay
:(0-255 min) delay between the detection of the open door condition and its
alarm signaling: the flashing message “dA” is displayed.
oA1 First relay configuration: (14-15): ALr =
alarm;
LHt
= light;
onF =
on/off relay
oA2 Second relay configuration: (14-16): ALr =
alarm;
LHt
= light;
onF =
on/off relay
AOP Alarm relay polarity:
cL = closing contacts (Relay will close on alarm giving voltage output);
oP = opening contacts (Relay will open on alarm no voltage output).
i1P Digital input 1 polarity (1-2)
: CL : the digital input is activated by closing the contact;
OP: the digital input is activated by opening the contact
i1L
Door switch to turn light ON(1-2):
(y / n) To turn the light ON automatically when the door is open. The
light will turn off based on LHt . Keyboard switch must be turned ON first.
i1F
Digital input 1 operating mode(1-2): EAL
= external alarm;
dor
= door switch;
dFr
= A defrost is
running;
LHt
= keep light ON (signal from occupancy sensor) override LHt.;
i2P Digital input 2 polarity (1-3)
: CL : the digital input is activated by closing the contact;
OP: the digital input is activated by opening the contact
i2F Digital input 2 operating mode
: configure the digital input function:
EAL
= External alarm;
PAn
=Panic alarm;
dFr
= A defrost is running; (need external CT’s)
LHt
= Keep light ON (signal from occupancy sensor) overrides LHt.
did Time interval/delay for digital input alarm
:(0-255 min.) If I2F=EAL or PAn (external alarms), “did”
parameter defines the time delay between the detection and the successive signaling of the alarm.
tbA Alarm relay & Buzzer disabling:
(
y
;
no
)
Pbc Type of probe (PTC, NTC)
dP1 Probe 1 Temperature
rEL Software
release
for internal use.
Ptb Parameter table code:
read only.