Mt2  (Maximum) duration of defrost for program 2: 

(0÷255 min) When 

P2P = n

, no 

evaporator probe, it sets the defrost duration, when 

P2P = y

, defrost end based 

on temperature, it sets the maximum length for defrost. 

dFd Display during defrost:   dEF

 = “dEF” label; 

 

dEG

 = “dEG” label;

 

dSd  Start  defrost  delay

:(0÷59min)  This  is  useful  when  different  defrost  start  times 

are necessary to avoid overloading the plant.  

Fdt Drain down time:

 (0÷60 min.) time interval between reaching defrost termination 

temperature and the restoring of the control’s normal operation. This time allows 
the evaporator to eliminate water drops that might have formed due to defrost.

 

dPO First defrost after start-up:    y 

= Immediately; 

n

 = after the IdF time 

cFE    Condenser  fan  working  during  defrost  :  no 

=  condenser  fan  doesn‘t  run 

during defrost; 

yES

 = condenser fan runs during defrost 

EVAPORATOR FANS 
FnC Fan operating mode for program 1: 

C-n

 = running with the compressor, OFF during the defrost;  

C-y

 = running with the compressor, ON during the defrost; 

O-n

 = continuous mode, OFF during the defrost; 

O-y

 = continuous mode, ON during the defrost; 

FC2 Fan operating mode for program 2: 

C-n

 = running with the compressor, OFF during the defrost;  

C-y

 = running with the compressor, ON during the defrost; 

O-n

 = continuous mode, OFF during the defrost; 

O-y

 = continuous mode, ON during the defrost; 

Fnd Fan delay after defrost:

 (0÷255 min)

 

The time interval between the defrost end 

and evaporator fans start.

 

FSt  Fan stop temperature:

 (-50÷110°C; -58÷230°F) setting of temperature, detected 

by evaporator probe, above which the fan is always OFF. 

ALARMS 
ALU  High temperature alarm setting related to the SET1:

 (-50 

÷

 150°C) when this 

temperature is reached and after the ALd delay time the tAL alarm is enabled. 

 

Au2  High temperature alarm setting related to the SET2:

 (-50 

÷

 150°C) when this 

temperature is reached and after the ALd delay time the tAL alarm is enabled. 

ALd  Temperature alarm delay:

 (0÷255 min) time interval between the detection of 

an alarm condition and the corresponding alarm signalling. 

dAO Exclusion of temperature alarm at start-up

 

or after a defrost

: (from 0.0 min 

to 23.5h) time interval between the detection of the temperature alarm condition 
after instrument power on and alarm signalling. 

tbA  Alarm relay muting

: (

no

 = muting disabled: the alarm relay is active till the alarm 

condition lasts, 

yES

 = muting enabled: the alarm relay can be muting by pressing 

a key. 

oAP Alarm  relay  polarity:  CL 

=  contact  63-64  are  closed  when  an  alarm  happens. 

oP 

= contact 63-65 are closed when an alarm happens. 

ArE Alarm relay activated by first digital input (door switch):  

(

no 

=  the  digital  input  doesn’t  activate  the  alarm  relay; 

yES 

=  the  digital  input 

activates the alarm relay)  

 

PROBE INPUTS 
Ot  Thermostat  probe  calibration: 

(-12.0

÷

÷

÷

÷

12.0°C/  -21

÷

÷

÷

÷

21°F)  allows  to  adjust 

possible offset of the thermostat probe. 

P2P Evaporator  probe  presence:  no

=  not  present:  the  defrost  stops  only  by  time; 

yES=

 present: the defrost stops by temperature and time. 

OE   Evaporator  probe  calibration: 

(-12.0

÷

÷

÷

÷

12.0°C/  -21

÷

÷

÷

÷

21°F)  allows  to  adjust 

possible offsets of the evaporator probe. 

P3P Second evaporator probe presence: no

= not present: the defrost stops only by 

time; 

yES=

 present: the defrost stops by temperature and time. 

O3   Second  Evaporator  probe  calibration: 

(-12.0

÷

÷

÷

÷

12.0°C/  -21

÷

÷

÷

÷

21°F)  allows  to 

adjust possible offsets of the evaporator probe. 

 

 

 

DIGITAL INPUTS 
i1P  Door  switch  input  polarity:  CL

  :  the  digital  input  is  activated  by  closing  the 

contact; 

OP

 : the digital input is activated by opening the contact. 

i2P  Pressure switch digital input polarity:

 

 

CL

 : the digital input is activated by closing the contact;

 

 

OP

 : the digital input is activated by opening the contact 

i3P  Digital input polarity of the safety thermostat for defrost:

 

 

CL

 : the digital input is activated by closing the contact;

 

 

OP

 : the digital input is activated by opening the contact 

did  Time interval delay for the first digital input (door switch):

(0

÷

255 min.) “did” 

parameter  defines  the  time  delay  between  the  detection  and  the  successive 
signalling of the alarm at first digital input. 

 

TO SET CURRENT TIME AND WEEKLY HOLIDAYS (3SEC.

 

 

afterward

 

 )

 

Hur 

Current hour 

(0 ÷ 23 h) 

Min 

Current minute

 (0 ÷ 59min) 

dAY  Current day

 (Sun ÷ SAt) 

Hd1  First weekly holiday 

(Sun ÷ nu) Set the first day of the week which follows the 

holiday times. 

