GENERAL WARNING 

1.1 

PLEASE READ BEFORE USING THIS MANUAL 

 

This  manual  is  part  of  the  product  and  should  be  kept  near  the  instrument  for 
easy and quick reference. 

 

The  instrument  shall  not  be  used  for  purposes  different  from  those  described 
hereunder. It cannot be used as a safety device. 

 

Check the application limits before proceeding. 

1.2 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do  not  expose  to  water  or  moisture:  use  the  controller only within the operating 
limits  avoiding  sudden  temperature  changes  with  high  atmospheric  humidity  to 
prevent  formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not 
be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or 
to “Dixell S.p.A.” (see address) with a detailed description of the fault. 

 

Consider  the  maximum  current  which  can  be  applied  to  each  relay  (see 
Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and 
far enough from each other, without crossing or intertwining. 

 

In  case  of  applications  in  industrial  environments,  the  use  of  mains  filters  (our 
mod. FT1) in parallel with inductive loads could be useful. 

GENERAL DESCRIPTION 

The 

XW562K

 series is fitted with a Real Time Clock which allows programming of up 

to eight daily defrost cycles, divided into holidays and workdays.  
Model 

XW562K

127x123

 mm format, is microprocessor based controller suitable for 

applications  on  medium  or  low  temperature  refrigerating  units.  It  is  provided with six 
relay outputs to control 2 compressors, defrost - which can be either electrical or hot 
gas    -  the  evaporator  fans,  the  condenser  fan  and  the  alarm  output.  They  are  also 
provided with 3 NTC probe inputs, one for temperature control, the other 2 to control 
the  defrost  end  temperature  of  the  evaporators.  There  are  3  digital  inputs  (free 
contact) for the door switch, the pressure switch and for safety end of defrost. 
The electronic controller can work with two parameter lists, switch over by a key. 
The  standard  TTL  output  allows  the  user  to  connect,  by  means  of  a  TTL/RS485 
external  module,  a 

ModBUS-RTU 

compatible  monitoring  system  and  to  programme 

the parameter list with the 

“Hot Key”.

 

The controller also provides an output for remote keyboard V650 

or CX650

.

 

CONTROLLING LOADS 

3.1 

THE COMPRESSORS 

The regulation is performed according to the temperature measured by the thermostat 
probe  with  a  positive  differential from the set point: if the temperature increases and 
reaches set point plus differential the compressor is started. The compressor is turned 
off when the temperature reaches the set point value again. 
In case of fault in the thermostat probe the start and stop of the compressor are timed 
through parameters “

COn

” and “

COF

”. 

3.2 

2

ND

 COMPRESSOR MANAGEMENT  

The  relay  of  the  second  compressor  is  activated  in  parallel  with  the  relay  of the first 
compressor, with a possible delay set in the 

AC1 

or 

AC2

 parameters, depending on 

program 1 or 2. Both the compressors are switched off at the same time. 

3.3 

DEFROST 

2  defrost  modes  are  available  through  the  “

tdF

”  parameter:  defrost  with  electrical 

heater  or  hot  gas.  The  defrost  interval  is  control  by  means  the  real  time  clock, 
depending  on  the  hours  set  in  the  parameters 

Ld1..Ld8

  on  workdays  and  in 

Sd1…Sd8

  in  holidays  for  program  1, 

2L1..  2L8

  on  workdays  and  in 

2S1…2S8

  in 

holidays for program 2. 
At the end of defrost the drip time is controlled through the “

Fdt

” parameter. 

3.4 

CONTROL OF EVAPORATOR FANS 

The fan control mode is selected by means of the “

FnC

” parameter for program 1 and 

Fn2

” parameter for program 2: 

C-n

  fans will switch ON and OFF with the compressor and

 not run

 during defrost; 

C-y

  fans will switch ON and OFF with the compressor, also during defrost  

After defrost, there is a timed fan delay allowing for drip time, set by means of the 
“Fnd” parameter. 

O-n

  fans will run continuously and

 not run

 during defrost; 

O-y

  fans will run continuously also during defrost 

 

An  additional  parameter  “FSt”  provides  the  setting  of  temperature,  detected  by  the 
evaporator  probe, above which the fans are always OFF. This can be used to make 
sure circulation of air only if his temperature is lower than set in “FSt”. 

3.5 

CONTROL OF CONDENSER FAN 

The condenser fan relay is always activated except during defrost. During the defrost 
the status of condenser fan depends on the 

cFE 

parameter: 

with 

cFE= no

 the condenser fan 

doesn’t run

 during defrost 

with 

cFE= yES

 the condenser fan 

runs

 during defrost 

 
 

KEYBOARD 

 

 

 

   

 

To display and modify target set point; in programming mode it selects a 
parameter or confirms an operation.  
By pressing it when the current time is displayed, it allows the User to re-
set the current time and three holidays. 
 

 

In  programming  mode  it  browses  the  parameter  codes  or  increases  the 
displayed value.  

 

in programming mode it browses the parameter codes or decreases the 
displayed value. 
By  holding  it  pressed  for  3s  the  current  time  is  displayed  and  it  permits 
the User to enter, Defrost and Clock parameter menu. 

 

 

 

 
By  holding  it  pressed  for  3s  the  defrost  is  started.  The  manual  defrost 
overrides the minimum running time of a compressor (“on” parameter) 
By  pressing  it  when  the  current  time  is  displayed,  it  allows  the  User    to 
set defrost times. 

 

 

Prg1

  Keep  it  pressed  for  2  seconds  to  switch  the  controller  from  the 

Program 2 to the Program 1.  

 

 

Prg2

  Keep  it  pressed  for  2  seconds  to  switch  the  controller  from  the 

Program 1 to the Program 2.  

 

KEY COMBINATIONS 

 

 

 

 

To lock and unlock the keyboard.

 

 

 

 

To enter the programming mode. 

 

 

 

 

To exit the programming mode.

 

4.1 

USE OF LEDS 

Each LED function is described in the following table. 

LED 

MODE 

Function 

 

ON 

The compressor 1 is running 

 

FLASHING 

- Programming Phase (flashing with 

- Anti-short cycle delay enabled  

 

ON 

The defrost is enabled 

 

FLASHING 

Programming Phase (flashing with 

)  

Drip time in progress 

 

ON 

The evaporator fan is running 

 

FLASHING 

The evaporator fan delay after defrost is running 

 

ON 

The compressor 2 is running 

 

FLASHING 

The second compressor delay is running 

 

ON 

Alarm is happening 

  

ON 

Condenser fan is running 

*** 

ON 

Prg1 is running 

ON 

Prg2 is running 

 