Hd2  Second  weekly  holiday 

(Sun  ÷  nu)  Set  the  second  day  of  the  week  which 

follows the holiday times. 

Hd3  Third  weekly  holiday 

(Sun ÷ nu) Set the third day of the week which follows 

the holiday times. 

N.B.   Hd1,Hd2,Hd3 

can be set also as

 “nu” 

value (Not Used) 

TO SET DEFROST TIMES (3SEC.

 

 

afterward

 

 )

 

Ld1÷Ld8 Workday defrost start for program 1

 (0 ÷ 23h 50 min.) These parameters 

set the beginning of the eight programmable defrost cycles during workdays. Ex. 
When 

Ld2

 = 12.4 the second defrost starts at 12.40 during workdays.  

Sd1÷Sd8 Holiday defrost start for program 1

 (0 ÷ 23h 50 min.) These parameters 

set  the  beginning  of  the  eight  programmable  defrost  cycles  on  holidays.  Ex. 
When 

Sd2

 = 3.4 the second defrost starts at 3.40 on holidays.  

N.B. : To disable a defrost cycle set it to “nu”(not used).  

Ex. 

 If

 Ld6

=nu

 ; 

 the sixth defrost cycle is disabled 

2L1÷2L8 Workday defrost start for program 2

 (0 ÷ 23h 50 min.) These parameters 

set the beginning of the eight programmable defrost cycles during workdays. Ex. 
When 

2L2

 = 12.4 the second defrost starts at 12.40 during workdays.  

2S1÷2S8 Holiday defrost start for program 2

 (0 ÷ 23h 50 min.) These parameters 

set  the  beginning  of  the  eight  programmable  defrost  cycles  on  holidays.  Ex. 
When 

2S2

 = 3.4 the second defrost starts at 3.40 on holidays.  

 
OTHER 
Adr  RS485  serial  address 

(1÷247)

Identifies  the  instrument  address  when 

connected to a ModBUS compatible monitoring system. 

onF  To  put  in  stand  by  the  instrument:  no= 

instrument  is  working. 

yES  = 

instrument is placed in standby mode. 

 

NOTE1: 

  changing  this  parameter  the  instrument  is  placed  in  STANDBY  mode 

when the programming is exited.  

 

***NOTE: to revert the instrument from stand by the standard working press 
for some seconds the SET key.**** 

rEL  Release software:

 (read only) Software version of the microprocessor. 

Ptb  Parameter  table:

  (read  only)  it  shows  the  original  code  of  the 

dIXEL

  parameter 

map. 

Prd    Probes  display: 

(read  only)  display  the  temperature  values  of  the  evaporator 

probe Pb2 and the auxiliary probe Pb3. 

DIGITAL INPUTS 

The XW562K can support 3 free contact digital inputs. 
The function of each one are described below. 

7.1 

DOOR SWITCH (TERMINALS 69-70) 

The digital input should be activated by closing the contact. The external alarm can be 
delayed by means of the 

did

 parameter.  

The recovery of this alarm type on the display is „

EA

“. By means of the 

ArE

 parameter 

can be chosen, either if there is the  message „EA“ on the display and the alarm relay 
is activated or if there is only the message „EA“ on the display.  
The alarm condition disappears as soon as the digital input is open. 
The polarity of this digital input is set in the 

i1P 

parameter. 

7.2 

PRESSURE SWITCH INPUT (TERMINALS 68-71) 

When the pressure switch is activated  the compressors are immediately stopped and 
the “PAL” message is displayed. The alarm relay is always activated.  
Condenser fans and evaporator fans continue working.  
If the pressure switch is activated during a hot gas defrost, the defrost is stopped. 

 

Standard regulation will restart 6min after the end of High pressure switch alarm. 
The polarity of this digital input is set in the 

i2P 

parameter. 

7.3 

SAFETY THERMOSTAT FOR DEFROST (TERMINALS 67-72) 

When this digital input is activated, the controller finishes the defrost immediately and 
goes to cooling operation.  
The  safety  thermostat  alarm  is  excluded  for  the  dAo  time  when  the  instrument  is 
switched on. 
The “

dEA

” alarm message is displayed and the alarm relay is activated.  

The next defrost starts at the next programmed defrost time, if the digital input is de-
activated. 
The polarity of this digital input is set in the 

i3P 

parameter. 

INSTALLATION AND MOUNTING 

Keyboard   

V650 

shall  be  mounted  on  vertical  panel,  in  a  72x56  mm  hole,  and  fixed 

using  screws 

  3  x  2mm.  To  obtain  an  IP65  protection  grade  use  the  front  panel 

rubber gasket (mod. RGW-V).  

Keyboard  

CX650 

shall be mounted on vertical panel, in a 29x71 mm hole, and fixed 

using the special bracket supplied.  

Power module 

XW562K

 shall be mounted in a panel with two or more screws and it 

must  be  connected  to  the  keyboard  by  means  of  a  two-wire  cable  (

  1mm).  The 

temperature range allowed for correct operation is 0 - 60 °C. Avoid places subject to 
strong  vibrations,  corrosive  gases,  excessive  dirt  or  humidity.  The  same 
recommendations apply to probes. Let the air circulate by the cooling holes. 

 
 

8.1  V650: CUT OUT   

 

56

72

40

83

,5

 

 

ELECTRICAL CONNECTIONS 

The instruments are provided with screw terminal block to connect cables with a cross 
section  up  to  2,5  mm

for  the  digital  and  analogue  inputs.  Relays  and  power  supply 